Skip to main content

Prolon PL-PN2-NC-WOD-M2-HPS : Pre-Wired Prolon Master Panel with M2000 Single Zone Heatpump Controller, Terminal for all Connections (24V Power Supply, Inputs, Outputs, Communication), NEMA 1 Enclosure, UL508

Prolon

$3,964.22
(No reviews yet) Write a Review
SKU:
PL-PN2-NC-WOD-M2-HPS
Condition:
New
Availability:
Ships in 2-4 Days
Adding to cart… The item has been added

The Prolon NC2000 Panel is a complete communications and interface package used to access and configure any Prolon control system, either locally or remotely. A ten-inch touchscreen display acts as a local interface to the system and is mounted into a steel enclosure which houses the pre-wired Prolon NC2000 Network Controller. The NC2000 is used to connect a Prolon system to the Internet, to send schedules to the controllers and distribute outside air temperature readings. It can also be used to record trend logs and to send email-based alerts upon user-configurable conditions.

Features

  • Built-in 10-inch touchscreen display for local setup and monitoring
  • Prolon Focus visualization and configuration software comes pre-installed
  • Implements a password lockout system for standard And advanced user access
  • Pre-wired panel equipped with fuses and clearly marked terminal blocks
  • Allows for remote configuration of your Prolon system over the Internet
  • Internal clock with up to 16 configurable weekly schedules and annual calendars
  • Automatic adjustment for daylight savings and time synchronization over the Internet
  • Keeps precise time without electricity for up to 10 days
  • Onboard LEDs allows for quick diagnostics of power, communication and operation
  • Shares outside air temperature and occupancy data between devices
  • Sends email alerts based on user-configurable conditions
  • Records up to 100 trend logs at the same time, saved onto a standard SD card

Technical Specifications

  • Supply: 24 VAC ±10%, 50/60 Hz, Class 2, 30 VA
  • Communication:
    • Modbus TCP/IP (Static IP address or DHCP)
    • Modbus RTU (RS485), 1 input port and 1 output port, up to 127 nodes - USB
  • SD Card: Standard size only, SDSC or SDHC, FAT16 or FAT32
  • Panel Dimensions: 12.25” x 16.25” x 6.25” (311mm x 403mm x 159mm)
  • Weight: 18 lbs (8.2 kg)
  • Environment: 32-122 oF (0-50 oC) Non-Condensing
  • NC2000 Certification: UL916 Energy Management Equip- ment, CAN/CSA-C22.2, RoHS, FCC part 15: 2012 class B

Datasheets

pdf logo Pre-Wired Network Controller Panel

 

Panel Type:
Master Controller Panel
Display:
No Display