Dwyer GSTA-C-D : Duct Mount Carbon Monoxide Transmitter, Selectable 200 or 500 PPM, Selectable Output Signals: 4-20 mA, 0-5 V, or 0-10 V, Normal or Reverse Output, 5-Year Warranty
The Series GSTA Carbon Monoxide Gas Transmitters are designed to monitor gas concentrations in mechanical rooms, underground parking garages, and loading docks. Specifically engineered to measure the exhaust from gasoline engines, these transmitters offer versatile gas-sensing solutions compatible with most building management controllers through field-selectable current and voltage outputs.
Benefits/Features
- Easy Maintenance: Industrial-grade, replaceable electrochemical sensors with a typical lifespan of two years.
- Inventory Efficiency: Field-selectable outputs reduce the need for multiple units.
Applications
- Ventilation monitoring in garages or loading docks.
- Air quality monitoring in mechanical rooms.
Specifications:
Sensor: | Field replaceable electrochemical, 2 years typical lifespan. |
Range: | GSTA CO: Switch selectable 200 or 500 PPM |
Output Drift: | <5% per year in air. |
Coverage Area: | 5000 to 7500 sq ft typical. |
Accuracy: | CO: 2% FS, at the time of calibration. |
Resolution: | CO: 1 PPM |
Temperature Limits: | -4 to 122°F (-20 to 50°C). |
Storage Temperature: | For best sensor life, 32 to 68°F (0 to 20°C). |
Humidity Limits: | 15 to 90% RH constant; 0 to 99% RH intermittent. |
Response Time: | <45 s to 90% CO |
Span and Zero Adjustment: | Via onboard push-buttons or using optional A-449 display |
Housing: | UV resistant glass filled polycarbonate. |
Output Signals: | GSTA: Switch selectable 4-20 mA (loop powered), 0-5 V @ 5 mA, or 0-10 V @ 5 mA; Switch selectable 0-5 V/1-5 V and 0-10 V/2-10 V; Switch selectable normal or reverse output |
Power Requirements: | GSTA: Current output: 10-35 VDC, Voltage output: 15-35 VDC or 15-29 VAC |
Electrical Connection: | Removable terminal block, knockouts for conduit fitting. |
Calibration: | Via onboard push-buttons (LCD model only) or using optional A-449 display. Span gas concentration is field selectable. |
Enclosure Rating: | IP64. |
Weight: | 1 lb (0.45 kg). |
Compliance: | CE. |
Datasheets
- Enclosure Style:
- Duct
- Gas Element:
- Carbon Monoxide
- Analog Output:
- 1
- Relay Output:
- None
- Communication:
- None
- Display:
- No Display