Senva TGW-A4X-A : Wall Mount R410A Refrigerant Sensor/Controller, 0-10V, 0-5V, 1-5V and 4-20mA Selectable Output, LCD Display, Clear/Tinted Enclosure, 7-Year Warranty
Applications
- Refrigerant leak detection in mechanical rooms
- Pre-calibrated for R410A and also senses refrigerant including R134A, R410A, R407C, R404A, R22, R123
- Monitor multiple gases with one mounted unit
- Alert occupants of elevated gas levels
- Directly control exhaust fans
Specifications
Power Supply | 15-30VDC/24VAC(1), 4W max, 160mA max. |
Analog Outputs | |
Programmable output | 0-10V (default), 0-5V, 1-5V, 4-20mA (menu selectable) |
Output scaling | Menu selectable; see installation manual for ranges |
Fan Relay | |
Fan relay characteristics | N.C. 1A@24/30VDC (50/60Hz) (no mains connection) |
Fan relay setpoint | 300 ppm (default), 0-1000 ppm (menu selectable) |
Alarm Relay | |
Alarm relay characteristics | N.C. 1A@24/30VDC (50/60Hz) (no mains connection) |
Alarm relay setpoint | 600 ppm (default), 0-1000 ppm (menu selectable) |
Display 3-1/2 digit LCD | Green, Yellow, Red |
Audible Alarm | 85dB Piezo transducer 30 minutes above alarm setpoint (menu selectable) |
General Purpose Sensor Performance | |
Type | MOS |
Detection Range | 0-1000 ppm |
Resolution | 1 ppm |
Listed Gas types 2-9 | Factory calibrated for respective gas |
R134A Sensitivity(2) | @300ppm test gas: 450 ppm R410A, 425 ppm R407C, 400 ppm R404A, 370 ppm R22, 300 ppm R134A, R134 |
Other detectable gases(3) | R407A, R407F, R427A, R452B, R507, R448A, R422A, R422D, R452A, R514A, R32, R123 |
Life expectancy | >10 years (typical life expectancy for MOS sensors) |
Coverage Area | 5000-7500 square feet |
Operating Environment | |
Temperature, Operational | -30 to 50oC (-22 to 122oF) (CO2 versions rated to -40o C) |
Humidity | 15-95% continuous, 0-95% intermittent |
Max Elevation | 2000m, Refrigerant 2629 m (8625 ft) |
Enclosure (Wall & Duct) | |
Material | ABS/Polycarbonate |
Dimensions | 4.0”h x 4.4”w x 2.1”d |
Conduit Opening | Tapped 1/2” NPT |
Rating | P43 or NEMA 3R |
Agency Compliance | UL61010-1 Listed UL, cUL, CE |
Datasheets
- Enclosure Style:
- Wall
- Gas Element:
- Refrigerant
- Analog Output:
- 2
- Relay Output:
- 2 SPDT
- Communication:
- None
- Display:
- LCD Display