null Skip to main content

Prolon PL-PN2-4P-7J : Pre-Wired Two Controller Panel with C1050 Humidity Controller and M2000 Hydronic Controller, Isolation Relays, NEMA 1 Enclosure, UL Listed

Prolon

Your Price:  $3,936.86
(No reviews yet) Write a Review
SKU:
PL-PN2-4P-7J
Condition:
New
Availability:
Ships in 2-4 Days
Adding to cart… The item has been added

Controller 1

C1050 Humidity

Controller 2

M2000 Hydronic

Supply

24 VAC, Class 2

Relays

17A @ 277 VAC

Protocol

Modbus RTU (RS485)

Panel

NEMA 1, UL listed

Overview

The Prolon PL-PN2-4P-7J is a pre-wired, UL listed NEMA 1 two controller panel built with a Prolon C1050 Humidity Controller and a Prolon M2000 Hydronic Controller. Isolation relays rated 17A @ 277 VAC on all digital outputs, overcurrent fuse protection and clearly marked terminal blocks come factory wired.

The C1050 Humidity Controller regulates the relative humidity level in a room or return duct, with both humidification and dehumidification sequences. The M2000 Hydronic Controller controls a variety of water-to-water heatpumps and hydronic systems. The panel contains 2 Modbus RTU (RS485) nodes and runs stand-alone or on a Prolon network of up to 127 nodes.

Specifications per Prolon Pre-Wired Two Controller Panel datasheet PL-DATA-PANEL2CON-EN-V1; Prolon PL-C1050-HU Controller datasheet REV 7.3.1 / PL-DATA-C1050HU-C/F-EN; Prolon PL-M2000-HYD Controller datasheet REV 7.3.0 / PL-DATA-M2000HYD-C/F-EN; Prolon C1050 Humidifier Controller Hardware Guide REV 7.3.2; Prolon M2000 Hydronic Controller Hardware Guide REV 7.3.0; Prolon Two Controller Panel product page (proloncontrols.com) retrieved 2026-09-24. Reviewed September 2026.

Best For

  • Room or return duct humidity control
  • Water-to-water heat pump plants
  • Mechanical rooms where two controllers share one UL listed enclosure

Warranty

For warranty coverage on this Prolon panel, contact ZOT Supply at sales@zotsupply.com or 855-825-2811.

Key Features

Two independent controllers

Controllers need not be related in function and may each serve completely different sequences from separate power sources.

17A isolation relays

Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel (C1050 = 4, M2000 = 5), and the controller outputs are protected by resettable fuses.

Fused, pre-wired NEMA 1 panel

Clearly marked terminal blocks, wire management channels and a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included. The wiring diagram is in the door, and all inputs and outputs are tested in the factory.

C1050: Humidify and dehumidify

Humidification and dehumidification sequences, with outdoor temperature reset and a supply high humidity limit.

M2000: Hydronic sequence library

Sequences include hot and cold tank, dual recovery, single hot tank with open or closed boiler loop, and dual energy boilers.

Reflash to another program

Each controller keeps its full functionality, including the ability to reflash into a different controller program. Wiring diagrams are available free at proloncontrols.com.

Authorized Distributor

ZOT Supply is an authorized distributor of Prolon products.

Technical Specifications

Panel
ControllersProlon C1050, Humidity Controller program + Prolon M2000, Hydronic Controller program
Supply24 VAC ±10%, 50/60 Hz, Class 2
Overcurrent ProtectionDisconnect-style Slo-Blo fuse (3A @ 250 VAC), with additional replacement fuse included
EnclosureNEMA 1
Panel Dimensions16.25 in. W x 20.25 in. H x 6.25 in. D (413 mm W x 514 mm H x 159 mm D)
Weight38 lbs (17.25 kg)
Isolation Relays17A @ 277 VAC on all digital outputs (C1050 = 4, M2000 = 5)
Network NodesStand-alone or networked (up to 127 nodes); this panel contains 2 nodes
Environment-4 to 122 °F (-20 to 50 °C), non-condensing
Panel CertificationComplete panel is UL certified
CertificationUL916 Energy Management Equipment, CAN/CSA-C22.2, RoHS, FCC part 15: 2012 class B
C1050 Controller Hardware
Power2 VA (consumption), 32 VA (input)
InputsOutside air: thermistor 10K; Return/room humidity: 0-5 / 0-10 VDC; Supply humidity: 0-5 / 0-10 VDC; Proof of fan: dry contact
Digital Outputs2 triac outputs, 10-30 VAC source or sink, 300 mA max (resettable fuse)
Analog Outputs1 output 0-10 VDC / 2-10 VDC, 40 mA max (resettable fuse)
Indication Lights (LED)State of each output / Communication / Power / State of microprocessor
CasingMolded ABS, UL94-HB
CommunicationModbus RTU (RS485), up to 127 nodes
Baud Rates9600, 19200, 38400, 57600, 76800, 115200
ConnectionRemovable screw-type terminal blocks (max 16 AWG)
Humidity Controller Program
ProgramHumidity Controller
ApplicationRegulates the relative humidity level in a room or return duct, with both humidification and dehumidification sequences
Program InputsOutside air: 10K thermistor; return/room humidity and supply humidity: 0-5 / 0-10 VDC; proof of fan: dry contact
Program Outputs2 triac outputs, 10-30 VAC source or sink, 300 mA max (resettable fuse); analog output: 1 output 0-10 VDC / 2-10 VDC, 40 mA max (resettable fuse)
M2000 Controller Hardware
Power5 VA (consumption), 40 VA (Input)
Inputs9 configurable analog inputs whose roles vary according to the selected sequence. Input signals (thermistor / dry contact / 4-20mA / 0-5 VDC) individually configurable for each input
Digital Outputs5 triac outputs, 10-30 VAC source, 300 mA max (resettable fuse)
Analog Outputs3 x 0-10 VDC outputs, 40 mA max (resettable fuse)
Indication Lights (LED)State of each output / Communication / Power / State of microprocessor
CasingMolded ABS, UL94-HB
CommunicationModbus RTU (RS485), up to 127 nodes
Baud Rates9600, 19200, 38400, 57600, 76800, 115200
ConnectionRemovable screw-type terminal blocks (16 AWG max) and RJ45 modular jacks
Hydronic Controller Program
ProgramHydronic Controller
ApplicationControls a variety of water-to-water heatpumps and hydronic systems
Program Inputs9 configurable analog inputs (thermistor / dry contact / 4-20mA / 0-5 VDC)
Program Outputs5 triac outputs; 3 x 0-10 VDC analog outputs, 40 mA max (resettable fuse)

Documentation

Frequently Asked Questions

What is the Prolon PL-PN2-4P-7J?

A pre-wired two controller panel built with a Prolon C1050 Humidity Controller and a Prolon M2000 Hydronic Controller, in a UL listed NEMA 1 enclosure with 17A isolation relays on all digital outputs.

What does the C1050 humidity program control?

It regulates the relative humidity level in a room or return duct, with both humidification and dehumidification sequences. Strategies include outdoor temperature reset, unoccupied mode setpoint offsets, supply high humidity limit and fan reactivation request in night mode.

What does the M2000 hydronic program control?

It controls a variety of water-to-water heatpumps and hydronic systems. Strategies include hot and cold tank, dual recovery system, single hot tank with open or closed boiler loop and dual energy boilers.

What power does the panel require?

24 VAC ±10%, 50/60 Hz, Class 2; the C1050 draws 2 VA (consumption), 32 VA (input) and the M2000 draws 5 VA (consumption), 40 VA (input).

Can the two controllers serve different equipment?

Yes. The controllers need not be related in function and may each serve completely different sequences from separate power sources.

Are the outputs isolated and protected?

Yes. Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel, and the panel has a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included.

What size is the PL-PN2-4P-7J panel?

16.25 in. W x 20.25 in. H x 6.25 in. D (413 mm W x 514 mm H x 159 mm D), and it weighs 38 lbs (17.25 kg).

Panel Type:
Dual Controller Panel
Display:
No Display
Controller Type:
Humidity
Controller Type:
Hydronic
Communication:
Modbus RTU (RS485)