Functional Devices RIBL12SBM : Enclosed Mechanically Latching Relay, 20 Amp Contact Rating, Relay Contact Type: SPST + True Override, 12 Vac/dc Coil Voltage, Status LED, Auxiliary Output, NEMA 1 Housing
Functional Devices Latching Relays are switched by pulse commands from an appropriate power source or a controller. The relay contacts are mechanically latched in position, so that the load remains in its last state (on or off) during a loss of power. A pulse of opposing polarity latches the relay in the alternate state.
Specifications
# Relays & Contact Type: One (1) SPST Latching Relay Dual Coil
Expected Relay Life: 1 million cycles minimum mechanical
Operating Temperature: 30 to 140° F
Humidity Range: 5 to 95% (noncondensing)
Operate Time: 50ms
Maximum Pulse Length: 30 seconds
Relay Status / Auxiliary
Contact Closed: LED On = Voltage Detected on Load Wire
Dimensions: 2.30" x 3.20" x 1.80"with .50" NPT Nipple
Wires: 16", 600V Rated
Approvals: UL Listed, UL60947, C-UL, CE, RoHS
Housing Rating: UL Accepted for Use in Plenum, NEMA 1
Gold Flash: No
Override Switch: Yes
Contact Ratings:
20 Amp Resistive @ 120-277 Vac
20 Amp Ballast @ 120-277 Vac
16 Amp Electronic Ballast @ 120-277 Vac
5540WattTungsten @ 277Vac
720 VA Pilot Duty @ 120-277 Vac
2 HP @ 277 Vac
3 HP @ 240 Vac
1.5 HP @ 120 Vac
Coil Current:
182 mA @ 10 Vac
250 mA @ 12 Vac
165 mA @ 10 Vdc
198 mA @ 12 Vdc
250 mA @ 15 Vdc
Latch / Unlatch: Min. 20 Vdc / 22 Vac
Auxiliary Contact: 3 Amp @ 30 Vac/dc max.
Notes:
- Application of voltage on latch coil (Wht/Blu & Wht/Yel) will close the contact.
- Application of voltage on unlatch coil (Wht/Red & Wht/Yel) will open the contact.
- Auxiliary contact and status LED activate when 120-277 Vac is applied between
Load (Org) wire and Load Neutral (Wht/Blk) wire. - Voltage should not be applied to the coil for more than 30 seconds.
Datasheets
- Relay Coil Voltage:
- 12 Vac/dc
- Relays:
- 1
- Contacts:
- SPST
- Override Switch:
- Yes
- Auxiliary Output:
- Yes