null Skip to main content

Prolon PL-PN2-4C-7C : Pre-Wired Two Controller Panel with C1050 Boiler Controller and M2000 Boiler Controller, Isolation Relays, NEMA 1 Enclosure, UL Listed

Prolon

Your Price:  $3,936.86
(No reviews yet) Write a Review
SKU:
PL-PN2-4C-7C
Condition:
New
Availability:
Ships in 2-4 Days
Adding to cart… The item has been added

Controller 1

C1050 Boiler

Controller 2

M2000 Boiler

Supply

24 VAC, Class 2

Relays

17A @ 277 VAC

Protocol

Modbus RTU (RS485)

Panel

NEMA 1, UL listed

Overview

The Prolon PL-PN2-4C-7C is a pre-wired, UL listed NEMA 1 two controller panel built with a Prolon C1050 Boiler Controller and a Prolon M2000 Boiler Controller. Isolation relays rated 17A @ 277 VAC on all digital outputs, overcurrent fuse protection and clearly marked terminal blocks come factory wired.

The C1050 Boiler Controller operates staged boilers, as well as the associated pumps and valves. The M2000 Boiler Controller runs staged or modulating boiler sequences with their pumps. The panel contains 2 Modbus RTU (RS485) nodes and runs stand-alone or on a Prolon network of up to 127 nodes.

Specifications per Prolon Pre-Wired Two Controller Panel datasheet PL-DATA-PANEL2CON-EN-V1; Prolon PL-C1050-BLR Controller datasheet REV 7.3.0 / PL-DATA-C1050BLR-C/F-EN; Prolon PL-M2000-BLR Controller datasheet REV 7.3.0 / PL-DATA-M2000BLR-C/F-EN; Prolon C1050 Boiler Controller Hardware Guide REV 7.3.2; Prolon M2000 Series Quick Start Guide REV 7.0 / PL-QCK-M2000-EN; Prolon Two Controller Panel product page (proloncontrols.com) retrieved 2026-09-24. Reviewed September 2026.

Best For

  • Staged boiler plants with lead-lag boilers and pumps
  • Staged boiler plants up to 4 stages
  • Mechanical rooms where two controllers share one UL listed enclosure

Warranty

For warranty coverage on this Prolon panel, contact ZOT Supply at sales@zotsupply.com or 855-825-2811.

Key Features

Two independent controllers

Controllers need not be related in function and may each serve completely different sequences from separate power sources.

17A isolation relays

Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel (C1050 = 4, M2000 = 5), and the controller outputs are protected by resettable fuses.

Fused, pre-wired NEMA 1 panel

Clearly marked terminal blocks, wire management channels and a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included. The wiring diagram is in the door, and all inputs and outputs are tested in the factory.

C1050: Staged boiler sequencing

Operates staged boilers with their pumps and valves, with lead-lag sequences, outside temperature reset and pump exercise intervals.

M2000: Staged or modulating boilers

Wiring configurations cover staged boilers (4 boiler stage outputs plus pumps) and modulating boilers driven from the analog outputs.

Reflash to another program

Each controller keeps its full functionality, including the ability to reflash into a different controller program. Wiring diagrams are available free at proloncontrols.com.

Authorized Distributor

ZOT Supply is an authorized distributor of Prolon products.

Technical Specifications

Panel
ControllersProlon C1050, Boiler Controller program + Prolon M2000, Boiler Controller program
Supply24 VAC ±10%, 50/60 Hz, Class 2
Overcurrent ProtectionDisconnect-style Slo-Blo fuse (3A @ 250 VAC), with additional replacement fuse included
EnclosureNEMA 1
Panel Dimensions16.25 in. W x 20.25 in. H x 6.25 in. D (413 mm W x 514 mm H x 159 mm D)
Weight38 lbs (17.25 kg)
Isolation Relays17A @ 277 VAC on all digital outputs (C1050 = 4, M2000 = 5)
Network NodesStand-alone or networked (up to 127 nodes); this panel contains 2 nodes
Environment-4 to 122 °F (-20 to 50 °C), non-condensing
Panel CertificationComplete panel is UL certified
CertificationUL916 Energy Management Equipment, CAN/CSA-C22.2, RoHS, FCC part 15: 2012 class B
C1050 Controller Hardware
Power2 VA (consumption), 32 VA (input)
InputsOutside air: thermistor 10K; Return Water: 10 K thermistor; Supply Water: 10 K thermistor; Proof of pump: dry contact
Digital Outputs4 triac outputs, 10-30 VAC source or sink, 300 mA max (resettable fuse)
Analog Outputs1 output 0-10 VDC / 2-10 VDC / 0-5 VDC, 40 mA max (resettable fuse) for the valve
Indication Lights (LED)State of each output / Communication / Supply / State of microprocessor
CasingMolded ABS, UL94-HB
CommunicationModbus RTU (RS485), up to 127 nodes
Baud Rates9600, 19200, 38400, 57600, 76800, 115200
ConnectionRemovable screw-type terminal blocks (16 AWG max)
Boiler Controller Program
ProgramBoiler Controller
ApplicationOperates staged boilers, as well as the associated pumps and valves
Program InputsOutside air, return water and supply water: 10K thermistor; proof of pump: dry contact
Program Outputs4 triac outputs; analog output: 1 output 0-10 VDC / 2-10 VDC / 0-5 VDC for the valve
M2000 Controller Hardware
Power5 VA (consumption), 40 VA (input)
Inputs7 configurable analog inputs (outside temp / supply temp / return temp / dry contacts for proof of pumps, max heat request and boiler disable). Input signals (thermistor / dry contact / 4-20mA / 0-5 VDC) individually configurable for each input
Digital Outputs5 triac outputs, 10-30 VAC source, 300 mA max (resettable fuse)
Analog Outputs3 x 0-10 VDC outputs, 40 mA max (resettable fuse)
Indication Lights (LED)State of each output / Communication / Power / State of microprocessor
CasingMolded ABS, UL94-HB
CommunicationModbus RTU (RS485), up to 127 nodes
Baud Rates9600, 19200, 38400, 57600, 76800, 115200
ConnectionRemovable screw-type terminal blocks (16 AWG max) and RJ45 modular jacks
Boiler Controller Program
ProgramBoiler Controller
ApplicationRuns staged or modulating boiler sequences with their pumps
Program InputsOutside air, supply water and return water: 10K thermistor; proof of pump 1, proof of pump 2, use max heat setpoint and disable boiler call: dry contact
Program OutputsStaged: DO1-DO4 boiler stages, DO5 pump 1, AO1 pump 2, AO3 valve (0-10 / 2-10 / 0-5 VDC). Modulating: AO2 and AO3 modulating boiler stages (0-10 / 2-10 / 0-5 VDC)

Documentation

Frequently Asked Questions

What is the Prolon PL-PN2-4C-7C?

A pre-wired two controller panel built with a Prolon C1050 Boiler Controller and a Prolon M2000 Boiler Controller, in a UL listed NEMA 1 enclosure with 17A isolation relays on all digital outputs.

What does the C1050 boiler program control?

It operates staged boilers, as well as the associated pumps and valves. Strategies include outside temperature reset, lead-lag sequences and pump exercise intervals.

What does the M2000 boiler program control?

It runs staged or modulating boiler sequences with their pumps. Strategies include staged boiler configuration and modulating boiler configuration.

What power does the panel require?

24 VAC ±10%, 50/60 Hz, Class 2; the C1050 draws 2 VA (consumption), 32 VA (input) and the M2000 draws 5 VA (consumption), 40 VA (input).

Can the two controllers serve different equipment?

Yes. The controllers need not be related in function and may each serve completely different sequences from separate power sources.

Are the outputs isolated and protected?

Yes. Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel, and the panel has a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included.

What size is the PL-PN2-4C-7C panel?

16.25 in. W x 20.25 in. H x 6.25 in. D (413 mm W x 514 mm H x 159 mm D), and it weighs 38 lbs (17.25 kg).

Panel Type:
Dual Controller Panel
Display:
No Display
Controller Type:
Boiler
Communication:
Modbus RTU (RS485)