Controller 1
NC2000 HMI
Controller 2
M2000 Boiler
Supply
24 VAC, Class 2
Relays
17A @ 277 VAC
Protocol
Modbus RTU / TCP/IP
Panel
NEMA 1, UL listed
Overview
The Prolon PL-PN2-1A-7C is a pre-wired, UL listed NEMA 1 two controller panel built with a Prolon NC2000 Network Controller with 10-Inch Touchscreen HMI and a Prolon M2000 Boiler Controller. Isolation relays rated 17A @ 277 VAC on all digital outputs, overcurrent fuse protection and clearly marked terminal blocks come factory wired.
The NC2000 connects the Prolon network to the internet, manages the occupancy schedule and outside temperature, sends email alerts and records trend logs, with a built-in 10-inch touchscreen for local setup. The M2000 Boiler Controller runs staged or modulating boiler sequences with their pumps. The panel contains 2 Modbus RTU (RS485) nodes and runs stand-alone or on a Prolon network of up to 127 nodes.
Specifications per Prolon Pre-Wired Two Controller Panel datasheet PL-DATA-PANEL2CON-EN-V1; Prolon PL-M2000-BLR Controller datasheet REV 7.3.0 / PL-DATA-M2000BLR-C/F-EN; Prolon M2000 Series Quick Start Guide REV 7.0 / PL-QCK-M2000-EN; Prolon Two Controller Panel product page (proloncontrols.com) retrieved 2026-09-24; Prolon NC2000 Network Controller datasheet REV 7.3.0 / PL-DATA-NC2000-C/F-EN. Reviewed September 2026.
Best For
- Remote access to the Prolon network over the internet with a local touchscreen
- Staged boiler plants up to 4 stages
- Mechanical rooms where two controllers share one UL listed enclosure
Warranty
For warranty coverage on this Prolon panel, contact ZOT Supply at sales@zotsupply.com or 855-825-2811.
Key Features
10-inch touchscreen HMI
Built-in 10-inch touchscreen display on the panel door for local setup and monitoring of the Prolon system.
17A isolation relays
Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel (C1050 = 4, M2000 = 5), and the controller outputs are protected by resettable fuses.
Fused, pre-wired NEMA 1 panel
Clearly marked terminal blocks, wire management channels and a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included. The wiring diagram is in the door, and all inputs and outputs are tested in the factory.
M2000: Staged or modulating boilers
Wiring configurations cover staged boilers (4 boiler stage outputs plus pumps) and modulating boilers driven from the analog outputs.
Free Prolon Focus software
Remote monitoring and configuration with free Prolon Focus software, stand-alone or networked up to 127 nodes.
ZOT Supply is an authorized distributor of Prolon products.
Technical Specifications
| Panel | |
|---|---|
| Controllers | Prolon NC2000 network controller with 10-inch touchscreen (HMI) + Prolon M2000, Boiler Controller program |
| Supply | 24 VAC ±10%, 50/60 Hz, Class 2 |
| Overcurrent Protection | Disconnect-style Slo-Blo fuse (3A @ 250 VAC), with additional replacement fuse included |
| Enclosure | NEMA 1 |
| Panel Dimensions | 16.25 in. W x 20.25 in. H x 6.25 in. D (413 mm W x 514 mm H x 159 mm D) |
| Weight | 38 lbs (17.25 kg) |
| Isolation Relays | 17A @ 277 VAC on all digital outputs (C1050 = 4, M2000 = 5) |
| Network Nodes | Stand-alone or networked (up to 127 nodes); this panel contains 2 nodes |
| Environment | -4 to 122 °F (-20 to 50 °C), non-condensing |
| Panel Certification | Complete panel is UL certified |
| Certification | UL916 Energy Management Equipment, CAN/CSA-C22.2, RoHS, FCC part 15: 2012 class B |
| NC2000 Network Controller | |
| Display | Built-in 10-inch touchscreen display (HMI) |
| Power | 30 VA |
| Communication | Modbus TCP/IP (Static IP address or DHCP) / USB / Ethernet |
| RS485 Ports | Modbus RTU (RS485): 1 input port and 1 output port, up to 127 nodes |
| Connection | Removable screw-type terminal blocks (max 16 AWG) for power and RS485, modular RJ45 jacks for Ethernet/RS485, USB female type A for local PC connection |
| SD Card | Standard size only, SDSC or SDHC, FAT16 or FAT32 |
| Scheduling | Internal clock with up to 16 configurable weekly schedules and annual calendars |
| Clock Backup | Super-capacitor 0.5F, keeps precise time for 10 days |
| Microprocessor | ASIX AX11015, 8 bits, 25 MHz, 512 KB FLASH memory |
| M2000 Controller Hardware | |
| Power | 5 VA (consumption), 40 VA (input) |
| Inputs | 7 configurable analog inputs (outside temp / supply temp / return temp / dry contacts for proof of pumps, max heat request and boiler disable). Input signals (thermistor / dry contact / 4-20mA / 0-5 VDC) individually configurable for each input |
| Digital Outputs | 5 triac outputs, 10-30 VAC source, 300 mA max (resettable fuse) |
| Analog Outputs | 3 x 0-10 VDC outputs, 40 mA max (resettable fuse) |
| Indication Lights (LED) | State of each output / Communication / Power / State of microprocessor |
| Casing | Molded ABS, UL94-HB |
| Communication | Modbus RTU (RS485), up to 127 nodes |
| Baud Rates | 9600, 19200, 38400, 57600, 76800, 115200 |
| Connection | Removable screw-type terminal blocks (16 AWG max) and RJ45 modular jacks |
| Boiler Controller Program | |
| Program | Boiler Controller |
| Application | Runs staged or modulating boiler sequences with their pumps |
| Program Inputs | Outside air, supply water and return water: 10K thermistor; proof of pump 1, proof of pump 2, use max heat setpoint and disable boiler call: dry contact |
| Program Outputs | Staged: DO1-DO4 boiler stages, DO5 pump 1, AO1 pump 2, AO3 valve (0-10 / 2-10 / 0-5 VDC). Modulating: AO2 and AO3 modulating boiler stages (0-10 / 2-10 / 0-5 VDC) |
Documentation
Frequently Asked Questions
What is the Prolon PL-PN2-1A-7C?
A pre-wired two controller panel built with a Prolon NC2000 Network Controller with 10-Inch Touchscreen HMI and a Prolon M2000 Boiler Controller, in a UL listed NEMA 1 enclosure with 17A isolation relays on all digital outputs.
What does the M2000 boiler program control?
It runs staged or modulating boiler sequences with their pumps. Strategies include staged boiler configuration and modulating boiler configuration.
What power does the panel require?
24 VAC ±10%, 50/60 Hz, Class 2; the NC2000 with HMI draws 30 VA and the M2000 draws 5 VA (consumption), 40 VA (input).
Are the outputs isolated and protected?
Yes. Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel, and the panel has a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included.
What size is the PL-PN2-1A-7C panel?
16.25 in. W x 20.25 in. H x 6.25 in. D (413 mm W x 514 mm H x 159 mm D), and it weighs 38 lbs (17.25 kg).
How does the NC2000 connect to a network?
Modbus TCP/IP with a static IP address or DHCP, USB and Ethernet, plus Modbus RTU (RS485) with 1 input port and 1 output port for up to 127 nodes.
- Panel Type:
- Master Controller Panel
- Display:
- Touchscreen Display
- Controller Type:
- Network Controller
- Controller Type:
- Boiler
- Communication:
- Modbus RTU (RS485)
- Communication:
- Modbus TCP/IP