Controller 1
M2000 SZ Heat Pump
Controller 2
M2000 MUA
Supply
24 VAC, Class 2
Relays
17A @ 277 VAC
Protocol
Modbus RTU (RS485)
Panel
NEMA 1, UL listed
Overview
The Prolon PL-PN2-7H-7K is a pre-wired, UL listed NEMA 1 two controller panel built with a Prolon M2000 Single-Zone Heat Pump Controller and a Prolon M2000 Make-Up Air (Standard) Controller. Isolation relays rated 17A @ 277 VAC on all digital outputs, overcurrent fuse protection and clearly marked terminal blocks come factory wired.
The M2000 Single-Zone Heatpump Controller operates residential or commercial heatpump equipment using PI control loops as a standalone controller that relies on the demand from a local sensor rather than acting as a master to zone controllers. The M2000 Air Make Up Controller operates a variety of make-up air units and systems. The panel contains 2 Modbus RTU (RS485) nodes and runs stand-alone or on a Prolon network of up to 127 nodes.
Specifications per Prolon Pre-Wired Two Controller Panel datasheet PL-DATA-PANEL2CON-EN-V1; Prolon PL-M2000-HPS Controller datasheet REV 7.3.0 / PL-DATA-M2000HPS-C/F-EN; Prolon PL-M2000-MUA Controller datasheet REV 7.3.0 / PL-DATA-M2000MUA-C/F-EN; Prolon M2000 Heatpump Controller Hardware Guide (HP and HPS) REV 7.3.1; Prolon M2000 Air Make Up Controller Hardware Guide REV 7.3.0; Prolon Two Controller Panel product page (proloncontrols.com) retrieved 2026-09-24. Reviewed September 2026.
Best For
- Single-zone heat pumps with a Prolon digital room sensor
- Make-up air units with building pressure control
- Mechanical rooms where two controllers share one UL listed enclosure
Warranty
For warranty coverage on this Prolon panel, contact ZOT Supply at sales@zotsupply.com or 855-825-2811.
Key Features
Two independent controllers
Controllers need not be related in function and may each serve completely different sequences from separate power sources.
17A isolation relays
Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel (C1050 = 4, M2000 = 5), and the controller outputs are protected by resettable fuses.
Fused, pre-wired NEMA 1 panel
Clearly marked terminal blocks, wire management channels and a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included. The wiring diagram is in the door, and all inputs and outputs are tested in the factory.
M2000: Local digital sensor
The INT port connects a Prolon digital temperature sensor, so the controller runs from local demand without zone controllers.
M2000: Standard MUA configuration
Standard make-up air panel without the additional door hardware (selector switch, door LEDs and lockout reset button).
Reflash to another program
Each controller keeps its full functionality, including the ability to reflash into a different controller program. Wiring diagrams are available free at proloncontrols.com.
ZOT Supply is an authorized distributor of Prolon products.
Technical Specifications
| Panel | |
|---|---|
| Controllers | Prolon M2000, Single-Zone Heatpump Controller program + Prolon M2000, Air Make Up Controller program |
| Supply | 24 VAC ±10%, 50/60 Hz, Class 2 |
| Overcurrent Protection | Disconnect-style Slo-Blo fuse (3A @ 250 VAC), with additional replacement fuse included |
| Enclosure | NEMA 1 |
| Panel Dimensions | 16.25 in. W x 20.25 in. H x 6.25 in. D (413 mm W x 514 mm H x 159 mm D) |
| Weight | 38 lbs (17.25 kg) |
| Isolation Relays | 17A @ 277 VAC on all digital outputs (C1050 = 4, M2000 = 5) |
| Network Nodes | Stand-alone or networked (up to 127 nodes); this panel contains 2 nodes |
| Environment | -4 to 122 °F (-20 to 50 °C), non-condensing |
| Panel Certification | Complete panel is UL certified |
| Certification | UL916 Energy Management Equipment, CAN/CSA-C22.2, RoHS, FCC part 15: 2012 class B |
| M2000 Controller Hardware | |
| Power | 5 VA (consumption), 40 VA (input) |
| Inputs | 9 configurable analog inputs (outside temperature / return / supply / zone / water supply / dry contact for clogged filter / schedule override / proof of fan / alarm, room setpoint, static pressure). Input signals (thermistor / dry contact / 4-20mA / 0-5 VDC) individually configurable for each input |
| Digital Outputs | 5 triac outputs, 10-30 VAC source, 300 mA max (resettable fuse) |
| Analog Outputs | 3 x 0-10 VDC outputs, 40 mA max |
| Indication Lights (LED) | State of each output / Communication / Power / State of microprocessor |
| Casing | Molded ABS, UL94-HB |
| Communication | Modbus RTU (RS485) up to 127 nodes |
| Baud Rates | 9600, 19200, 38400, 57600, 76800, 115200 |
| Connection | Removable screw-type terminal blocks (max 16 AWG) and RJ45 modular jacks |
| Single-Zone Heatpump Controller Program | |
| Program | Single-Zone Heatpump Controller |
| Application | Operates residential or commercial heatpump equipment using PI control loops as a standalone controller that relies on the demand from a local sensor rather than acting as a master to zone controllers |
| Program Inputs | 9 configurable analog inputs (thermistor / dry contact / 4-20mA / 0-5 VDC); INT port connects a Prolon digital temperature sensor |
| Program Outputs | 3 x 0-10 VDC analog outputs, 40 mA max |
| M2000 Controller Hardware | |
| Power | 5 VA (consumption), 40 VA (input) |
| Inputs | 9 configurable analog inputs (zone temp / outside temp / discharge temp, dry contact for proof of exhaust, fan and damper opening, manual overrides, CO2 levels, static pressure). Input signals (thermistor / dry contact / 4-20mA / 0-5 VDC) individually configurable for each input |
| Digital Outputs | 5 triac outputs, 10-30 VAC source, 300 mA max (resettable fuse) |
| Analog Outputs | 3 x 0-10 VDC outputs, 40 mA max (resettable fuse) |
| Indication Lights (LED) | State of each output / Communication / Power / State of microprocessor |
| Casing | Molded ABS, UL94-HB |
| Communication | Modbus RTU (RS485), up to 127 nodes |
| Baud Rates | 9600, 19200, 38400, 57600, 76800, 115200 |
| Connection | Removable screw-type terminal blocks (16 AWG max) and RJ45 modular jacks |
| Air Make Up Controller Program | |
| Program | Air Make Up Controller |
| Application | Operates a variety of make-up air units and systems |
| Program Inputs | 9 configurable analog inputs: zone temp, outside temp, discharge temp, proof of exhaust, fan and damper opening (dry contact), manual overrides, CO2 levels, static pressure (thermistor / dry contact / 4-20mA / 0-5 VDC) |
| Program Outputs | 5 triac outputs; 3 x 0-10 VDC analog outputs, 40 mA max (resettable fuse) |
| Panel Version | MUA Standard: without additional hardware (selector, LEDs, lockout reset button) |
Documentation
Frequently Asked Questions
What is the Prolon PL-PN2-7H-7K?
A pre-wired two controller panel built with a Prolon M2000 Single-Zone Heat Pump Controller and a Prolon M2000 Make-Up Air (Standard) Controller, in a UL listed NEMA 1 enclosure with 17A isolation relays on all digital outputs.
What does the M2000 single-zone heatpump program control?
It operates residential or commercial heatpump equipment using PI control loops as a standalone controller that relies on the demand from a local sensor rather than acting as a master to zone controllers. Strategies include bypass or VFD and outside air damper control, CO2 levels and schedule, unoccupied mode, morning warm-up and supply air pre-heating.
What does the M2000 air make up program control?
It operates a variety of make-up air units and systems. Strategies include outdoor temperature reset, building pressure control, CO2 control and lockout mode and safety limits.
What power does the panel require?
24 VAC ±10%, 50/60 Hz, Class 2; each M2000 draws 5 VA (consumption), 40 VA (input).
Can the two controllers serve different equipment?
Yes. The controllers need not be related in function and may each serve completely different sequences from separate power sources.
Are the outputs isolated and protected?
Yes. Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel, and the panel has a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included.
What size is the PL-PN2-7H-7K panel?
16.25 in. W x 20.25 in. H x 6.25 in. D (413 mm W x 514 mm H x 159 mm D), and it weighs 38 lbs (17.25 kg).
Does the panel include make-up air door controls?
No. The K selection is the standard make-up air configuration, without the additional hardware (selector, LEDs, lockout reset button). The L selection adds it.
- Panel Type:
- Dual Controller Panel
- Display:
- No Display
- Controller Type:
- Heat Pump
- Controller Type:
- Make-Up Air
- Communication:
- Modbus RTU (RS485)