Senva P5-0100-1XX : Universal Differential Pressure Transmitter, Select Range (Uni/Bi): 0-1"(0.1/0.25/0.5/1.0"), Select Outputs: 4-20 mA, 0-5 VDC, or 0-10 VDC, Auto-Zero, No Probe, Buy American Act Compliant, 7 Year Limited Warranty
The P5 Universal Dry Pressure transmitter from the P5 Series is a highly versatile and efficient solution with various sizes and selectable sub-ranges. It accurately measures pressures for zone pressure, filter measurement, and static duct applications. The transmitter's universal output and uni/bi directional readings reduce inventory and streamline maintenance efforts. Its user-friendly features, including a zero calibration push button and non-position sensitivity, simplify installation and setup. Equipped with LED indicators for crucial status information, the P5 Universal Dry Pressure transmitter ensures reliable and accurate pressure measurements for HVAC applications while reducing inventory and call-backs.
Applications:
- Building (Zone) Pressure: The transmitter can be used to measure pressure differentials within a building's zones. This can be useful for monitoring and controlling airflow and ventilation systems.
- Filter Condition Measurement: The device is capable of measuring pressure differentials across filters. This allows for the monitoring of filter condition and can indicate when filters need to be replaced or cleaned.
- Duct/Static: The transmitter is suitable for measuring static pressure within ductwork. This can help in monitoring airflow and detecting potential issues in the duct system.
Features:
- Duct, Filter, and Remote Probe Applications: The transmitter is designed to handle various applications, including duct, filter, and remote probe measurements, all in one device.
- Universal Output: The transmitter offers a universal output, which helps reduce inventory requirements and potential callbacks.
- Selectable Sub-Ranges: It supports selectable sub-ranges, allowing for more flexibility and reducing the need for additional inventory items.
- Zero Calibration Push Button and Remote Contact Input: The transmitter includes a zero calibration push button and supports remote contact input, facilitating calibration and adjustment processes.
- Non-Position Sensitive: The device is non-position sensitive, making it easy to install and place in the desired location.
- Dual DIN Mount: It offers a dual DIN mount, allowing for side mount density (which conserves panel space) or flat panel mount for LCD viewable panel mount.
- Conduit Ready: The transmitter is conduit ready for 3/8" flex connectors, eliminating the need for additional parts.
- LED Indicators: The transmitter features LED indicators that provide information on power status (heartbeat), auto-zero completion, and over-pressure conditions (110% over pressure). These indicators facilitate the locating of the sensor within ductwork.
Specifications
Power Supply | 12-30VDC/24VAC(1), 30mA max |
Selectable outputs | 4-20mA loop powered, 4-20 mA 3-wire, 0-5VDC, 0-10VDC |
Output scaling | 0-1” (Selectable 0.1, 0.25, 0.5, 1.0, ±0.1, ±0.25, ±0.5, ±1.0 “WC) |
Operating range | -4 to 140F (-20 to 60ºC) |
Compensated range | -4 to 140F (-20 to 60ºC) |
Media compatibility | Dry, oil-free air, N2 |
Accuracy | ±1.0% of selected range (combined linearity and hysteresis) |
Zero Tolerance | Included in accuracy specification |
Zero Drift (1 year) | 0.004”WC/year max. 0.4% for units >0.5”w.c. |
Auto-zero input | Push-button and contact closure |
Enclosure | NEMA 1 |
Datasheets
Senva P5 Universal Pressure Sensor Datasheet | |
Senva P5 Universal Pressure Installation Manual | |
Senva P5 Engineering Specifications | |
Senva Buy-American ACT 2023 |
- Output Signal:
- 4-20 mA, 0-5 VDC, or 0-10 VDC
- Pressure Type:
- Differential
- Pressure Ranges:
- 0 to 1 Inch
- Media:
- Dry
- Accuracy:
- 1.0%
- LCD Display:
- No Display
- Zero Function:
- Yes
- Range Setting:
- Adjustable
- Communication:
- None
- Series:
- P5 Series