Controller 1
C1050 FlexIO
Controller 2
M2000 SZ Heat Pump
Supply
24 VAC, Class 2
Relays
17A @ 277 VAC
Protocol
Modbus RTU (RS485)
Panel
NEMA 1, UL listed
Overview
The Prolon PL-PN2-4F-7H is a pre-wired, UL listed NEMA 1 two controller panel built with a Prolon C1050 FlexIO Controller and a Prolon M2000 Single-Zone Heat Pump Controller. Isolation relays rated 17A @ 277 VAC on all digital outputs, overcurrent fuse protection and clearly marked terminal blocks come factory wired.
The C1050 FlexIO Controller is a general purpose HVAC controller whose inputs and outputs can be individually configured for applications not covered by a dedicated Prolon program. The M2000 Single-Zone Heatpump Controller operates residential or commercial heatpump equipment using PI control loops as a standalone controller that relies on the demand from a local sensor rather than acting as a master to zone controllers. The panel contains 2 Modbus RTU (RS485) nodes and runs stand-alone or on a Prolon network of up to 127 nodes.
Specifications per Prolon Pre-Wired Two Controller Panel datasheet PL-DATA-PANEL2CON-EN-V1; Prolon PL-C1050-FLX Controller datasheet REV 7.3.0 / PL-DATA-C1050FLX-C/F-EN; Prolon PL-M2000-HPS Controller datasheet REV 7.3.0 / PL-DATA-M2000HPS-C/F-EN; Prolon C1050 FlexIO Controller Hardware Guide REV 7.3.2; Prolon M2000 Heatpump Controller Hardware Guide (HP and HPS) REV 7.3.1; Prolon Two Controller Panel product page (proloncontrols.com) retrieved 2026-09-24. Reviewed September 2026.
Best For
- Outlying HVAC functions not covered by a dedicated Prolon program
- Single-zone heat pumps with a Prolon digital room sensor
- Mechanical rooms where two controllers share one UL listed enclosure
Warranty
For warranty coverage on this Prolon panel, contact ZOT Supply at sales@zotsupply.com or 855-825-2811.
Key Features
Two independent controllers
Controllers need not be related in function and may each serve completely different sequences from separate power sources.
17A isolation relays
Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel (C1050 = 4, M2000 = 5), and the controller outputs are protected by resettable fuses.
Fused, pre-wired NEMA 1 panel
Clearly marked terminal blocks, wire management channels and a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included. The wiring diagram is in the door, and all inputs and outputs are tested in the factory.
C1050: Up to 5 occupancy states
Can receive up to 5 different occupancy states from an NC2000, and outputs can act on any local input or on network data.
M2000: Local digital sensor
The INT port connects a Prolon digital temperature sensor, so the controller runs from local demand without zone controllers.
Reflash to another program
Each controller keeps its full functionality, including the ability to reflash into a different controller program. Wiring diagrams are available free at proloncontrols.com.
ZOT Supply is an authorized distributor of Prolon products.
Technical Specifications
| Panel | |
|---|---|
| Controllers | Prolon C1050, FlexIO Controller program + Prolon M2000, Single-Zone Heatpump Controller program |
| Supply | 24 VAC ±10%, 50/60 Hz, Class 2 |
| Overcurrent Protection | Disconnect-style Slo-Blo fuse (3A @ 250 VAC), with additional replacement fuse included |
| Enclosure | NEMA 1 |
| Panel Dimensions | 16.25 in. W x 20.25 in. H x 6.25 in. D (413 mm W x 514 mm H x 159 mm D) |
| Weight | 38 lbs (17.25 kg) |
| Isolation Relays | 17A @ 277 VAC on all digital outputs (C1050 = 4, M2000 = 5) |
| Network Nodes | Stand-alone or networked (up to 127 nodes); this panel contains 2 nodes |
| Environment | -4 to 122 °F (-20 to 50 °C), non-condensing |
| Panel Certification | Complete panel is UL certified |
| Certification | UL916 Energy Management Equipment, CAN/CSA-C22.2, RoHS, FCC part 15: 2012 class B |
| C1050 Controller Hardware | |
| Power | 2 VA (consumption), 32 VA (input) |
| Inputs | 3 analog inputs with individually configurable signal ranges (thermistor, dry contact, 0-5 VDC, 1-5 VDC, 0.5-4.5 VDC, 0-10 VDC), and 1 digital input |
| Digital Outputs | 4 triac outputs, 10-30 VAC source or sink, 300 mA max (resettable fuse) |
| Analog Outputs | 1 output 0-10 VDC / 2-10 VDC / 0-5 VDC, 40 mA max (resettable fuse) |
| Indication Lights (LED) | State of each output / Communication / Power / State of microprocessor |
| Casing | Molded ABS, UL94-HB |
| Communication | Modbus RTU (RS485), up to 127 nodes |
| Baud Rates | 9600, 19200, 38400, 57600, 76800, 115200 |
| Connection | Removable screw-type terminal blocks (16 AWG max) |
| FlexIO Controller Program | |
| Program | FlexIO Controller |
| Application | Is a general purpose HVAC controller whose inputs and outputs can be individually configured for applications not covered by a dedicated Prolon program |
| Program Outputs | 4 triac outputs; analog output: 1 output 0-10 VDC / 2-10 VDC / 0-5 VDC |
| M2000 Controller Hardware | |
| Power | 5 VA (consumption), 40 VA (input) |
| Inputs | 9 configurable analog inputs (outside temperature / return / supply / zone / water supply / dry contact for clogged filter / schedule override / proof of fan / alarm, room setpoint, static pressure). Input signals (thermistor / dry contact / 4-20mA / 0-5 VDC) individually configurable for each input |
| Digital Outputs | 5 triac outputs, 10-30 VAC source, 300 mA max (resettable fuse) |
| Analog Outputs | 3 x 0-10 VDC outputs, 40 mA max |
| Indication Lights (LED) | State of each output / Communication / Power / State of microprocessor |
| Casing | Molded ABS, UL94-HB |
| Communication | Modbus RTU (RS485) up to 127 nodes |
| Baud Rates | 9600, 19200, 38400, 57600, 76800, 115200 |
| Connection | Removable screw-type terminal blocks (max 16 AWG) and RJ45 modular jacks |
| Single-Zone Heatpump Controller Program | |
| Program | Single-Zone Heatpump Controller |
| Application | Operates residential or commercial heatpump equipment using PI control loops as a standalone controller that relies on the demand from a local sensor rather than acting as a master to zone controllers |
| Program Inputs | 9 configurable analog inputs (thermistor / dry contact / 4-20mA / 0-5 VDC); INT port connects a Prolon digital temperature sensor |
| Program Outputs | 3 x 0-10 VDC analog outputs, 40 mA max |
Documentation
Frequently Asked Questions
What is the Prolon PL-PN2-4F-7H?
A pre-wired two controller panel built with a Prolon C1050 FlexIO Controller and a Prolon M2000 Single-Zone Heat Pump Controller, in a UL listed NEMA 1 enclosure with 17A isolation relays on all digital outputs.
What does the C1050 flexio program control?
It is a general purpose HVAC controller whose inputs and outputs can be individually configured for applications not covered by a dedicated Prolon program. Strategies include ON/OFF, PI loop, direct or reverse acting, and pulsed output logic, output interlocks and overrides based on outside temperature and/or occupancy.
What does the M2000 single-zone heatpump program control?
It operates residential or commercial heatpump equipment using PI control loops as a standalone controller that relies on the demand from a local sensor rather than acting as a master to zone controllers. Strategies include bypass or VFD and outside air damper control, CO2 levels and schedule, unoccupied mode, morning warm-up and supply air pre-heating.
What power does the panel require?
24 VAC ±10%, 50/60 Hz, Class 2; the C1050 draws 2 VA (consumption), 32 VA (input) and the M2000 draws 5 VA (consumption), 40 VA (input).
Can the two controllers serve different equipment?
Yes. The controllers need not be related in function and may each serve completely different sequences from separate power sources.
Are the outputs isolated and protected?
Yes. Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel, and the panel has a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included.
What size is the PL-PN2-4F-7H panel?
16.25 in. W x 20.25 in. H x 6.25 in. D (413 mm W x 514 mm H x 159 mm D), and it weighs 38 lbs (17.25 kg).
- Panel Type:
- Dual Controller Panel
- Display:
- No Display
- Controller Type:
- FlexIO
- Controller Type:
- Heat Pump
- Communication:
- Modbus RTU (RS485)