ACI A/MSCS Mini Fixed Trip Point Current Switch
A fixed trip point current switch answers one question: is the equipment drawing current or not. The A/MSCS trips at 0.55 A or less, which is set at the factory and is not field-adjustable. That makes it the right choice for go / no-go status where the only requirement is a reliable dry contact and no commissioning adjustment is wanted.
The split-core housing opens around an existing conductor, so the A/MSCS can be fitted to wiring that is already terminated. ACI directs that the switch be installed on the line side of the power feeding the monitored equipment, and that all power sources be disconnected and locked out before the device is installed. That is what makes split-core the standard choice for retrofit work and for service vehicles, where one part covers most jobs.
The miniature housing is substantially smaller than the A/CS2 and A/SCS2 style switches, which matters in crowded panels and equipment enclosures. The unit secures to the monitored cable using a cable tie through the integrated anchor, and an attachable mounting foot allows Tek screw or 35 mm DIN rail mounting in any orientation.
Specifications on this page are taken from the ACI Mini Fixed Status data sheet (MCS & MSCS Series) and Installation & Operation Instructions I0000557 Rev. 8.0.
Best For
- Motor, pump, fan and compressor run status feedback to a BMS, PLC or DDC controller
- Proof-of-operation and run-status interlocks on air handlers and hydronic equipment
- Runtime accumulation and basic load trending from dry-contact closures
- Lighting circuit status and usage logging
- Local alarm triggering with strobes and audible devices
Warranty
Key Features
Factory-Set Trip Point
Trips at 0.55 A or less. The trip point is set at the factory and is not field-adjustable, so there is no commissioning step to perform.
Self-Powered by Induction
Power is induced from the monitored conductor. There is no 24 V supply to run, no transformer to size and no separate power wiring to install.
Split-Core Aperture
Opens around an existing conductor for retrofit installation without disconnecting any wiring.
Normally-Open (N/O) Dry Contact
Rated 0.5 A continuous @ 36 VAC/VDC, wired to a 2-position screw terminal block that is not polarity sensitive. Contact resistance is under 0.5 Ohms tripped and over 1 Meg Ohm open.
Compact Housing
At 2.650 in (67.19 mm) on the long axis, the miniature enclosure fits panels where a full-size A/CS2 style switch will not.
Cable Tie Anchor and Mounting Foot
Secures to the monitored cable with a cable tie through the integrated anchor, or mounts with the attachable foot using one Tek screw.
Technical Specifications
| ACI Item Number | 117853 |
| Core Style | Split-Core |
| Trip Point Style | Fixed Trip Point |
| Trip Point | 0.55 A or less |
| Amperage Range | 0 to 150 A |
| Contact Type | Normally-Open (N/O) |
| Contact Rating | 0.5 A continuous @ 36 VAC/VDC |
| Response Time | < 40 mS typical |
| Monitored Current Type | AC Current |
| Maximum AC Voltage | 600 VAC |
| Operating Frequency Range | 50/60 Hz |
| Sensor Power | Induced from the monitored conductor (insulated conductors only) |
| Isolation Voltage | 2200 VAC |
| Contact On Resistance | Off Resistance | < 0.5 Ohms (tripped) | > 1 Meg Ohm (open) |
| Aperture Size (Diameter) | 0.53 in (13.46 mm) |
| Operating Temperature Range | -22 to 140 °F (-30 to 60 °C) |
| Operating Humidity Range | 0 to 95% RH, non-condensing |
| Recommended Storage Temperature | RH | 41 to 95 °F (5 to 35 °C) | 40 to 85% RH, non-condensing |
| Enclosure Material | Flammability Rating | PC/ABS (polycarbonate / ABS blend) | UL94-V0 |
| Wiring Connections | 2-position screw terminal block (not polarity sensitive) |
| Wire Size | 16 to 22 AWG (1.31 mm2 to 0.33 mm2), copper wires only |
| Terminal Block Torque Rating | 4.43 to 5.31 in-lbs (0.5 to 0.6 Nm) |
| Minimum Mounting Distance | 1 in (2.6 cm) from relays, contactors and transformers |
| Agency Approvals | UL/CUL US Listed (UL 916) Energy Management Equipment, File # E334792, CE, RoHS2, WEEE |
| CE Wiring Note | Maximum wire length must not exceed 98.4 ft (30 m) to meet CE requirements |
| Product Dimensions (L x W x H) | 2.650 in (67.19 mm) x 0.940 in (23.94 mm) x 2.380 in (60.49 mm) |
| Product Weight | 0.20 lbs (0.091 kg) |
| Warranty | Five (5) Year Limited Warranty |
Not intended for use in life / safety applications or in hazardous / classified locations.
Documentation
Related Products
Frequently Asked Questions
What is the trip point of the ACI A/MSCS?
The A/MSCS trip point is 0.55 A or less. It is factory set and cannot be adjusted.
Does the ACI A/MSCS need external power?
No. Power is induced from the conductor being monitored, so no 24 VAC or 24 VDC supply, transformer or power wiring is required. The two terminals carry the dry contact output only.
Is the ACI A/MSCS solid-core or split-core?
The A/MSCS is split-core. Split-core units open around an existing conductor and install without disconnecting any wiring, which is why they are used in retrofit work.
What is the contact rating of the ACI A/MSCS?
The status contact is Normally-Open (N/O) rated 0.5 A continuous @ 36 VAC/VDC. Contact resistance is under 0.5 Ohms when tripped and over 1 Meg Ohm when open.
What amperage range does the ACI A/MSCS monitor?
The A/MSCS monitors 0 to 150 A with a maximum conductor voltage of 600 VAC and 2200 VAC isolation.
ACI Five (5) Year Limited Warranty. This product is covered by Automation Components, Inc.’s Five (5) Year Limited Warranty, published in the front of the ACI Sensors & Transmitters catalog and on the ACI website. Warranty terms are set by the manufacturer and are subject to change without notice.
- Mounting Type:
- Split-Core
- Setpoint:
- Fixed Trip
- Contact Type:
- Normally Open
- Amp Range:
- 0-150A
- Trip Point:
- 0.55A
- Contact Rating:
- 0.5 A @ 36 VAC/VDC
- Contact Termination:
- Terminal Strip
- Sensor Power:
- Self-Powered
- Warranty:
- 5-Year Limited