The Senva P4-0250-BU1XP is part of the Senva P4 Value Series of fixed-range dry-media pressure transmitters - the cost-optimized line in the P4 family, engineered for high-volume HVAC and BAS deployments where a calibration certificate is not required but a 7-year warranty, MEMS silicon sensor, and Made-in-USA manufacturing are still valuable. It senses 0 to 2.5 in WC (unidirectional) and outputs a linear 0-10 VDC signal (3-wire VAC or VDC powered). Built around a MEMS silicon piezoresistive sensor with non-position-sensitive design, manual or contact-closure auto-zero, and a patented enclosure that integrates high-density DIN-rail mounting with 3/8 in conduit-ready entry - no separate adapters needed for typical commercial HVAC installs. This SKU ships with the integrated duct probe for direct in-duct installation.
WARRANTY
Key Features
Cost-Optimized for High-Volume HVAC
The P4 Value Series delivers MEMS silicon precision and 7-year warranty coverage at a price point engineered for high-volume specification on commercial HVAC and BAS projects. +/-1.00% of range accuracy (combined non-linearity, hysteresis, and repeatability at 70 F).
MEMS Silicon Piezoresistive Sensing
Solid-state silicon sensing element with precision factory calibration. Non-position-sensitive design means the transmitter can be mounted flat, vertical, or DIN-rail without zero shift. Thermal drift is 0.02% FSO per deg C (0.01% per deg F) referenced to 72 F.
0-10 VDC Output Signal
Provides a linear 0-10 VDC output proportional to applied differential pressure. 3-wire vac or vdc powered with 12-30 VDC or 24 VAC input. Drop-in compatible with virtually any BAS, DDC, or analog control input.
Manual + Contact-Closure Auto-Zero
Front-panel pushbutton zero plus remote auto-zero via contact-closure input. Hold the ZERO SET button for 2 seconds with no pressure applied (or temporarily connect H and L ports together) to re-zero. Zero drift is <0.004 in WC per year typical.
Patented DIN-Rail and Conduit-Ready Mount
Patented enclosure design with two DIN-rail mounting orientations (back or side - side saves panel space for high-density panels), plus an integrated 3/8 in flex conduit cover - no separate fittings or adapters required for typical commercial install.
Integrated Duct Probe
Ships with the integrated static-pressure probe, designed to thread directly into the back of the enclosure for in-duct mounting. The same probe transforms for either direct duct mount or remote-probe service with the optional RP-6 6-inch remote probe (sold separately).
Technical Specifications
| Specification | Value |
|---|---|
| Model | P4-0250-BU1XP |
| Series | P4 Value |
| Pressure Range | 0 to 2.5 in WC |
| Direction | Unidirectional |
| Accuracy | +/-1.00% of range (combined non-linearity, hysteresis, repeatability at 70 F) |
| Output Signal | 0-10 VDC, 3-wire VAC or VDC powered |
| Supply Voltage | 12-30 VDC or 24 VAC, 30 mA max |
| Other Outputs Available (Family) | 4-20 mA loop powered, 4-20 mA 3-wire, 0-5 VDC, 0-10 VDC |
| Sensor Type | MEMS silicon piezoresistive, precision calibrated |
| Zero Function | Pushbutton + contact-closure auto-zero |
| Zero Tolerance | Included in accuracy specification |
| Span Tolerance | +/-1.00% (+/-1% +/-0.005 in WC for ranges below 0.10 in WC) |
| Zero Drift (1 year) | 0.004 in WC/year max (0.4% for units over 0.5 in WC) |
| Thermal Shift (Zero and Span) | 0.02% FSO per deg C (0.01% FSO per deg F), measured from 22 C (72 F) |
| Response Rate | 8 seconds (full scale) |
| Overpressure | 41.5 in WC |
| Max Static Line Pressure | 41.5 in WC |
| Burst Pressure | 83 in WC |
| Position Sensitivity | Non-position sensitive |
| Operating Temperature | -4 to 140 F (-20 to 60 C) |
| Compensated Temperature | -4 to 140 F (-20 to 60 C) |
| Operating Humidity | 0 to 95% RH, non-condensing |
| Media Compatibility | Dry, oil-free air or nitrogen (N2) |
| Display | None |
| Duct Probe | Integrated duct probe included |
| Enclosure Material | UL94-5VB rated, ABS |
| Enclosure Rating | NEMA 1 |
| Conduit Entry | 3/8 in flex conduit cover (integrated) |
| Tubing Connection | Hose barbs, accepts 1/8 in and 1/4 in ID tubing |
| DIN Rail Mounting | Back or side (two orientations) - patented design |
| Dimensions | 4.75 x 4.20 x 1.82 in (approx) |
| Weight | 0.20 lb |
| Compliance | CE, RoHS |
| Procurement Compliance | Buy American Act (BAA) and TAA compliant |
| Country of Origin | Made in USA - Beaverton, Oregon |
| Warranty | 7-year limited (electronics) |
| Manufacturer Part Number | P4-0250-BU1XP |
Documentation
Frequently Asked Questions
What pressure range and direction does the P4-0250-BU1XP measure?
How does the P4 Value accuracy compare to other transmitters?
How do I wire the 0-10 VDC output?
Does this version have a display?
What's included for duct mounting?
How do I zero the transmitter and what media can it measure?
- Series:
- P4 Value
- Pressure Range Class:
- Low (1 to 10 in WC)
- Pressure Range:
- 0 to 2.5 in WC
- Direction:
- Unidirectional
- Output Signal:
- 0-10 V
- Display:
- None
- Accuracy Class:
- Mid (0.5 to 2% FS)
- Mounting:
- Duct
- Probe:
- Probe
- Made in USA:
- Yes