Senva TGM-BCO-F : Metal Wall Mount Dual Combustible Gas Sensor/Controller, Carbon Monoxide (CO) and Oxygen (O2), BACnet MS/TP or Modbus RTU Output, 10K Type II Thermistor, LCD Display, 7-Year Warranty
Specifications
BACnet /Modbus | BACnet MS/TP, Modbus RTU, Modbus ASCII |
Fan relay characteristics | N.C. 1A@24/30VDC (50/60Hz) (no mains connection) |
Fan relay setpoint | 300 ppm (default), 0-1000 ppm (menu selectable) |
Alarm relay characteristics | N.C. 1A@24/30VDC (50/60Hz) (no mains conenction) |
Alarm relay setpoint | 600 ppm (default), 0-1000 ppm (menu selectable) |
Display | 3-1/2 digit LCD |
LEDs | Green = Normal, Yellow = Relay, Red = Alarm |
Audible Alarm | 85dB Piezo transducer / 30 minutes above alarm setpoint (menu selectable) |
Oxygen Sensor Performance | |
Type | Electrochemical |
Detection Range | 0-25% Volume |
Accuracy | ±5% of range |
Resolution | 0.1% |
Life expectancy | 5 years, with Annual Calibration |
Mounting | 3 to 6 feet off the ground; coverage of 5000-7500 square feet |
CO Sensor Performance | |
Type | Electrochemical |
Accuracy | ±5% of default range(2) ±5%of reading above 200ppm |
Resolution | 1ppm |
Life expectancy | >7 years |
Coverage Area | 5000-7500 square feet |
Enclosure | IP43 or NEMA 3R |
Data Sheets
- Enclosure Style:
- Wall
- Gas Element:
- Carbon Monoxide / Oxygen
- Analog Output:
- None
- Relay Output:
- 2 SPDT
- Communication:
- BACnet/Modbus
- Display:
- LCD Display