Prolon PL-PN2-4G-7F : Pre-Wired Two Controller Panel with C1050 Zoning Heat Pump Controller and M2000 FlexIO Controller, Isolation Relays, NEMA 1 Enclosure, UL Listed

Prolon

Your Price:  $3,936.86
(No reviews yet) Write a Review
SKU:
PL-PN2-4G-7F
Condition:
New
Availability:
Ships in 2-4 Days
Adding to cart… The item has been added

Controller 1

C1050 Heat Pump

Controller 2

M2000 FlexIO

Supply

24 VAC, Class 2

Relays

17A @ 277 VAC

Protocol

Modbus RTU / BACnet MS/TP

Panel

NEMA 1, UL listed

Overview

The Prolon PL-PN2-4G-7F is a pre-wired, UL listed NEMA 1 two controller panel built with a Prolon C1050 Zoning Heat Pump Controller and a Prolon M2000 FlexIO Controller. Isolation relays rated 17A @ 277 VAC on all digital outputs, overcurrent fuse protection and clearly marked terminal blocks come factory wired.

The C1050 Zoning Heatpump Controller operates residential or commercial heatpump equipment using PI control loops, and acts as a master when networked with Prolon zone controllers. The M2000 FlexIO Controller is a general purpose HVAC controller whose inputs and outputs can be individually configured for applications not covered by a dedicated Prolon program. The panel contains 2 Modbus RTU (RS485) nodes and runs stand-alone or on a Prolon network of up to 127 nodes.

Specifications per Prolon Pre-Wired Two Controller Panel datasheet PL-DATA-PANEL2CON-EN-V1; Prolon PL-C1050-HP Controller datasheet REV 7.3.0 / PL-DATA-C1050HP-C/F-EN; Prolon PL-M2000-FLX Controller datasheet REV 7.3.0 / PL-DATA-M2000FLX-C/F-EN; Prolon C1050 Heatpump Controller Hardware Guide (HP and HPS) REV 7.3.2; Prolon M2000 FlexIO Controller Hardware Guide REV 7.3.0; Prolon Two Controller Panel product page (proloncontrols.com) retrieved 2026-09-24. Reviewed September 2026.

Best For

  • Zoned heat pump systems with Prolon zone controllers
  • Multi-point custom sequences needing 9 inputs
  • Mechanical rooms where two controllers share one UL listed enclosure

Warranty

For warranty coverage on this Prolon panel, contact ZOT Supply at sales@zotsupply.com or 855-825-2811.

Key Features

Two independent controllers

Controllers need not be related in function and may each serve completely different sequences from separate power sources.

17A isolation relays

Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel (C1050 = 4, M2000 = 5), and the controller outputs are protected by resettable fuses.

Fused, pre-wired NEMA 1 panel

Clearly marked terminal blocks, wire management channels and a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included. The wiring diagram is in the door, and all inputs and outputs are tested in the factory.

C1050: Zoning master

Acts as the master when used on a network with Prolon zone controllers, analyzing zone demand to drive the heat pump.

M2000: Up to 8 occupancy states

Can receive up to 8 different occupancy states from an NC2000, and outputs can act on any local input or on network data.

Reflash to another program

Each controller keeps its full functionality, including the ability to reflash into a different controller program. Wiring diagrams are available free at proloncontrols.com.

Authorized Distributor

ZOT Supply is an authorized distributor of Prolon products.

Technical Specifications

Panel
ControllersProlon C1050, Zoning Heatpump Controller program + Prolon M2000, FlexIO Controller program
Supply24 VAC ±10%, 50/60 Hz, Class 2
Overcurrent ProtectionDisconnect-style Slo-Blo fuse (3A @ 250 VAC), with additional replacement fuse included
EnclosureNEMA 1
Panel Dimensions16.25 in. W x 20.25 in. H x 6.25 in. D (413 mm W x 514 mm H x 159 mm D)
Weight38 lbs (17.25 kg)
Isolation Relays17A @ 277 VAC on all digital outputs (C1050 = 4, M2000 = 5)
Network NodesStand-alone or networked (up to 127 nodes); this panel contains 2 nodes
Environment-4 to 122 °F (-20 to 50 °C), non-condensing
Panel CertificationComplete panel is UL certified
CertificationUL916 Energy Management Equipment, CAN/CSA-C22.2, RoHS, FCC part 15: 2012 class B
C1050 Controller Hardware
Power2 VA (consumption), 32 VA (input)
Inputs4 configurable inputs with selectable functions (outside temp / return temp / supply temp / water intake temp / night setback / proof of fan / alarm)
Digital Outputs4 triac outputs, 10-30 VAC source, 300 mA max (resettable fuse)
Analog Outputs1 output 0-10 VDC / 2-10 VDC / 0-5 VDC, 40 mA max (resettable fuse)
Indication Lights (LED)State of each output / Communication / Power / State of microprocessor
CasingMolded ABS, UL94-HB
CommunicationModbus RTU (RS485) or BACnet MS/TP (RS485) up to 127 nodes
Baud Rates9600, 19200, 38400, 57600, 76800, 115200
ConnectionRemovable screw-type terminal blocks (16 AWG max)
Zoning Heatpump Controller Program
ProgramZoning Heatpump Controller
ApplicationOperates residential or commercial heatpump equipment using PI control loops, and acts as a master when networked with Prolon zone controllers
Program Outputs4 triac outputs, all set to SOURCE mode because they share a single source supply (the equipment transformer), 300 mA max (resettable fuse); analog output: 1 output 0-10 VDC / 2-10 VDC / 0-5 VDC
M2000 Controller Hardware
Power5 VA (consumption), 40 VA (input)
Inputs9 analog inputs with individually configurable signal ranges (thermistor, dry contact, 4-20mA, 0-20 mA, 0-5 VDC, 1-5 VDC, 0.5-4.5 VDC)
Digital Outputs5 triac outputs, 10-30 VAC source, 300 mA max (resettable fuse)
Analog Outputs3 x 0-10 VDC outputs, 40 mA max
Indication Lights (LED)State of each output / Communication / Power / State of microprocessor
CasingMolded ABS, UL94-HB
CommunicationModbus RTU (RS485), up to 127 nodes
Baud Rates9600, 19200, 38400, 57600, 76800, 115200
ConnectionRemovable screw-type terminal blocks (16 AWG max) and RJ45 modular jacks
FlexIO Controller Program
ProgramFlexIO Controller
ApplicationIs a general purpose HVAC controller whose inputs and outputs can be individually configured for applications not covered by a dedicated Prolon program
Program Inputs9 analog inputs with individually configurable signal ranges (thermistor, dry contact, 4-20mA, 0-5 VDC, 1-5 VDC, 0.5-4.5 VDC)
Program Outputs5 triac outputs; 3 x 0-10 VDC analog outputs, 40 mA max

Documentation

Frequently Asked Questions

What is the Prolon PL-PN2-4G-7F?

A pre-wired two controller panel built with a Prolon C1050 Zoning Heat Pump Controller and a Prolon M2000 FlexIO Controller, in a UL listed NEMA 1 enclosure with 17A isolation relays on all digital outputs.

What does the C1050 zoning heatpump program control?

It operates residential or commercial heatpump equipment using PI control loops, and acts as a master when networked with Prolon zone controllers. Strategies include unoccupied mode settings, morning warm-up and supply air pre-heating.

What does the M2000 flexio program control?

It is a general purpose HVAC controller whose inputs and outputs can be individually configured for applications not covered by a dedicated Prolon program. Strategies include ON/OFF, PI loop, and direct or reverse acting output logic, output interlocks and overrides based on outside temperature and/or occupancy.

What power does the panel require?

24 VAC ±10%, 50/60 Hz, Class 2; the C1050 draws 2 VA (consumption), 32 VA (input) and the M2000 draws 5 VA (consumption), 40 VA (input).

Can the two controllers serve different equipment?

Yes. The controllers need not be related in function and may each serve completely different sequences from separate power sources.

Are the outputs isolated and protected?

Yes. Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel, and the panel has a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included.

What size is the PL-PN2-4G-7F panel?

16.25 in. W x 20.25 in. H x 6.25 in. D (413 mm W x 514 mm H x 159 mm D), and it weighs 38 lbs (17.25 kg).

How are the C1050 digital outputs wired?

On the C1050 heat pump program, all triac outputs are set to SOURCE mode because they share a single source supply, the equipment transformer.

Does the C1050 heat pump controller support BACnet?

Yes. The C1050 heat pump controller communicates over Modbus RTU (RS485) or BACnet MS/TP (RS485), up to 127 nodes.

Panel Type:
Dual Controller Panel
Display:
No Display
Controller Type:
Heat Pump
Controller Type:
FlexIO
Communication:
Modbus RTU (RS485)
Communication:
BACnet MS/TP (RS485)