Skip to main content

Veris PX3DLX01S : Differential Pressure/Air Velocity Transducer, Switch Selectable Bidirectional: -0.1" to 1" WC, Selectable Outputs: 4-20mA, 0-5 VDC, or 0-10 VDC Duct Probe, LCD Display, Standard - No Wireless Technology

Veris

MSRP: $244.00
$136.64
(You save $107.36 )
(No reviews yet) Write a Review
SKU:
PX3DLX01S
Condition:
New
Availability:
Ships in 1-2 Weeks
Adding to cart… The item has been added

Veris PX3DLX01S : Differential Pressure/Air Velocity Transducer, Switch Selectable Bidirectional: -0.1" to 1" WC, Selectable Outputs: 4-20mA, 0-5 VDC, or 0-10 VDC Duct Probe, LCD Display, Standard - No Wireless Technology

The PX3 transducer can measure either air pressure or velocity with the flip of a switch. The PX3 has an IP65/ NEMA 4 environmental rating and a 5-year limited warranty. This product is intended for use in HVAC and building environmental control applications. It is not intended for direct medical monitoring of patients.

Specifications:

Media Compatibility Dry air or inert gas
Input Power Three-wire Volt mode: 24 Vac or 12-30 Vdc* Two-wire mA mode: 12-30 Vdc*
Pressure Range 1
  • Unidirectional: 0.1/0.25/0.5/1 in. WC, switch selectable
  • Bidirectional: ±0.1/±0.25/±0.5/±1 in. WC, switch selectable
  • Unidirectional: 25/50/100/250 Pa, switch selectable
  • Bidirectional: ±25/±50/±100/±250 Pa, switch selectable
  • Velocity Mode: 500/1,000/2,000/3,000 ft/min 2.5/5/10/15 m/s
Response Time Standard: T95 in 20 sec, Fast: T95 in 2 sec, DIP switch selectable
Mode Unidirectional or bidirectional, DIP switch selectable
Zero Drift (1-year) 1 in. WC (250 Pa) models: 2.5% FS typ.;
Zero Adjust Pushbutton auto-zero and digital input (2-pos terminal block)

 

Data Sheets

pdf logo

Veris PX3 Differential Pressure / Air Velocity Data Sheet

pdf logo

Veris PX3 Differential Pressure / Air Velocity Installation Sheet

pdf logo

Veris PX3 EU Declaration of Conformity (DoC)

Output Signal:
4-20 mA, 0-5 VDC, or 0-10 VDC
Pressure Type:
Differential
Pressure Ranges:
0 to 1 Inch
Media:
Dry
LCD Display:
LCD Display
Zero Function:
Yes
Range Setting:
Adjustable
Accuracy:
1.0%
Series:
PX3 Series
Communication:
None