The Senva TG0R-3B is a recessed room-mount refrigerant leak detector for VRF systems and other occupied spaces. It uses a metal oxide semiconductor (MOS) sensing element factory calibrated to R134A, reports 0-1000 ppm on a 0-10 VDC 3-wire output, and carries a normally closed alarm relay, a status LED and an 82 dB local buzzer behind a single-gang wall plate. Senva positions the TG0R Series as an A2L refrigerant leak detector for VRF applications such as hotel guest rooms, schools, multi-family, mixed-use and commercial facilities.
Specifications on this page were verified against the Senva TG0R Series A2L Refrigerant Leak Detector for VRF datasheet and Senva installation instructions document 152-0408-0B, revised 7/8/2024.
Best For
- VRF systems where a local room-level leak alarm is required, per the applications Senva lists for the TG0R Series
- Hotel guest rooms, schools, multi-family, mixed-use and commercial facilities (applications listed on the Senva TG0R datasheet)
- Retrofits into an existing single-gang box, where a recessed low-profile plate is preferred over a surface enclosure
- Spaces that need both a stand-alone audible alarm and a signal back to the building automation system
- Controllers with 0-10 VDC universal inputs already available on the panel
Warranty
7-year warranty. Senva backs the TG0R Series with a seven year warranty. Senva also states that its liability, whether in contract, in tort, under any warranty, in negligence or otherwise, shall not exceed the purchase price paid for the product, and that Senva is not liable for special or consequential damages. ZOT Supply is an authorized Senva distributor; warranty claims are handled directly with Senva.
Key Features
Technical Specifications
| Power | |
| Power supply | 12-30 VDC / 24 VAC, 24 mA max (15-30 VDC / 24 VAC required for full 10 V output) |
| Transformer note | One side of the transformer secondary connects to signal common. A dedicated transformer is recommended. |
| Output | |
| Analog output | 0-10 VDC, 3-wire |
| Refrigerant output scaling | 0-1000 ppm |
| Alarm | |
| Relay characteristics | N.C., 1 A at 24/30 VAC/VDC (50/60 Hz), no mains connection |
| Relay and buzzer setpoint | Above 300 ppm for 1 hour, or above 600 ppm for 15 minutes |
| LED indication | 1 long blink above 300 ppm; 1 short blink above 600 ppm |
| End-of-life indication | 3 blinks at 30 second intervals |
| Buzzer level | 82 dB |
| Alarm silence | Hold hand over cap touch button for 3 seconds (3 silences maximum) |
| Alarm test | Hidden button; press 1 second, relay activates 2 seconds |
| Refrigerant sensor performance | |
| Sensing element | MOS (metal oxide semiconductor) |
| Factory calibration | R134A |
| Resolution | 1 ppm |
| Life expectancy | Greater than 10 years (typical life expectancy of MOS sensors) |
| Coverage area | 5,000 to 7,500 square feet |
| Calibration interval | 6 months; hold test button 10 seconds to enter cal mode |
| Field calibration | Hold test button 10 seconds to enter cal mode, then apply R134A at 0.2 LPM and 1000 ppm for 5 minutes |
| Other detectable gases | R407A, R407F, R427A, R452B, R507, R448A, R449A, R422A, R422D, R452A, R513A, R514A, R32. Senva states these gases may be detected but sensitivity curves are not available at this time. |
| Environment | |
| Unit temperature rating | -4 to 122 °F (-20 to 50 °C), per the current TG0R datasheet |
| Humidity | 15-95% continuous, 0-95% intermittent |
| Maximum elevation | 2,629 m (8,625 ft) per the current TG0R datasheet; field calibration recommended to maintain accuracy at altitude |
| Enclosure and compliance | |
| Dimensions | 4.45 in. H x 2.7 in. W x 0.5 in. D (depth measured from wall) |
| Mounting | Recessed; fits a standard single-gang box |
| Mounting height | 6 in. above finished floor for refrigerant sensors |
| Compliance | CE, RoHS |
| Country of origin | United States |
Environmental values above follow the current Senva TG0R datasheet where it differs from installation document 152-0408-0B (revised 7/8/2024).
Published response of the R134A calibrated element
Senva publishes the following measured readings when 300 ppm of test gas is applied to an R134A calibrated element. Readings above 300 ppm mean the element over-reports that gas relative to its R134A calibration, which is why Senva describes it as a cover-all general purpose refrigerant element.
| Test gas at 300 ppm | Reading on R134A calibrated element |
|---|---|
| R410A | 450 ppm |
| R407C | 425 ppm |
| R404A | 400 ppm |
| R22 | 370 ppm |
| R134A | 300 ppm |
Installation notes from Senva
- Mount refrigerant sensors 6 in. above finished floor, and confirm mounting height against local and state building codes.
- Do not install the sensor in multi-gang electrical boxes with line voltage or other electrical devices.
- Use installation wire rated 75 °C and above.
- Confirm the supplied insulation covers the entire junction box opening so wall cavity air does not affect the reading.
- Do not install in hazardous or classified locations.
Documentation
Related Senva TG0R Detectors
Calibration accessory: order Senva CALKITHW-R to receive the calibration fitting and regulator used for the 6 month field calibration.
Frequently Asked Questions
7-Year Warranty. Senva backs the TG0R Series with a seven year warranty. Senva liability shall not exceed the purchase price paid for the product, and Senva is not liable for special or consequential damages. ZOT Supply is an authorized Senva distributor; warranty claims are handled directly with Senva.
- Type:
- Refrigerant Leak Detector
- Calibrated Gas:
- R134A (Multi-Gas)
- Sensor Technology:
- MOS
- Series:
- TG0R
- Enclosure Style:
- Wall (Recessed)
- Analog Output:
- 0-10 VDC (3-Wire)
- Relay Output:
- 1 N.C.
- Local Alarm:
- LED and Audible Buzzer
- Communication:
- None
- Display:
- None
- Country of Origin:
- United States