Strato Automation OS537MHCW : OPENSTAT BACnet MS/TP & Wi-Fi 6 Wall Controller, Temperature, RH, Radar Motion & NDIR CO2 Sensors, 15 I/O (5 UI, 3 AO, 7 BO)

Strato Automation

MSRP: $1,037.00
Your Price:  $349.99
(You save $687.01 )
(No reviews yet) Write a Review
SKU:
OS537MHCW
Condition:
New
Availability:
Ships in 1-2 Days
Adding to cart… The item has been added
ProtocolsBACnet MS/TP + BACnet/IP
WirelessWi-Fi 6, 2.4 GHz
I/O15 (5 UI / 3 AO / 7 BO)
SensorsTemp + RH + Motion + CO2
Power24 VAC/VDC
BTLB-BC Listed

The Strato Automation OS537MHCW is an OPENSTAT configurable BACnet wall controller with 15 I/O (5 universal inputs, 3 analog outputs, 7 binary outputs), built-in temperature, humidity, radar motion and NDIR CO2 sensing, and BACnet MS/TP plus BACnet/IP over Wi-Fi 6. It mounts on a standard 2 x 4 in. electrical junction box and runs on 24 VAC/VDC.

The OS537MHCW controls AHU, FCU, RTU, HP and WSHP equipment, with numerous configurations to fit the project. A Sensirion SHT40 sensor provides room temperature and humidity at the wall. A radar motion sensor detects human presence up to 20 ft straight ahead, and a self-calibrating Telaire T6713 NDIR sensor measures CO2 from 400 to 2000 ppm. Configuration is available from the local buttons, BACnet configuration objects, embedded web pages or Strato software tools.

Best For

  • Air handling units (AHU)
  • Fan coil units (FCU)
  • Rooftop units (RTU)
  • Heat pumps (HP)
  • Water source heat pumps (WSHP)
  • Projects that need BACnet/IP over the building Wi-Fi network as well as BACnet MS/TP
  • Rooms where occupancy is detected at the wall controller by radar
  • Rooms where CO2 is measured at the wall controller

Warranty

Strato Automation backs the OS537MHCW with a 2-year manufacturer warranty.

Key Features

BACnet MS/TP and Wi-Fi 6 BACnet/IP

BTL listed BACnet Building Controller (B-BC). Connects on MS/TP (76800 bps default) and on BACnet/IP over Wi-Fi 6 at 2.4 GHz with WPA3 or WPA2 security, integrated web services and REST API support.

15 I/O on the Wall

5 universal inputs (10K thermistor Type 2 or 3, dry contact, 0-10 VDC), 3 0-10 VDC analog outputs and 7 isolated MOSFET solid state relay binary outputs rated 10 to 30 VAC, 2.0 A max.

Temperature and Humidity

Sensirion SHT40 sensor: ±1.8% RH from 25 to 75% RH (±3% RH overall) and ±0.2 °C from 0 to 60 °C.

Radar Motion Detection

Radar cross-section optimized for human presence: 20 ft (6 m) at 0°, 16 ft (5 m) at ±45° and 3 ft (1 m) at ±80°.

NDIR CO2 Sensing

Self-calibrating Telaire T6713 NDIR sensor, 400 to 2000 ppm, ±30 ppm @ 3% of reading after 2 weeks of continuous operation.

Phone and Browser Setup

A built-in Wi-Fi access point lets a phone or laptop open the embedded web pages directly. Export a finished configuration and import it on the next controller.

Authorized Distributor

ZOT Supply is an authorized distributor of Strato Automation products.

Technical Specifications

Identity
ManufacturerStrato Automation
ModelOS537MHCW
Product lineOPENSTAT configurable wall controller
I/O
Total I/O15: 5 universal inputs (AI/BI), 3 analog outputs, 7 binary outputs
Power
Supply24 VAC/VDC ±15%, Class 2
Current consumption1.5 VA controller only; 96 VA max including binary outputs at 2 A each
Communication
BACnet MS/TPMS/TP device; 9600, 19200, 38400, 76800 bps (76800 default)
RS-485 transceiver1/4 load device
Service portMini USB2 for MS/TP network access
BACnet/IPWi-Fi 6, 2.4 GHz BACnet/IP module with integrated web services and REST API support
BTL listingBTL listed, BACnet Building Controller (B-BC), listing BTL-31479
Inputs
Universal input types10K ohm thermistor (Type 2 or 3), dry contact, 0-10 VDC (20K ohm input impedance)
Input resolution12 bits (4096 segments)
Outputs
Binary output typeMOSFET solid state relays, isolated; 10 to 30 VAC, 2.0 A max
Analog output type0-10 VDC linear
Wi-Fi
StandardWi-Fi 6 (IEEE 802.11ax), single band 2.4 GHz
SecurityWPA3-Personal (SAE) or WPA2, selectable
RadiosAccess Point mode for direct phone or laptop setup; Station mode for the building Wi-Fi network
Range (line of sight)Station mode up to 30 m; Access Point mode up to 12 m
Network notesBroadcast SSID required (hidden SSIDs not supported); DHCP or fixed IP
Sensors
Temperature and humidity sensorSensirion SHT40
Humidity accuracy±1.8% RH @ 25 to 75% RH; ±3% RH overall
Temperature accuracy±0.2 °C @ 0 to 60 °C (±0.36 °F @ 32 to 140 °F)
Motion sensorRadar motion detection, radar cross-section optimized for human presence
Motion detection distance20 ft (6 m) @ 0°; 16 ft (5 m) @ ±45°; 3 ft (1 m) @ ±80°
CO2 sensorTelaire T6713, self-calibrating non-dispersive infrared (NDIR)
CO2 range400 to 2000 ppm
CO2 accuracy±30 ppm @ 3% of reading; valid after a minimum of 2 weeks of continuous operation
CO2 response time3 minutes
Hardware
MicroprocessorSTM32 (ARM Cortex M33), 32 bits, 250 MHz
Memory2 MB non-volatile flash; 640 KB SRAM
Real-time clockBuilt-in capacitor, one-week backup
Mechanical
Dimensions (W x H x D)3.58 x 4.92 x 0.98 in. (91 x 125 x 25 mm)
MountingStandard 2 x 4 in. electrical junction box
EnclosureWhite, PC-ABS, UL94 V-0
Environment
Operating temperature32 to 122 °F (0 to 50 °C)
Storage temperature-22 to 122 °F (-30 to 50 °C)
Operating humidity10 to 90% RH, non-condensing
Configuration
Configuration methodsLocal buttons, BACnet configuration objects, embedded web pages or Strato software tools
Certifications
SafetyUL 916 Energy Management Equipment
FCCClass A digital device, pursuant to Part 15 of the FCC Rules
Compliance
SequencesASHRAE Guideline 36 (G36) compliant applications
Energy codeDesigned to support installations intended to meet California Title 24 Building Energy Efficiency Standards performance requirements when properly configured and commissioned
Warranty
Manufacturer warranty2 years

Specifications verified November 4, 2026 against the Strato Automation OS537 Spec Sheet (May 2026, rev 3), the OPENSTAT Series Wi-Fi User Guide (July 2026, rev 5) and BTL Listing BTL-31479.

Frequently Asked Questions

What is the Strato Automation OS537MHCW?

The OS537MHCW is an OPENSTAT configurable BACnet wall controller with 15 I/O (5 universal inputs, 3 analog outputs, 7 binary outputs) and built-in temperature, humidity, radar motion and NDIR CO2 sensing. It communicates on BACnet MS/TP and on BACnet/IP over Wi-Fi 6.

Does the OS537MHCW support BACnet/IP over Wi-Fi?

Yes. The OS537MHCW has a Wi-Fi 6 (802.11ax) BACnet/IP module on the 2.4 GHz band with WPA3-Personal or WPA2 security, and it also supports BACnet MS/TP. It is BTL listed as a BACnet Building Controller (B-BC). The network must broadcast its SSID; hidden SSIDs are not supported.

How many inputs and outputs does the OS537MHCW have?

15 in total: 5 universal inputs that accept a 10K thermistor (Type 2 or 3), dry contact or 0-10 VDC, 3 0-10 VDC analog outputs and 7 isolated MOSFET solid state relay binary outputs rated 10 to 30 VAC, 2.0 A max.

How far does the OS537MHCW detect motion?

Its radar motion sensor detects up to 20 ft (6 m) straight ahead, 16 ft (5 m) at ±45° and 3 ft (1 m) at ±80°.

What CO2 range and accuracy does the OS537MHCW have?

It uses a self-calibrating Telaire T6713 NDIR sensor with a 400 to 2000 ppm range and ±30 ppm @ 3% of reading accuracy, valid after a minimum of 2 weeks of continuous operation. Response time is 3 minutes.

How accurate are the temperature and humidity readings on the OS537MHCW?

The Sensirion SHT40 sensor is rated ±1.8% RH from 25 to 75% RH (±3% RH overall) and ±0.2 °C from 0 to 60 °C (±0.36 °F from 32 to 140 °F).

What power does the OS537MHCW need?

24 VAC/VDC ±15%, Class 2. The controller alone draws 1.5 VA; maximum consumption is 96 VA including the binary outputs at 2 A each.

How do you set up the OS537MHCW on Wi-Fi?

Connect a phone or laptop to the controller's built-in access point, open its embedded web pages at https://192.168.4.1, then enter the building Wi-Fi network in Station mode. A finished configuration can be exported and imported on the next controller.

What warranty comes with the OS537MHCW?

Strato Automation provides a 2-year manufacturer warranty.

2 Year Manufacturer Warranty
Supported Protocols:
BACnet MS/TP
Supported Protocols:
BACnet/IP
Wireless:
Wi-Fi 6
Voltage:
24VAC/VDC
Universal Inputs:
5
Analog Outputs:
3
Binary Outputs:
7
Built-In Sensors:
Temperature
Built-In Sensors:
Humidity
Built-In Sensors:
Motion
Built-In Sensors:
CO2