Controller 1
C1050 Humidity
Controller 2
M2000 Hydronic
Supply
24 VAC, Class 2
Relays
17A @ 277 VAC
Protocol
Modbus RTU (RS485)
Panel
NEMA 1, UL listed
Overview
The Prolon PL-PN2-4P-7J is a pre-wired, UL listed NEMA 1 two controller panel built with a Prolon C1050 Humidity Controller and a Prolon M2000 Hydronic Controller. Isolation relays rated 17A @ 277 VAC on all digital outputs, overcurrent fuse protection and clearly marked terminal blocks come factory wired.
The C1050 Humidity Controller regulates the relative humidity level in a room or return duct, with both humidification and dehumidification sequences. The M2000 Hydronic Controller controls a variety of water-to-water heatpumps and hydronic systems. The panel contains 2 Modbus RTU (RS485) nodes and runs stand-alone or on a Prolon network of up to 127 nodes.
Specifications per Prolon Pre-Wired Two Controller Panel datasheet PL-DATA-PANEL2CON-EN-V1; Prolon PL-C1050-HU Controller datasheet REV 7.3.1 / PL-DATA-C1050HU-C/F-EN; Prolon PL-M2000-HYD Controller datasheet REV 7.3.0 / PL-DATA-M2000HYD-C/F-EN; Prolon C1050 Humidifier Controller Hardware Guide REV 7.3.2; Prolon M2000 Hydronic Controller Hardware Guide REV 7.3.0; Prolon Two Controller Panel product page (proloncontrols.com) retrieved 2026-09-24. Reviewed September 2026.
Best For
- Room or return duct humidity control
- Water-to-water heat pump plants
- Mechanical rooms where two controllers share one UL listed enclosure
Warranty
For warranty coverage on this Prolon panel, contact ZOT Supply at sales@zotsupply.com or 855-825-2811.
Key Features
Two independent controllers
Controllers need not be related in function and may each serve completely different sequences from separate power sources.
17A isolation relays
Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel (C1050 = 4, M2000 = 5), and the controller outputs are protected by resettable fuses.
Fused, pre-wired NEMA 1 panel
Clearly marked terminal blocks, wire management channels and a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included. The wiring diagram is in the door, and all inputs and outputs are tested in the factory.
C1050: Humidify and dehumidify
Humidification and dehumidification sequences, with outdoor temperature reset and a supply high humidity limit.
M2000: Hydronic sequence library
Sequences include hot and cold tank, dual recovery, single hot tank with open or closed boiler loop, and dual energy boilers.
Reflash to another program
Each controller keeps its full functionality, including the ability to reflash into a different controller program. Wiring diagrams are available free at proloncontrols.com.
ZOT Supply is an authorized distributor of Prolon products.
Technical Specifications
| Panel | |
|---|---|
| Controllers | Prolon C1050, Humidity Controller program + Prolon M2000, Hydronic Controller program |
| Supply | 24 VAC ±10%, 50/60 Hz, Class 2 |
| Overcurrent Protection | Disconnect-style Slo-Blo fuse (3A @ 250 VAC), with additional replacement fuse included |
| Enclosure | NEMA 1 |
| Panel Dimensions | 16.25 in. W x 20.25 in. H x 6.25 in. D (413 mm W x 514 mm H x 159 mm D) |
| Weight | 38 lbs (17.25 kg) |
| Isolation Relays | 17A @ 277 VAC on all digital outputs (C1050 = 4, M2000 = 5) |
| Network Nodes | Stand-alone or networked (up to 127 nodes); this panel contains 2 nodes |
| Environment | -4 to 122 °F (-20 to 50 °C), non-condensing |
| Panel Certification | Complete panel is UL certified |
| Certification | UL916 Energy Management Equipment, CAN/CSA-C22.2, RoHS, FCC part 15: 2012 class B |
| C1050 Controller Hardware | |
| Power | 2 VA (consumption), 32 VA (input) |
| Inputs | Outside air: thermistor 10K; Return/room humidity: 0-5 / 0-10 VDC; Supply humidity: 0-5 / 0-10 VDC; Proof of fan: dry contact |
| Digital Outputs | 2 triac outputs, 10-30 VAC source or sink, 300 mA max (resettable fuse) |
| Analog Outputs | 1 output 0-10 VDC / 2-10 VDC, 40 mA max (resettable fuse) |
| Indication Lights (LED) | State of each output / Communication / Power / State of microprocessor |
| Casing | Molded ABS, UL94-HB |
| Communication | Modbus RTU (RS485), up to 127 nodes |
| Baud Rates | 9600, 19200, 38400, 57600, 76800, 115200 |
| Connection | Removable screw-type terminal blocks (max 16 AWG) |
| Humidity Controller Program | |
| Program | Humidity Controller |
| Application | Regulates the relative humidity level in a room or return duct, with both humidification and dehumidification sequences |
| Program Inputs | Outside air: 10K thermistor; return/room humidity and supply humidity: 0-5 / 0-10 VDC; proof of fan: dry contact |
| Program Outputs | 2 triac outputs, 10-30 VAC source or sink, 300 mA max (resettable fuse); analog output: 1 output 0-10 VDC / 2-10 VDC, 40 mA max (resettable fuse) |
| M2000 Controller Hardware | |
| Power | 5 VA (consumption), 40 VA (Input) |
| Inputs | 9 configurable analog inputs whose roles vary according to the selected sequence. Input signals (thermistor / dry contact / 4-20mA / 0-5 VDC) individually configurable for each input |
| Digital Outputs | 5 triac outputs, 10-30 VAC source, 300 mA max (resettable fuse) |
| Analog Outputs | 3 x 0-10 VDC outputs, 40 mA max (resettable fuse) |
| Indication Lights (LED) | State of each output / Communication / Power / State of microprocessor |
| Casing | Molded ABS, UL94-HB |
| Communication | Modbus RTU (RS485), up to 127 nodes |
| Baud Rates | 9600, 19200, 38400, 57600, 76800, 115200 |
| Connection | Removable screw-type terminal blocks (16 AWG max) and RJ45 modular jacks |
| Hydronic Controller Program | |
| Program | Hydronic Controller |
| Application | Controls a variety of water-to-water heatpumps and hydronic systems |
| Program Inputs | 9 configurable analog inputs (thermistor / dry contact / 4-20mA / 0-5 VDC) |
| Program Outputs | 5 triac outputs; 3 x 0-10 VDC analog outputs, 40 mA max (resettable fuse) |
Documentation
Frequently Asked Questions
What is the Prolon PL-PN2-4P-7J?
A pre-wired two controller panel built with a Prolon C1050 Humidity Controller and a Prolon M2000 Hydronic Controller, in a UL listed NEMA 1 enclosure with 17A isolation relays on all digital outputs.
What does the C1050 humidity program control?
It regulates the relative humidity level in a room or return duct, with both humidification and dehumidification sequences. Strategies include outdoor temperature reset, unoccupied mode setpoint offsets, supply high humidity limit and fan reactivation request in night mode.
What does the M2000 hydronic program control?
It controls a variety of water-to-water heatpumps and hydronic systems. Strategies include hot and cold tank, dual recovery system, single hot tank with open or closed boiler loop and dual energy boilers.
What power does the panel require?
24 VAC ±10%, 50/60 Hz, Class 2; the C1050 draws 2 VA (consumption), 32 VA (input) and the M2000 draws 5 VA (consumption), 40 VA (input).
Can the two controllers serve different equipment?
Yes. The controllers need not be related in function and may each serve completely different sequences from separate power sources.
Are the outputs isolated and protected?
Yes. Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel, and the panel has a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included.
What size is the PL-PN2-4P-7J panel?
16.25 in. W x 20.25 in. H x 6.25 in. D (413 mm W x 514 mm H x 159 mm D), and it weighs 38 lbs (17.25 kg).
- Panel Type:
- Dual Controller Panel
- Display:
- No Display
- Controller Type:
- Humidity
- Controller Type:
- Hydronic
- Communication:
- Modbus RTU (RS485)