null Skip to main content

Prolon PL-PN2-4N-7M : Pre-Wired Two Controller Panel with C1050 Single-Zone Rooftop Controller and M2000 Zoning Rooftop Controller, Isolation Relays, NEMA 1 Enclosure, UL Listed

Prolon

Your Price:  $3,936.86
(No reviews yet) Write a Review
SKU:
PL-PN2-4N-7M
Condition:
New
Availability:
Ships in 2-4 Days
Adding to cart… The item has been added

Controller 1

C1050 SZ RTU

Controller 2

M2000 RTU

Supply

24 VAC, Class 2

Relays

17A @ 277 VAC

Protocol

Modbus RTU (RS485)

Panel

NEMA 1, UL listed

Overview

The Prolon PL-PN2-4N-7M is a pre-wired, UL listed NEMA 1 two controller panel built with a Prolon C1050 Single-Zone Rooftop Controller and a Prolon M2000 Zoning Rooftop Controller. Isolation relays rated 17A @ 277 VAC on all digital outputs, overcurrent fuse protection and clearly marked terminal blocks come factory wired.

The C1050 Single-Zone Rooftop Controller operates a single-zone rooftop or other mechanical HVAC system from a Prolon digital temperature sensor. The M2000 Zoning Rooftop Controller operates rooftops or other mechanical HVAC systems using PI control loops, and acts as a master when used on a network with Prolon zone controllers. The panel contains 2 Modbus RTU (RS485) nodes and runs stand-alone or on a Prolon network of up to 127 nodes.

Specifications per Prolon Pre-Wired Two Controller Panel datasheet PL-DATA-PANEL2CON-EN-V1; Prolon PL-C1050-RTUS Controller datasheet REV 7.3.0 / PL-DATA-C1050RTUS-C/F-EN; Prolon PL-M2000-RTU Controller datasheet REV 7.3.1 / PL-DATA-M2000RTU-C/F-EN; Prolon C1050 Rooftop Controller Hardware Guide (RTU and RTUS) REV 7.3.3; Prolon M2000 Rooftop Controller Hardware Guide (RTU and RTUS) REV 7.5.1; Prolon Two Controller Panel product page (proloncontrols.com) retrieved 2026-09-24. Reviewed September 2026.

Best For

  • Single-zone rooftop units
  • Zoned rooftops with bypass or VFD control
  • Mechanical rooms where two controllers share one UL listed enclosure

Warranty

For warranty coverage on this Prolon panel, contact ZOT Supply at sales@zotsupply.com or 855-825-2811.

Key Features

Two independent controllers

Controllers need not be related in function and may each serve completely different sequences from separate power sources.

17A isolation relays

Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel (C1050 = 4, M2000 = 5), and the controller outputs are protected by resettable fuses.

Fused, pre-wired NEMA 1 panel

Clearly marked terminal blocks, wire management channels and a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included. The wiring diagram is in the door, and all inputs and outputs are tested in the factory.

C1050: Network schedule

The C1050-RTUS can receive a schedule from a network master, and uses a Prolon digital temperature sensor on its INT port.

M2000: Zoning master with schedule

Acts as the master for Prolon zone controllers and operates on a configurable schedule using an internal real time clock.

Reflash to another program

Each controller keeps its full functionality, including the ability to reflash into a different controller program. Wiring diagrams are available free at proloncontrols.com.

Authorized Distributor

ZOT Supply is an authorized distributor of Prolon products.

Technical Specifications

Panel
ControllersProlon C1050, Single-Zone Rooftop Controller program + Prolon M2000, Zoning Rooftop Controller program
Supply24 VAC ±10%, 50/60 Hz, Class 2
Overcurrent ProtectionDisconnect-style Slo-Blo fuse (3A @ 250 VAC), with additional replacement fuse included
EnclosureNEMA 1
Panel Dimensions16.25 in. W x 20.25 in. H x 6.25 in. D (413 mm W x 514 mm H x 159 mm D)
Weight38 lbs (17.25 kg)
Isolation Relays17A @ 277 VAC on all digital outputs (C1050 = 4, M2000 = 5)
Network NodesStand-alone or networked (up to 127 nodes); this panel contains 2 nodes
Environment-4 to 122 °F (-20 to 50 °C), non-condensing
Panel CertificationComplete panel is UL certified
CertificationUL916 Energy Management Equipment, CAN/CSA-C22.2, RoHS, FCC part 15: 2012 class B
C1050 Controller Hardware
Power2 VA (consumption), 32 VA (input)
InputsOutdoor: thermistor 10K; Return: thermistor 10K; Supply: thermistor 10K; External clock or Proof of fan: dry contact
Digital Outputs4 triac outputs, 10-30 VAC source or sink, 300 mA max (resettable fuse)
Analog Outputs1 output 0-10 VDC / 2-10 VDC / 0-5 VDC, 40 mA max (resettable fuse)
Indication Lights (LED)State of each output / Communication / Power / State of microprocessor
CasingMolded ABS, UL94-HB
CommunicationModbus RTU (RS485) up to 127 nodes
Baud Rates9600, 19200, 38400, 57600, 76800, 115200
ConnectionRemovable screw-type terminal blocks (max 16 AWG)
Single-Zone Rooftop Controller Program
ProgramSingle-Zone Rooftop Controller
ApplicationOperates a single-zone rooftop or other mechanical HVAC system from a Prolon digital temperature sensor
Program InputsOutdoor, return and supply: 10K thermistor; external clock or proof of fan: dry contact; INT port connects a Prolon digital temperature sensor, powered at 24 VAC
Program Outputs4 triac outputs, all set to SOURCE mode because they share a single source supply (the equipment transformer); analog output: 1 output 0-10 VDC / 2-10 VDC / 0-5 VDC
M2000 Controller Hardware
Power5 VA (consumption), 40 VA (input)
Inputs9 configurable analog inputs (outside temp /return / supply / mixed air / room, dry contact for clogged filter / schedule override / proof of fan / room setpoint / CO2 levels / static pressure / auxiliary temp). Input signals (thermistor / dry contact / 4-20mA / 0-5 VDC / RH%) individually configurable for each input
Digital Outputs5 triac outputs, 10-30 VAC source, 300 mA max (resettable fuse)
Analog Outputs3 x 0-10 VDC outputs, 40 mA max
Indication Lights (LED)State of each output / Communication / Power / State of microprocessor
CasingMolded ABS, UL94-HB
CommunicationModbus RTU (RS485) up to 127 nodes
Baud Rates9600, 19200, 38400, 57600, 76800, 115200
ConnectionRemovable screw-type terminal blocks (max 16 AWG) and RJ45 modular jacks
Zoning Rooftop Controller Program
ProgramZoning Rooftop Controller
ApplicationOperates rooftops or other mechanical HVAC systems using PI control loops, and acts as a master when used on a network with Prolon zone controllers
Program Inputs9 configurable analog inputs: outside, return, supply, mixed air and room temperature, clogged filter, schedule override, proof of fan, room setpoint, CO2, static pressure, auxiliary temp (thermistor / dry contact / 4-20mA / 0-5 VDC, RH%)
Program Outputs5 triac outputs; 3 x 0-10 VDC analog outputs, 40 mA max

Documentation

Frequently Asked Questions

What is the Prolon PL-PN2-4N-7M?

A pre-wired two controller panel built with a Prolon C1050 Single-Zone Rooftop Controller and a Prolon M2000 Zoning Rooftop Controller, in a UL listed NEMA 1 enclosure with 17A isolation relays on all digital outputs.

What does the C1050 single-zone rooftop program control?

It operates a single-zone rooftop or other mechanical HVAC system from a Prolon digital temperature sensor. Strategies include unoccupied mode settings, morning warm-up and supply air pre-heating and schedule received from a network master.

What does the M2000 zoning rooftop program control?

It operates rooftops or other mechanical HVAC systems using PI control loops, and acts as a master when used on a network with Prolon zone controllers. Strategies include bypass or VFD and outside air damper control, CO2 levels and schedule, unoccupied mode, morning warm-up and supply air pre-heating.

What power does the panel require?

24 VAC ±10%, 50/60 Hz, Class 2; the C1050 draws 2 VA (consumption), 32 VA (input) and the M2000 draws 5 VA (consumption), 40 VA (input).

Can the two controllers serve different equipment?

Yes. The controllers need not be related in function and may each serve completely different sequences from separate power sources.

Are the outputs isolated and protected?

Yes. Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel, and the panel has a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included.

What size is the PL-PN2-4N-7M panel?

16.25 in. W x 20.25 in. H x 6.25 in. D (413 mm W x 514 mm H x 159 mm D), and it weighs 38 lbs (17.25 kg).

How are the C1050 digital outputs wired?

On the C1050 rooftop program, all triac outputs are set to SOURCE mode because they share a single source supply, the equipment transformer.

Panel Type:
Dual Controller Panel
Display:
No Display
Controller Type:
Rooftop
Communication:
Modbus RTU (RS485)