Controller 1
M2000 Boiler
Controller 2
M2000 Chiller
Supply
24 VAC, Class 2
Relays
17A @ 277 VAC
Protocol
Modbus RTU (RS485)
Panel
NEMA 1, UL listed
Overview
The Prolon PL-PN2-7C-7D is a pre-wired, UL listed NEMA 1 two controller panel built with a Prolon M2000 Boiler Controller and a Prolon M2000 Chiller Controller. Isolation relays rated 17A @ 277 VAC on all digital outputs, overcurrent fuse protection and clearly marked terminal blocks come factory wired.
The M2000 Boiler Controller runs staged or modulating boiler sequences with their pumps. The M2000 Chiller Controller operates air cooled and water cooled chillers with up to four stages, as well as the associated system pumps. The panel contains 2 Modbus RTU (RS485) nodes and runs stand-alone or on a Prolon network of up to 127 nodes.
Specifications per Prolon Pre-Wired Two Controller Panel datasheet PL-DATA-PANEL2CON-EN-V1; Prolon PL-M2000-BLR Controller datasheet REV 7.3.0 / PL-DATA-M2000BLR-C/F-EN; Prolon PL-M2000-CHL Controller datasheet REV 7.3.4 / PL-DATA-M2000CHL-C/F-EN; Prolon M2000 Series Quick Start Guide REV 7.0 / PL-QCK-M2000-EN; Prolon M2000 Chiller Controller Hardware Guide REV 7.3.4; Prolon Two Controller Panel product page (proloncontrols.com) retrieved 2026-09-24. Reviewed September 2026.
Best For
- Staged boiler plants up to 4 stages
- Air cooled or water cooled chillers up to 4 stages
- Mechanical rooms where two controllers share one UL listed enclosure
Warranty
For warranty coverage on this Prolon panel, contact ZOT Supply at sales@zotsupply.com or 855-825-2811.
Key Features
Two independent controllers
Controllers need not be related in function and may each serve completely different sequences from separate power sources.
17A isolation relays
Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel (C1050 = 4, M2000 = 5), and the controller outputs are protected by resettable fuses.
Fused, pre-wired NEMA 1 panel
Clearly marked terminal blocks, wire management channels and a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included. The wiring diagram is in the door, and all inputs and outputs are tested in the factory.
M2000: Staged or modulating boilers
Wiring configurations cover staged boilers (4 boiler stage outputs plus pumps) and modulating boilers driven from the analog outputs.
M2000: Up to 4 chiller stages
Regulates chilled water supply temperature on air cooled and water cooled chillers with up to four stages, with condenser water and water pressure inputs.
Reflash to another program
Each controller keeps its full functionality, including the ability to reflash into a different controller program. Wiring diagrams are available free at proloncontrols.com.
ZOT Supply is an authorized distributor of Prolon products.
Technical Specifications
| Panel | |
|---|---|
| Controllers | Prolon M2000, Boiler Controller program + Prolon M2000, Chiller Controller program |
| Supply | 24 VAC ±10%, 50/60 Hz, Class 2 |
| Overcurrent Protection | Disconnect-style Slo-Blo fuse (3A @ 250 VAC), with additional replacement fuse included |
| Enclosure | NEMA 1 |
| Panel Dimensions | 16.25 in. W x 20.25 in. H x 6.25 in. D (413 mm W x 514 mm H x 159 mm D) |
| Weight | 38 lbs (17.25 kg) |
| Isolation Relays | 17A @ 277 VAC on all digital outputs (C1050 = 4, M2000 = 5) |
| Network Nodes | Stand-alone or networked (up to 127 nodes); this panel contains 2 nodes |
| Environment | -4 to 122 °F (-20 to 50 °C), non-condensing |
| Panel Certification | Complete panel is UL certified |
| Certification | UL916 Energy Management Equipment, CAN/CSA-C22.2, RoHS, FCC part 15: 2012 class B |
| M2000 Controller Hardware | |
| Power | 5 VA (consumption), 40 VA (input) |
| Inputs | 7 configurable analog inputs (outside temp / supply temp / return temp / dry contacts for proof of pumps, max heat request and boiler disable). Input signals (thermistor / dry contact / 4-20mA / 0-5 VDC) individually configurable for each input |
| Digital Outputs | 5 triac outputs, 10-30 VAC source, 300 mA max (resettable fuse) |
| Analog Outputs | 3 x 0-10 VDC outputs, 40 mA max (resettable fuse) |
| Indication Lights (LED) | State of each output / Communication / Power / State of microprocessor |
| Casing | Molded ABS, UL94-HB |
| Communication | Modbus RTU (RS485), up to 127 nodes |
| Baud Rates | 9600, 19200, 38400, 57600, 76800, 115200 |
| Connection | Removable screw-type terminal blocks (16 AWG max) and RJ45 modular jacks |
| Boiler Controller Program | |
| Program | Boiler Controller |
| Application | Runs staged or modulating boiler sequences with their pumps |
| Program Inputs | Outside air, supply water and return water: 10K thermistor; proof of pump 1, proof of pump 2, use max heat setpoint and disable boiler call: dry contact |
| Program Outputs | Staged: DO1-DO4 boiler stages, DO5 pump 1, AO1 pump 2, AO3 valve (0-10 / 2-10 / 0-5 VDC). Modulating: AO2 and AO3 modulating boiler stages (0-10 / 2-10 / 0-5 VDC) |
| M2000 Controller Hardware | |
| Power | 5 VA (consumption), 40 VA (input) |
| Inputs | 9 analog inputs (outside temp / supply water temp / return water temp / dry contacts for proof of pumps, entering condenser water temp, leaving condenser water temp, water pressure and alarm). Input signals (thermistor / dry contact / 4-20mA / 0-5 VDC) individually configurable for each input |
| Digital Outputs | 5 triac outputs, 10-30 VAC source, 300 mA max (resettable fuse) |
| Analog Outputs | 3 x 0-10 VDC outputs, 40 mA max (resettable fuse) |
| Indication Lights (LED) | State of each output / Communication / Power / State of microprocessor |
| Casing | Molded ABS, UL94-HB |
| Communication | Modbus RTU (RS485), up to 127 nodes |
| Baud Rates | 9600, 19200, 38400, 57600, 76800, 115200 |
| Connection | Removable screw-type terminal blocks (16 AWG max) and RJ45 modular jacks |
| Chiller Controller Program | |
| Program | Chiller Controller |
| Application | Operates air cooled and water cooled chillers with up to four stages, as well as the associated system pumps |
| Program Inputs | 9 analog inputs: outside temp, supply water temp, return water temp, proof of pumps (dry contact), entering condenser water temp, leaving condenser water temp, water pressure and alarm |
| Program Outputs | 5 triac outputs; 3 x 0-10 VDC analog outputs, 40 mA max (resettable fuse) |
Documentation
Frequently Asked Questions
What is the Prolon PL-PN2-7C-7D?
A pre-wired two controller panel built with a Prolon M2000 Boiler Controller and a Prolon M2000 Chiller Controller, in a UL listed NEMA 1 enclosure with 17A isolation relays on all digital outputs.
What does the M2000 boiler program control?
It runs staged or modulating boiler sequences with their pumps. Strategies include staged boiler configuration and modulating boiler configuration.
What does the M2000 chiller program control?
It operates air cooled and water cooled chillers with up to four stages, as well as the associated system pumps. Strategies include outside temperature reset scales, lead-lag sequences and pump exercise intervals.
What power does the panel require?
24 VAC ±10%, 50/60 Hz, Class 2; each M2000 draws 5 VA (consumption), 40 VA (input).
Can the two controllers serve different equipment?
Yes. The controllers need not be related in function and may each serve completely different sequences from separate power sources.
Are the outputs isolated and protected?
Yes. Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel, and the panel has a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included.
What size is the PL-PN2-7C-7D panel?
16.25 in. W x 20.25 in. H x 6.25 in. D (413 mm W x 514 mm H x 159 mm D), and it weighs 38 lbs (17.25 kg).
- Panel Type:
- Dual Controller Panel
- Display:
- No Display
- Controller Type:
- Boiler
- Controller Type:
- Chiller
- Communication:
- Modbus RTU (RS485)