Senva TGM-REM-20 : Metal Enclosure Kit Allows for Dual Mounting Heights for TGM or TGW Series with Pre-Cut 20 Foot CAT-5 Cable, Mounting Bracket, No Programming Necessary, 7-Year Warranty
TG-REM kit allows for dual mounting heights with a single power source and output connection.
- Great for local codes requiring gases monitored at different heights
- Plug-and-play; provided with pre-cut CAT-5 cable
- Single power source, single location for RS-485/analog/relay connections
- Through-the-back wiring makes junction-box-mounting easy
- No programming necessary
The TGx-REM kit offers a convenient solution for installations requiring sensors to be mounted at different heights. It includes an RJ45 cable, a plug-and-play sensor extension board, and a secondary TGW or TGM box to relocate one sensor board.
Installation Steps:
- Remove the sensor board from the rightmost position of the primary TG (with LCD) and replace it with the extender board from the TG-REM kit.
- Connect the removed sensor board to the TG-REM board using the red connectors.
- Use the included RJ45 cable to link the two enclosures, plugging each end into the corresponding sensor boards.
Calibration:
- Use the LCD on the primary TG for calibration.
- Alternatively, reconnect the remote sensor to the primary TG for local calibration.
Note: Refrigerant and catalytic sensors in the REM kit need re-zeroing due to GND shift caused by inductors that reduce noise on the RJ45 cable.
This seamless setup lets you monitor multiple gasses at two separate levels with the same efficiency as a single device. The RIM Kit makes advanced gas monitoring easy and efficient, giving you all the tools you need in one complete package!