BAPI BA/T1K[0 TO 100C]-H200-O-BB Overview
The BAPI BA/T1K[0 TO 100C]-H200-O-BB is an outside air humidity and temperature transmitter that combines a ±2% RH capacitive polymer humidity transmitter (0 to 5 VDC output) with a T1K 1K platinum RTD temperature transmitter (4 to 20 mA output scaled 0 to 100°C), housed in a BAPI-Box enclosure rated IP66 / NEMA 4.
BAPI calibrates its humidity transmitters at 10 points from 10 to 90% RH, eliminating field calibration. The humidity sensor sits in a 1 in. diameter probe below the enclosure, protected by a replaceable 80 micron sintered stainless steel filter.
The 0 to 5 VDC humidity output spans 0 to 100% RH, powered from 10 to 35 VDC or 12 to 27 VAC. The temperature transmitter runs on its own 12 to 40 VDC supply and sends a 4 to 20 mA signal scaled 0 to 100°C from a 1K platinum RTD (385 curve).
The BAPI-Box enclosure is UV-resistant polycarbonate rated IP66 and NEMA 4, and closed cell foam on the back seals it to the mounting surface.
Specifications verified against BAPI Outside Air Units datasheet Rev. 10/06/25, BAPI installation instructions 26415 rev. 10/12/26, enclosure dimension drawings Rev. 05/26/17 and BAPI enclosure styles application note Rev. 05/02/23. Last reviewed by ZOT Supply on November 3, 2026.
Best For
- Controllers with 0 to 5 VDC analog inputs for outdoor humidity
- Controllers that need outdoor air temperature as a 4 to 20 mA signal scaled 0 to 100°C
- Panels with a DC supply for the temperature transmitter (12 to 40 VDC)
- Exterior walls exposed to rain, sleet, snow, windblown dust and hose-directed water (NEMA 4)
Warranty
BAPI warrants its products to be free from defects in materials and workmanship for five years from the date of sale.
Key Features
10-Point Calibration
Calibrated at 10 points from 10 to 90% RH, eliminating field calibration.
0 to 5 VDC Humidity Output
0 to 5 VDC humidity output for 0 to 100% RH, powered from 10 to 35 VDC or 12 to 27 VAC.
1K RTD Temperature Transmitter
T1K transmitter with a 4 to 20 mA output scaled 0 to 100°C, ±0.065% of span system accuracy.
IP66 / NEMA 4 BAPI-Box
UV-resistant polycarbonate enclosure, UL 94 V-0, dust tight and protected against powerful water jets.
Replaceable Sintered Filter
80 micron sintered stainless steel filter unscrews for cleaning; replacement part BA/HDOFS3.
Reverse Polarity Protected
The humidity transmitter is polarity sensitive and reverse polarity protected.
ZOT Supply is an authorized distributor of BAPI products.
Technical Specifications
| Humidity | |
|---|---|
| Sensor | Capacitive polymer |
| Accuracy | ±2% RH (10 to 80% RH @ 25°C), ±3% RH (80 to 90% RH @ 25°C), non-condensing |
| Calibration | 10 points from 10 to 90% RH |
| Drift | 0.5% per year |
| Response Time | < 5 seconds in moving air |
| RH Linearity | Negligible, factory corrected linear from 10 to 80% RH |
| RH Hysteresis | Factory corrected to <1% |
| Output | 0 to 5 VDC at 0 to 100% RH |
| Low RH Behavior | Output goes to its maximum value if humidity drops to 5% RH or below |
| Output Impedance | 10 kΩ |
| Wiring | Red: power; White: humidity output to controller analog input; Black: common (ground for power and humidity output) |
| Power | |
| Humidity Transmitter Supply | 10 to 35 VDC, 22 mA max; 12 to 27 VAC, 0.53 VA max |
| Temperature Transmitter Supply | 12 to 40 VDC |
| Temperature Transmitter | |
| Transmitter | T1K |
| Output | 4 to 20 mA |
| Range | 0 to 100°C |
| Output Load | 850 Ω @ 24 VDC |
| Wiring | Red: power (12 to 40 VDC); Black: 4 to 20 mA output to controller analog input |
| System Accuracy | ±0.065% of span |
| Span and Zero Limits | Span 30 to 1000°F (17 to 555°C); zero -148 to 900°F (-100 to 482°C) |
| Sensor | 1K platinum RTD, 385 curve, 2-wire |
| RTD Accuracy | ±0.55°F (±0.3°C), standard accuracy |
| RTD Stability | ±0.25°F (±0.14°C) |
| RTD Self Heating | 0.4°C/mW @ 0°C |
| RTD Probe Range | -40 to 221°F (-40 to 105°C) |
| Physical | |
| Probe | 2.4 in. below enclosure, 1 in. diameter |
| Filter | 80 micron sintered stainless steel, replaceable (BA/HDOFS3) |
| Enclosure | BAPI-Box (BB) |
| Enclosure Material | UV-resistant polycarbonate, UL 94 V-0 |
| Enclosure Rating | IP66, NEMA 4 |
| Enclosure Dimensions | 4.15 x 5 x 2.5 in. (105.4 x 127 x 63.5 mm), W x H x D |
| Ports | 1/2 in. NPSM ports and a 1/2 in. drillable port |
| Mounting Seal | Closed cell foam |
| Termination | Open wire; 18 to 26 AWG with sealant filled crimp connector (BA/SFC1000-x00) or 26 to 16 AWG with sealant filled wire nut (BA/SFC2000-x00) |
| Wiring Practice | Twisted pair, 22 AWG minimum; do not run in the same conduit as AC power wiring; keep at least 5 ft from radio-emitting devices |
| Environment and Compliance | |
| Operating Range (Humidity Transmitter) | -40 to 158°F (-40 to 70°C), 0 to 100% RH |
| Temperature Transmitter Ambient | -4 to 158°F (-20 to 70°C), 0 to 95% RH, non-condensing |
| Compensation | Fully temperature compensated |
| Agency | CE EN 61326-1:2013 EMC, RoHS |
| Warranty | 5 years from date of sale |
Documentation
Frequently Asked Questions
What is the BAPI BA/T1K[0 TO 100C]-H200-O-BB?
The BAPI BA/T1K[0 TO 100C]-H200-O-BB is an outside air humidity and temperature transmitter that combines a ±2% RH capacitive polymer humidity transmitter (0 to 5 VDC output) with a T1K 1K platinum RTD temperature transmitter (4 to 20 mA output scaled 0 to 100°C), housed in a BAPI-Box enclosure rated IP66 / NEMA 4.
What power supply does the BAPI BA/T1K[0 TO 100C]-H200-O-BB need?
The humidity transmitter runs on 10 to 35 VDC (22 mA max) or 12 to 27 VAC (0.53 VA max). Power requirements depend on the humidity output type. The temperature transmitter needs 12 to 40 VDC.
How accurate is the BAPI BA/T1K[0 TO 100C]-H200-O-BB?
Humidity accuracy is ±2% RH (10 to 80% RH @ 25°C), ±3% RH (80 to 90% RH @ 25°C), non-condensing. The temperature transmitter is accurate to ±0.065% of span, and its 1K platinum RTD to ±0.55°F (±0.3°C).
How do I convert the 0 to 5 VDC output to percent RH?
Use %RH = V / 0.05. The output spans 0 to 100% RH.
How do I convert the 4 to 20 mA temperature output to temperature?
Use T = Tlow + ((mA - 4) x Tspan) / 16, where Tspan = Thigh - Tlow. For this unit, Tlow and Thigh are the ends of the 0 to 100°C range.
Can the BAPI-Box enclosure take hose-directed water?
Yes. The BAPI-Box is rated IP66 (dust tight and protected against powerful water jets from any direction) and NEMA 4 (protected against rain, sleet, snow, windblown dust, splashing water and hose-directed water, and undamaged by external ice formation).
Does an outdoor sensor need a weather shade?
Radiant heat from building surfaces and parking lots affects outdoor temperature and humidity sensors. The BAPI Weather Shade blocks that radiant heat, improving sensor accuracy.
Where should an outside air humidity sensor be mounted?
Mount it in a permanently shaded area away from windows and doors, out of direct sunlight, with the sensor probe pointed down. Seal the wiring hole with caulk after wiring, and terminate with sealant filled connectors.
- Sensor Type:
- Outside Air
- Humidity Element:
- 2%
- Output Signal:
- 0-5 VDC
- Temperature Element:
- Transmitter
- CO2 Element:
- None
- Display:
- No Display
- VOC Element:
- None
- Probe Length:
- 2.4
- Enclosure:
- NEMA 4 Enclosure
- Supported Protocols:
- None