ACI A/CS2 : Solid-Core Fixed Trip Point Current Switch, Contact Type: Normally Open "N/O", Amp Range: 0-250A, Trip Point: 0.25A or less, Contact Rating 0.2A @ 200VAC/VDC, 5-Year Warranty
The ACI A/CS2 is a solid-core fixed trip point current switch for AC current monitoring applications requiring a "Go/No Go" or On/Off status for specific equipment. It operates with a contact type of Normally Open (N/O) and has an amp range of 0-250A, with a trip point set at 0.25A or less. The contact rating is 0.2A at 200VAC/VDC.. Ideal for installations in various equipment such as motors, pumps, or compressors. The ACI A/CS2 can be used for determining equipment run time and basic load trending and features a patented 35mm Din Rail mounting foot for easy panel installation. The ACI A/CS2 is UL/CUL US Listed, CE, RoHS2, and WEEE compliant.
Applications:
- Pump Status
- Fan Status
- Compressors
- Motor Status
- Ovens
- Industrial Equipment
- Lighting Status and Usage
- Electrical Load Status
- Local Alarms (Strobes and Audible Alarms)
Specifications:
| Monitored Current Type | AC Current |
| Maximum AC Voltage | 600 VAC |
| Core Style | Solid Core |
| Sensor Power | Induced from the Monitored Conductor |
| Amperage Range | 0 to 250A |
| Isolation Voltage | 2200 VAC |
| Trip Point Style | Trip Point | 0.25A or Less |
| Contact Type | Normally Open "N/O" |
| “Status” Contact Rating | 0.2A @ 200 VAC/VDC |
| Status LED Indication | Red LED (Monitored current is above Trip Point) |
| Aperture Size | 0.75” (19.05 mm) |
| Din Rail Size | 35 mm | (U.S. Patent No. 7,416,421) |
| Wiring Connections | 2 Position Screw Terminal Block (Not Polarity Sensitive) |
| Wire Size | 16 to 22 AWG (1.31 mm2 to 0.33 mm2) Copper Wires only |
| Agency Approvals | UL/CUL US Listed (UL 508) Ind. Control Equipment (File # E309723), CE, RoHS2, WEEE |
Datasheets
| ACI Fixed "Status" Switch Data Sheet | |
| ACI Fixed "Status" Switch Installation Instructions |
- Mounting Type:
- Solid-Core
- Setpoint:
- Fixed Trip
- Contact Type:
- Normally Open
- Amp Range:
- 0-250A
- Trip Point:
- 0.25A
- Contact Rating:
- 0.2A @ 200VAC/VDC
- Contact Termination:
- Terminal Strip