BAPI BA/ZPM-SR-AT-D-BB : Zone Pressure Multi-Sensor (ZPM) Differential Pressure Sensor, 10 Field Selectable Standard Pressure Ranges and 5 Field Selectable Outputs, Attached Static Probe, NEMA 4 Enclosure, LCD Display, 5-Year Warranty
Features & Options
- 10 Pressure Ranges and 5 Output Options
- Non-Flow-Through Sensor so There’s No Cross Contamination of Air
- IP66-rated Enclosure with Thumb Latch Closure
- NIST Certificate Included with With Each Unit at No Extra Charge
- Outputs, Ranges and Units all Easily Set in the Field Without Power
- Three LEDs to Indicate Current Pressure Status Without Having to Access the BAS
Standard Range Units
- 0 to 1.00 / 0 to 2.00 / 0 to 2.50 / 0 to 3.00 / 5.00 to 5.00 / -1.00 to 1.00 / -2.00 to 2.00 / -2.50 to 2.50 / -3.00 to 3.00 / -5.00 to 5.00
Outputs Available
- 4 to 20 mA / 0 to 5 V / 0 to 10 V / 2 to 10 V / 1 to 5 V
Specifications
Power: | 7 to 40 VDC (4 to 20 mA Output) 7 to 40 VDC or 18 to 32 VAC (0 to 5 or 1 to 5 VDC Output) 13 to 40 VDC or 18 to 32 VAC (0 to 10 or 2 to 10 VDC Output) |
Power Consumption: | 20 mA max, DC only at 4 to 20 mA Output / 5.2 mA max DC at 0 to 5 or 0 to 10 VDC Output 0.12 VA max AC at 0 to 5 or 0 to 10 VDC Output |
Load Resistance: | 4 to 20 mA Output 850 Ω Maximum @ 24 VDC 0 to 5 or 0 to 10 VDC Output 6KΩ Minimum |
System Accuracy: | ±0.25% FS at 72°F (22°C) for all units |
Stability: | ±0.25% FS per year |
Media: | Clean, dry, non-corrosive gases |
Compensated Temperature Range: | 32 to 122°F (0 to 50°C) |
Environmental Operating Range: | -4 to 140°F (-20 to 60°C) |
Storage Temperature: | -40 to 185°F (-40 to 85°C) |
Humidity: | 0 to 95% RH, non-condensing |
Wiring: | 2 wires (4 to 20mA Current loop) 3 wires (AC or DC powered, VDC output) |
Port Size: | 1/4” barb |
Enclosure Material: | UV-resistant Polycarbonate, UL94 V-0 |
Enclosure Rating: | IP66, NEMA 4 |
Enclosure Dimensions: | 5.49 x 4.11 x 2.5” (139 x 104 x 64mm) |
Agency: | CE EN 61326-1:2013 EMC (Industrial Electromagnetic Environment), UL, RoHS |
Datasheets
BAPI ZPM in a BAPI-Box Pressure Sensor, Datasheet for Submittal | |
ZPM in a BAPI-Box - Zone Pressure Sensor Instructions - Standard Ranges | |
Frequently Asked Questions - BAPI's Pressure Line of Products |
- Output Signal:
- 4-20 mA, 0-5 VDC, or 0-10 VDC
- Pressure Type:
- Differential
- Pressure Ranges:
- 0 to 5 Inch
- Media:
- Dry
- Accuracy:
- 0.25%
- LCD Display:
- LCD Display
- Zero Function:
- Yes
- Range Setting:
- Adjustable
- Communication:
- None
- Series:
- ZPM Series