ACI A/SCSX2 : Split-Core Fixed Trip Point Current Switch, Contact Type: Normally-Closed "N/C", Amp Range: 0-200A, Trip Point: 1.5A or less, Contact Rating 0.2A @ 200VAC/VDC, 5-Year Warranty
The ACI A/SCSX2 Split-Core Fixed Trip Point Current Switch is a versatile tool for monitoring AC current in any application where you need a simple "Go/No Go" or On/Off status. This makes it ideal for monitoring pumps, fans, compressors, motors, ovens, industrial equipment, lighting, and more.
With a trip point of 1.5A or less and a contact rating of 0.2A @ 200VAC/VDC, the A/SCSX2 is accurate and reliable. It's also easy to install, thanks to its split-core design, which allows you to clamp it around a wire without disconnecting it. In addition to its basic monitoring capabilities, the A/SCSX2 can also be used to determine the run time of your equipment and track basic load trends. This makes it a valuable tool for energy management and preventative maintenance.
The A/SCSX2 is backed by ACI's five-year warranty, so you can be confident in its quality and performance.
Here are some of the key features of the ACI A/SCSX2 Split-Core Fixed Trip Point Current Switch:
- Monitors AC current from 0 to 200A
- Trip point of 1.5A or less
- Contact rating of 0.2A @ 200VAC/VDC
- Split-core design for easy installation
- Red LED indicates when monitored current is above trip point
- 35mm DIN rail mount
- UL/CUL listed, CE, RoHS2, and WEEE compliant
Specifications:
Monitored Current Type | AC Current |
Maximum AC Voltage | 600 VAC |
Core Style | Split Core |
Sensor Power | Induced from the Monitored Conductor |
Amperage Range | 0 to 200A |
Isolation Voltage | 2200 VAC |
Trip Point Style | Trip Point | 1.5A or Less |
Contact Type | Normally-Closed "N/C" |
“Status” Contact Rating | 0.2A @ 200 VAC/VDC |
Status LED Indication | Red LED (Monitored current is above Trip Point) |
Aperture Size | 0.75” (19.05 mm) |
Din Rail Size | 35 mm | (U.S. Patent No. 7,416,421) |
Wiring Connections | 2 Position Screw Terminal Block (Not Polarity Sensitive) |
Wire Size | 16 to 22 AWG (1.31 mm2 to 0.33 mm2) Copper Wires only |
Agency Approvals | UL/CUL US Listed (UL 508) Ind. Control Equipment (File # E309723), CE, RoHS2, WEEE |
Datasheets
ACI Fixed "Status" Switch Data Sheet | |
ACI Fixed "Status" Switch Installation Instructions |
- Mounting Type:
- Split-Core
- Setpoint:
- Fixed Trip
- Contact Type:
- Normally Closed
- Amp Range:
- 0-200A
- Trip Point:
- 1.5A
- Contact Rating:
- 0.2A @ 200VAC/VDC
- Contact Termination:
- Terminal Strip