Skip to main content

ACI A/RH2-RP2-20'-EH : Remote Probe Relative Humidity, 2% Accuracy, RH Outputs: 0-5, 0-10 VDC & 4-20mA (Default), 20' Plenum Cable, Plastic Enclosure (Euro), Made in USA

ACI

MSRP: $935.00
$356.26
(You save $578.74 )
(No reviews yet) Write a Review
SKU:
A/RH2-RP2-20'-EH
Condition:
New
Availability:
Ships in 2-4 Days
Adding to cart… The item has been added

ACI A/RH2-RP2-20'-EH : Remote Probe Relative Humidity, 2% Accuracy, RH Outputs: 0-5, 0-10 VDC & 4-20mA (Default), 20' Plenum Cable, Plastic Enclosure (Euro), Made in USA

The ACI Relative Humidity Remote Probe is a device used for measuring relative humidity in remote sensing applications. It is designed with a thermoset polymer capacitive sensing element, which detects changes in humidity levels and provides a proportional analog output signal.

The remote probe is equipped with a hydrophobic filter, which helps repel water and protect the sensing element from moisture. This filter ensures reliable performance even in environments with high humidity or mildly corrosive atmospheres.

The remote probe wiring harness is available in lengths of 3, 6, 10, or 20 feet, allowing for flexible mounting options in various applications.

Field calibration can be performed on the humidity transmitter using the increment and decrement DIP switches. Each toggle of these switches allows for a ±0.5% RH increase or decrease in calibration.

For models with current or voltage output, calibration of the electronics can be done using both the Zero and Span potentiometers. These adjustments help ensure accurate readings based on the specific output requirements.

To protect the sensing element from direct moisture spray in wash-down applications, a vinyl cap is provided to be placed over the sintered filter. This additional protection helps maintain the performance and longevity of the sensor.

The ACI Relative Humidity Remote Probe finds application in various industries and environments, including clean rooms, process control, environmental chambers, stability chambers, pharmaceutical labs, and remote sensing applications. It is particularly useful in situations where monitoring and controlling humidity levels are critical for maintaining optimal conditions and ensuring the quality and integrity of products, experiments, or processes.

Specifications

RH Supply Voltage (Reverse Polarity Protected):

4-20 mA: 250 Ohm Load: 15 - 40 VDC / 18 - 28 VAC | 500 Ohm Load: 18 - 40 VDC / 18 - 28 VAC

0-5 VDC: 12 - 40 VDC / 18 - 28 VAC | 0-10 VDC: 18 - 40 VDC / 18 - 28 VAC

RH Output Signal: 2-wire: 4 - 20 mA (Factory Default) | 3-wire: 0-5 or 0-10 VDC and 4 - 20 mA (Field Selectable)
RH Measurement Range: 0-100%
Operating RH Range: 0 to 95% RH, non-condensing
RH Stability | Repeatability | Sensitivity: Less than 2% drift / 5 years | 0.5% RH | 0.1% RH

 

Datasheets

pdf logo ACI Remote Probe Relative Humidity Data Sheet
pdf logo ACI Remote Probe Relative Humidity Installation
Sensor Type:
Remote Probe
Humidity Element:
2%
Humidity Ouput:
4-20 mA, 0-5 VDC, or 0-10 VDC
Temperature Element:
None
CO2 Element:
None
Display:
No Display
VOC:
No
Supported Protocols:
None
Setpoint:
No Setpoint
Override:
No Override
Material:
Plastic