Skip to main content

Dwyer GSTA-C : Wall Mount Carbon Monoxide Transmitter, Selectable 200 or 500 PPM, Selectable Output Signals: 4-20 mA, 0-5 V, or 0-10 V, Normal or Reverse Output, 5-Year Warranty

Dwyer

MSRP: $228.05
$216.65
(You save $11.40 )
(No reviews yet) Write a Review
SKU:
GSTA-C
Condition:
New
Availability:
Ships in 1-2 Days
Adding to cart… The item has been added

Dwyer GSTA-C : Wall Mount Carbon Monoxide Transmitter, Selectable 200 or 500 PPM, Selectable Output Signals: 4-20 mA, 0-5 V, or 0-10 V, Normal or Reverse Output, 5-Year Warranty

The Series GSTA Carbon Monoxide Gas Transmitters are designed to monitor gas concentrations in mechanical rooms, underground parking garages, and loading docks. Specifically engineered to measure the exhaust from gasoline engines, these transmitters offer versatile gas-sensing solutions compatible with most building management controllers through field-selectable current and voltage outputs.

Benefits/Features

  • Easy Maintenance: Industrial-grade, replaceable electrochemical sensors with a typical lifespan of two years.
  • Inventory Efficiency: Field-selectable outputs reduce the need for multiple units.

Applications

  • Ventilation monitoring in garages or loading docks.
  • Air quality monitoring in mechanical rooms.

Specifications: 

Sensor: Field replaceable electrochemical, 2 years typical lifespan.
Range: GSTA CO: Switch selectable 200 or 500 PPM
Output Drift: <5% per year in air.
Coverage Area: 5000 to 7500 sq ft typical.
Accuracy: CO: 2% FS, at the time of calibration.
Resolution: CO: 1 PPM
Temperature Limits: -4 to 122°F (-20 to 50°C).
Storage Temperature: For best sensor life, 32 to 68°F (0 to 20°C).
Humidity Limits: 15 to 90% RH constant; 0 to 99% RH intermittent.
Response Time: <45 s to 90% CO
Span and Zero Adjustment: Via onboard push-buttons or using optional A-449 display
Housing: UV resistant glass filled polycarbonate.
Output Signals: GSTA: Switch selectable 4-20 mA (loop powered), 0-5 V @ 5
mA, or 0-10 V @ 5 mA; Switch selectable 0-5 V/1-5 V and 0-10 V/2-10 V; Switch selectable normal or reverse output
Power Requirements: GSTA: Current output: 10-35 VDC, Voltage output: 15-35 VDC or 15-29 VAC
Electrical Connection: Removable terminal block, knockouts for conduit fitting.
Calibration: Via onboard push-buttons (LCD model only) or using optional A-449
display. Span gas concentration is field selectable.
Enclosure Rating: IP64.
Weight: 1 lb (0.45 kg).
Compliance: CE.

 

Datasheets

pdf logo Dwyer GSTA Series | Carbon Monoxide Data Sheet
pdf logo Dwyer GSTA Series | Carbon Monoxide Catalog Pages
pdf logo Dwyer GSTA Series | Specifications - Installation and Operating Instructions
pdf logo Dwyer GSTA Series | Specifications -Application and Installation Note
Enclosure Style:
Wall
Gas Element:
Carbon Monoxide
Analog Output:
1
Relay Output:
None
Communication:
None
Display: