Senva TGD-ACM-A : Duct Mount Dual Combustible Gas Sensor/Controller, Carbon Monoxide (CO) and Methane (CH4), 0-10V, 0-5V, 1-5V and 4-20mA Selectable Output, LCD Display, 7-Year Warranty
The Senva TGD-ACM-A is a duct mount dual combustible gas sensor/controller designed for monitoring Carbon Monoxide (CO) and Methane (CH4). It features selectable output options including 0-10V, 0-5V, 1-5V, and 4-20mA. Equipped with a 3-1/2 digit LCD display, this device comes with a 7-year warranty. The analog outputs are menu-selectable, and the fan relay, set at 300 ppm by default, is capable of handling 1A@24/30VDC. The alarm relay, set at 600 ppm by default, also has a 1A@24/30VDC capacity. The device includes LEDs indicating normal, relay, and alarm statuses, along with an audible alarm (85dB Piezo transducer) with a duration of 30 minutes above the alarm setpoint. The CO sensor, of electrochemical type, boasts an accuracy of ±5% of the default range and a life expectancy of over 7 years, covering an area of 5000-7500 square feet.
Specifications
Analog Outputs | 0-10V (default), 0-5V, 1-5V, 4-20mA (menu selectable) |
Fan relay characteristics | N.C. 1A@24/30VDC (50/60Hz) (no mains connection) |
Fan relay setpoint | 300 ppm (default), 0-1000 ppm (menu selectable) |
Alarm relay characteristics | N.C. 1A@24/30VDC (50/60Hz) (no mains conenction) |
Alarm relay setpoint | 600 ppm (default), 0-1000 ppm (menu selectable) |
Display | 3-1/2 digit LCD |
LEDs | Green = Normal, Yellow = Relay, Red = Alarm |
Audible Alarm | 85dB Piezo transducer / 30 minutes above alarm setpoint (menu selectable) |
CO Sensor Performance | |
Type | Electrochemical |
Accuracy | ±5% of default range(2) ±5%of reading above 200ppm |
Resolution | 1ppm |
Life expectancy | >7 years |
Coverage Area | 5000-7500 square feet |
Methane/Propane/Hydrogen Sensors Performance | |
Type | Catalytic |
Detection Range | 0-50% LEL (Lower Explosive Limit) |
Accuracy | 5% of range |
Certifications | UL2075 Listed Component |
Resolution | 1%LEL |
Life expectancy | >5 years |
Response Time | <10s to 90% |
Coverage Area | Methane/Hydrogen 5000-7500 sq ft; Propane 5000 sq ft |
Enclosure | IP43 or NEMA 3R |
Data Sheets
- Enclosure Style:
- Duct
- Gas Element:
- Carbon Monoxide / Methane
- Analog Output:
- 2
- Relay Output:
- 2 SPDT
- Communication:
- None
- Display:
- LCD Display