The Omega DPS20-LV is an economical 1/8 DIN panel meter for load-cell and weighing applications, supplied with no I/O modules on the 11 to 60 Vdc / 24-48 Vac power input. It accepts 4- and 6-wire cells with configurable 5 or 10 Vdc excitation, characterizes the cell by sensitivity, nominal load and excitation, and lets you rescale reading units independently — all on a bright 6-digit red LED behind a NEMA 4 (IP65) front.
Specifications per the OMEGA DPS20 Series product datasheet and User’s Guide (M5760).
Overview
The OMEGA DPS20 brings high-performance load-cell metering to a compact 1/8 DIN panel-mount package. It accepts 4- and 6-wire cells and provides 5 Vdc and 10 Vdc configurable excitation to power the load cell, with two power supply options for high and low AC/DC supplies so the unit suits global installations. Independent scaling of the load-cell signal and reading units, prevention of false tares, stability alarms and a configurable rear terminal round out a meter built for real-world weighing.
Best for
- Assembly-line, batching and process weighing on a panel front
- Control panels and laboratory benches needing a compact load-cell readout
- Applications using 1, 2 or 3 mV/V cells on 4- or 6-wire connections
Key Features
Load-cell ready
Accepts 1, 2 and 3 mV/V cells on 4- or 6-wire connections with configurable 5 or 10 Vdc excitation — drives up to 8 standard 350 ohm cells at 5 Vdc, 4 at 10 Vdc.
Independent scaling
Characterize the cell by sensitivity, nominal load and excitation, then rescale reading units independently without re-characterizing the load cell.
0.05% FS accuracy
0.05% of full scale at 25 C with 50 ppm/C thermal stability, 20 Mohm input impedance and a recursive display filter for steady readings.
Smart tare
Configurable tare from the front key, rear terminal or auto-tare, with a maximum-tare limit that prevents undesired tares plus stability alarms.
Scalable I/O
Supplied with no output modules (display and front-key configuration only). Relays configure as max/min alarms with setpoint, hysteresis, delays, dual setpoints and latching.
NEMA 4 panel front
1/8 DIN bezel with NEMA 4 (IP65) front protection, plug-in screw terminals (male and female included) and 5 brightness levels with password protection.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | Omega DPS20-LV |
| Meter type | Load cell / strain-gage panel meter |
| Display digits | 6 (reading 999999 / -199999) |
| Digit height | 14 mm (0.55 in) |
| LED color | Red |
| Decimal point | Configurable |
| Load cell types | 1 mV/V, 2 mV/V, 3 mV/V and others |
| Wiring | 4-wire and 6-wire cells |
| Excitation voltage | 5 Vdc or 10 Vdc (configurable) |
| Max. excitation current | 140 mA |
| Cells driven (350 ohm) | 1 to 8 at 5 Vdc; 1 to 4 at 10 Vdc |
| Max. Vdc at input | +/-30 Vdc |
| Internal signal ranges | 100, 30, 20, 15, 10, 5 mV |
| Accuracy at 25 C | 0.05% FS |
| Thermal stability | 50 ppm/C |
| Input impedance | 20 Mohm |
| Acquisitions per sec | 16, 50 or 60 (configurable) |
| Step response (0-99%) | 17, 20 or 63 ms (configurable) |
| Power supply | 11 to 60 Vdc and 24/48 Vac (low-voltage, isolated 1500 Veff) |
| Output / control | no output modules (display and front-key configuration only) |
| Consumption | <1.5 W (meter) / <4.0 W (with options) |
| Configuration | Front keypad |
| External contact | Configurable function |
| Front protection | NEMA 4 (IP65) |
| Connections | Plug-in screw terminals (male and female included) |
| Mounting | Panel |
| Front size | 96 x 48 mm (1/8 DIN) |
| Panel cut-out | 92 x 44 mm |
| Depth | 91 mm (incl. terminals) |
| Operating temp range | 32 to 122 F (0 to 50 C) |
| Storage temp range | -4 to 158 F (-20 to 70 C) |
| Weight | 5.3 oz (150 g) |
Documentation
Related Products
Frequently Asked Questions
What load cells does the Omega DPS20 work with?
The DPS20 accepts 1, 2 and 3 mV/V load cells (and others) on 4- or 6-wire connections with configurable 5 or 10 Vdc excitation. At 5 Vdc it drives up to eight standard 350 ohm cells; at 10 Vdc, up to four.
How accurate is the DPS20?
Accuracy is 0.05% of full scale at 25 C, with 50 ppm/C thermal stability and 20 Mohm input impedance. Acquisition rate is configurable at 16, 50 or 60 readings per second.
What power supply does the DPS20-LV use?
This version uses the 11 to 60 Vdc and 24/48 Vac (low-voltage, isolated 1500 Veff) input. The low-voltage option suits 24/48 Vac and 11 to 60 Vdc panels.
Does it fit a standard 1/8 DIN cut-out?
Yes. The front bezel is 96 x 48 mm (1/8 DIN) with a 92 x 44 mm cut-out and 91 mm depth including terminals. Front protection is NEMA 4 (IP65); both male and female plug-in terminals are included.
- Series:
- DPS20
- Meter Type:
- Load Cell Panel Meter
- DIN Size:
- 1/8 DIN
- Display:
- 6-Digit Red LED
- Power Supply:
- Low Voltage (11-60 Vdc / 24-48 Vac)
- Relay Outputs:
- 0
- Analog Output:
- No
- Communication:
- None