Skip to main content

BAPI BA/CQX : Room Particulate Sensor, Field Selectable Particulate Size of PM1.0, PM2.5 and PM10, Field Selectable Outputs of 0 to 5V, 0 to 10V and 4 to 20mA, Standard Mounting Base, 5-Year Warranty

BAPI

MSRP: $475.00
$206.00
(You save $269.00 )
(No reviews yet) Write a Review
SKU:
BA/CQX
Condition:
New
Availability:
Ships 2 Weeks
Adding to cart… The item has been added

BAPI BA/CQX : Room Particulate Sensor, Field Selectable Particulate Size of PM1.0, PM2.5 and PM10, Field Selectable Outputs of 0 to 5V, 0 to 10V and 4 to 20mA, Standard Mounting Base, 5-Year Warranty

Protect Your Indoor Air Quality with the BAPI-Stat BA/CQX “Quantum” Particulate Sensor

The BAPI-Stat BA/CQX “Quantum” Particulate Sensor is an accurate and reliable way to continuously monitor the concentration of harmful particles in your indoor environment. This sensor is ideal for commercial applications, such as offices, schools, and hospitals, where maintaining good air quality is essential.

Key features of the BAPI-Stat “Quantum” Particulate Sensor:

  • Measures PM1.0, PM2.5, and PM10 particles: These tiny particles can pose serious health risks, and the BAPI-Stat “Quantum” Sensor can help you track their levels in real-time.
  • Field-selectable outputs: Choose from 0 to 5V, 0 to 10V, or 4 to 20mA output to integrate the sensor seamlessly with your existing monitoring system.
  • Laser-based sensing: This technology provides highly accurate particle measurements, even in challenging environments.
  • Long sensor life: With a 10-year expected lifetime, you can count on the BAPI-Stat “Quantum” Sensor to provide reliable data for years to come.
  • Easy to install: The sensor comes with a standard mounting base for quick and easy installation.
  • 5-year warranty: BAPI stands behind the quality of their products with a 5-year warranty on the BAPI-Stat “Quantum” Sensor.

Protect your health and improve your indoor air quality with the BAPI-Stat BA/CQX “Quantum” Particulate Sensor.

Specifications

Power:
  • 7 to 40 VDC (4 to 20mA Output)
  • 7 to 40 VDC or 12 to 28 VAC (0 to 5 VDC Output)
  • 15 to 40 VDC or 15 to 28 VAC (0 to 10 VDC Output)
Power Consumption: 75 mA Max @ 24 VDC • 3 VA Max @ 24 VAC
Load Resistance:  VDC Output 4K Ohms Min
Sensing Element:  Laser-based, Light Scattering
Sensor Element Life:  10 Years Typical
Concentration Range: 0 to 1,000 μg/m3
Accuracy at 77°F (25°C):
  • 0 to 100 μg/m3
    • PM1.0
      • ±25 μg/m3
    • PM2.5
      • ±15 μg/m3
    • PM10
      • ±25 μg/m3
  • 100 to 1,000 μg/m3
    • PM1.0
      • ±25% of reading
    • PM2.5
      • ±15% of reading
    • PM10
      • ±25% of reading
Response Time:  <6 Seconds
Wiring:  3 Wires, 16 to 22 AWG
Environmental Operating Range:
  • -4 to 158°F (-20 to 70°C)
  • 0 to 95%RH Non-condensing
Enclosure Material:  ABS Plastic, UL94 V-0
Agency: CE EN 61326-1:2013 EMC, UL94 V-0, RoHS

 

Datasheets

pdf logo BAPI Particulate Sensor, BAPI-Stat “Quantum” Enclosure, Datasheet for Submittal
pdf logo Particulate Sensor, BAPI-Stat “Quantum” Enclosure, Instructions
pdf logo Particulate Sensor Overview - App Note
Sensor Type:
Wall Mount
Output Signal:
4-20mA, 0-5 VDC, or 0-10 VDC
CO2 Element:
None
Humidity Element:
None
VOC Element:
None
Temperature Element:
None
Display:
None
Supported Protocols:
None