Skip to main content

Dent Instruments PS12HD-P-D-N : PowerScout 12 HD Multi-Circuit Power Submeter, No Enclosure, Includes Display, Revenue Grade, BACnet or Modbus Protocol

Dent Instruments

MSRP: $1,675.00
$1,199.99
(You save $475.01 )
(No reviews yet) Write a Review
SKU:
PS12HD-P-D-N
Condition:
New
Availability:
Ships in 1-2 days
Adding to cart… The item has been added

Dent Instruments PS12HD-P-D-N : Dent Instruments PS12HD-P-D-N : PowerScout 12 HD Multi-Circuit Power Submeter, No Enclosure, Includes Display, Revenue Grade, BACnet or Modbus Protocol

The PowerScout 12 HD is a multi-channel power meter offering maximum flexibility and accurate monitoring for various applications, including:

  • Tenant Submetering: Track individual energy use in apartments, malls, offices, and more.
  • Net Metering: Manage renewable energy generation from solar or wind power.
  • Data Center Monitoring: Ensure efficient power usage in your critical IT infrastructure.
  • Commercial, Retail, and Industrial Facilities: Gain insights into energy consumption for informed decision-making.

Key Benefits:

  • Versatile Configuration: Monitor up to 12 single-phase or 4 three-phase circuits with various CT options.
  • High Accuracy: Delivers revenue-grade data (ANSI C12.20-2010 Class 0.2) with 1-second updates.
  • Easy Installation: Line-powered with broad voltage range, field-selectable protocols (Modbus or BACnet),and pre-configuration via ViewPoint HD software.
  • Seamless Integration: Connects to any Building Management System (BMS) using BACnet or Modbus protocols.
  • Standardized Features: Eliminates the need for multiple SKUs with features like flexible communication protocols and CT compatibility.

Technical

Service Type Single Phase, Split Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire (Delta)
Power From L1 Phase to L2 Phase. 90-600VAC RMS CAT III 50/60Hz, 500mA AC Max. Use of 12 volt auxiliary output requires 100 VAC minimum input voltage.
AC Protection 0.5A Fuse 200kA interrupt capacity
Power Out Unregulated 12VDC output, 200 mA, self-resetting fuse.
Voltage Channels 90-346 Volts AC Line-to-Neutral, 600V Line-to-Line, CAT III.
Current Channels 12 channels, 0.525 VAC max, 333 mV CTs, 0-4,000 Amps depending on CT
Maximum Current Input 150% of current transducer rating (mV CTs) to maintain accuracy. Measure up to 4000A with RōCoil CTs
Measurment Type True RMS using high-speed digital signal processing (DSP) with continuous sampling
Line Frequency 50/60 Hz (45-70 Hz measurable range). Measurement taken L1-N.
Waveform Sampling 1.8 kHz
Parameter Update Rate 1 second
Measurments Volts, Amps, kW, kVAR, kVA, aPF, dPF, kW demand, kVA demand, Import (Received) kWh, Export (Delivered) kWh, Net kWh, Import (Received) kVAh, Export (Delivered) kVAh, Net kVAh, Import (Received) kVARh, Export (Delivered) kVARh, Net kVARh, THD, Theta, Frequency. All parameters for each phase and element total
Accuracy 0.2% ANSI C12.20-2010 Class 0.2
Resolution Values in IEEE-754 single precision floating point format (32 bit).
Display Optional 4-line display, tri-color backlight (PhaseChekTM)
Alarm Output Over/Under Voltage & Current (SPDT Relay - 30 VDC)
Pulse Inputs Four inputs. 3.3V sourcing voltage (current limited) to customer dry contact pulse output. Max pulse rate 10 Hz (50 mSec minimum transition time).

Communications

Hardware RS-485, Ethernet, and USB (for configuration only)
Supported Protocols Modbus RTU, BACnet MS/TP, Modbus TCP or BACnet IP
Max Communication Length 1200 meters with Data Range of 100K bits/second or less
Communication Rate (BAUD) 9600 (Default), 19200, 38400, 57600, 76800, 115200
Data Bits 8
Parity None, Even, Odd
Stop Bit 2, 1
Termination None provided

Mechanical

Wire Connections 12-28 AWG 600 VAC, Voltage connection must be #14 AWG or larger & 600 VAC rated
Mounting Panel Mount/Enclosure
High Voltage Cover IP30. Available with PS12 Enclosure Models
Operating Temperature -20° to 60°C (-4° to 140°F)**
Humidity 5% to 95% non-condensing
Enclosure ABS Plastic, 94-V0 flammability rating. Connections: 1” EMT conduit
Enclosure Dimensions (L) 24.8cm x (W) 25.1cm x (H) 8.0 cm (9.8” x 9.8” x 3.1”)
Mounting Plate Dimensions (L) 17.8cm x (W) 26.3cm x (H) 8.0 cm (7.0” x 10.4” x 3.1”)

 

Datasheets

pdf logo Dent POWERSCOUT 12 HD Datasheet
pdf logo Dent Operators Guide PowerScout HD Networked Power Meters
pdf logo Dent PowerScout HD Series How Do We Compare
pdf logo Dent BACnet Protocol Implementation Conformance Statement
pdf logo Dent Declaration of Conformity
pdf logo Powerscout to Powerscout HD Migration Guide

Warranty Statement

DENT Instruments, Inc. promises buyer that any product sold by DENT Instruments, Inc. shall be free from material defects in design, materials, or manufacturing for the period shown on the current data sheet for that product beginning from the manufacture date; provided, however, that the warranty shall not extend to ordinary wear and tear, or to normally replaceable components (e.g., batteries and humidity sensor elements). During the warranty period, DENT Instruments, Inc. may repair or replace (at its sole discretion) any product suffering from a warranty defect and returned freight prepaid by buyer, with no charge to buyer for any warranty repair or replacement. The warranty shall remain in full force and effect for said period, provided that the product: (1) was installed, operated, and maintained properly; (2) has not been abused or misused; (3) has not been repaired, altered, or modified outside of DENT Instruments’ authorized facilities; (4) has not been sold subject to other warranty terms specified at the time of sale. This warranty provides specific legal rights that may be varied by local laws.

POWERSCOUT SERIES INSTRUMENTS & ACCESSORIES

Seller warrants to Buyer that PowerScout Series instruments products and accessories or services are free from substantial defect in material and workmanship under normal use given prior installation and maintenance for the period of 5 years (60 months) after delivery.

LIMITATION OF WARRANTY

CORRECTION OF DEFECTS BY REPAIR, REPLACEMENT, SERVICE OR CREDIT WILL BE AT SELLER’S OPTION AND CONSTITUTE FULFILLMENT OF ALL OBLIGATIONS TO BUYER FOR BREACH OF WARRANTY.

Seller assumes no warranty liability with respect to defects in the product caused by: (a) modification, repair, installation, operation or maintenance of the product by anyone other than Seller or its agent, except as described in Seller’s documentation; or (b) the negligent or other improper use of the product.

Other manufacturers’ equipment purchased by Seller and resold to Buyer will be limited to that manufacturers’ warranty. Seller assumes no warranty liability for other manufacturers’ equipment furnished by Buyer.

No agent, distributor, or representative is authorized to make any warranties on behalf of Seller or to assume for Seller any other liability in connection with any Seller product or service.

DISCLAIMER OF WARRANTY

Buyer understands and agrees as follows:

THE ABOVE WARRANTY REPLACES ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, & ALL OTHER OBLIGATIONS OR LIABILITIES OF SELLER, INCLUDING ANY WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. ALL OTHER WARRANTIES ARE DISCLAIMED AND EXCLUDED BY SELLER.THE FOREGOING WILL BE THE SOLE AND EXCLUSIVE REMEDY WHETHER IN CONTRACT, TORT, OR OTHERWISE, & SELLER WILL NOT BE LIABLE FOR INJURIES OR DAMAGES CAUSED BY THE GROSS NEGLIGENCE OF SELLER. THIS LIMITATION APPLIES TO ALL SERVICES AND PRODUCTS DURING AND AFTER THE WARRANTY PERIOD.

LIMITATION OF REMEDIES

IN NO EVENT WILL SELLER BE LIABLE FOR ANY SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES OR COMMERCIAL LOSSES EVEN IF SELLER HAS BEEN ADVISED OF THE POSSIBILITY THEREOF.

 

Supported Protocols:
Modbus RTU, BACnet MS/TP, Modbus TCP or BACnet IP
Meter Type:
Multi-Circuit
Mounting:
Panel Mount/Enclosure
Current Channels:
12

Videos Hide Videos Show Videos