Kit contents and field wiring guidance from the Prolon VAV ProPack quick installation guide. Specifications from the Prolon Zone Controller (PL-VC2000) datasheet REV 7.3.0 (PL-DATA-VC2000-C/F-EN) and the VAV Zone Controller VC2000 Series Hardware Guide REV 7.3.2 (PL-HRDW-VC2000-EN), reviewed September 19, 2026.
The kit supplies the PL-VC2000-PI controller, the zone wall sensor, the duct temperature sensor, and the wiring diagram and installation instructions together. The 24 VAC transformer and field wiring are sourced separately.
Best For
- Pressure independent VAV zone control on single-zone VAV boxes
- Contractor installations using Prolon's prepackaged VAV controller and sensor set
- Zone temperature control from a wall sensor, with optional network integration
- Installs that need a duct temperature sensor at the inlet, reading supply air from the RTU or AHU
Warranty
Key Features
Bundled Zone Hardware
Controller, wall sensor, duct sensor, wiring diagram and installation instructions are supplied together in one kit.
Pressure Independent Control
The included PL-VC2000-PI regulates to an airflow setpoint using its 0-2 inch WC (0-500 Pa) airflow sensor.
Integrated 45 in-lb Actuator
The controller mounts directly to the damper shaft with a Belimo actuator using Halomo technology, no separate actuator required.
Modbus RTU or BACnet MS/TP
One RS485 network port runs either protocol on networks of up to 127 nodes.
Wall Sensor Configuration
The PL-T1000-WGL sets zone setpoints and provides monitoring and configuration of the controller from the digital sensor.
Supply Air Monitoring
The PL-DT-T6 reports inlet air temperature from the RTU or AHU to the controller analog input.
Kit Contents
| Component | Details |
|---|---|
| PL-VC2000-PI VAV Controller | Pressure independent VAV zone controller with an integrated 45 in-lb Belimo actuator, one triac digital output, one 0-10 VDC analog output, and Modbus RTU or BACnet MS/TP over RS485. |
| PL-T1000-WGL Wall Sensor | T1000 series wall module for zone temperature input and controller setup and navigation. |
| PL-DT-T6 Duct Temperature Sensor | Sensor intended for inlet (supply air) temperature monitoring from the RTU or AHU. |
| Documentation | Quick installation instructions and wiring diagram included with the kit. |
| Country of Origin | Made in Canada |
Technical Specifications
Installation and wiring
- 24 VAC supply required; the transformer is not included. When one transformer powers several PL-VC2000-PI controllers, allow 5 VA per controller.
- 24 VAC supply wiring: #18/2 AWG stranded; shielded wire recommended.
- Wall sensor data wiring: #22/2 AWG stranded, shielded, low capacitance, twisted pair recommended.
- The duct temperature sensor connects to the controller analog input terminals 13 and 14.
- Pressure independent airflow control uses high and low pressure pickup tubing from the airflow measuring station.
- Occupied mode setpoints come from the wall sensor; damper behavior responds to space demand and the duct temperature relationship.
- Default airflow setpoints, pressure independent: minimum ventilation setpoint 90 CFM, maximum ventilation setpoint 225 CFM.
Network and connectivity
- The controller daisy chains to other Prolon devices over the RS485 NET A and NET B terminals.
- Internet connectivity requires a PL-NC2000 Network Controller, sold separately.
- Wireless wall sensor capability uses PL-TREE-COM adapters, sold separately; both devices still require 24 VAC power.
- Smartphone app and Focus software configuration use the PL-485-BT Prolon Connection Tool, sold separately.
Not included
- 24 VAC transformer
- Field wiring, both 24 VAC and data cable
- PL-485-BT Prolon Connection Tool
- PL-NC2000 Network Controller
Documentation
Frequently Asked Questions
What ships in the PL-PROPACK-VAV?
One PL-VC2000-PI VAV controller, one PL-T1000-WGL wall sensor, one PL-DT-T6 duct temperature sensor, and the quick installation instructions and wiring diagram.
Is a transformer included?
No. The kit requires a 24 VAC supply and the transformer is not included. When one transformer powers several PL-VC2000-PI controllers, allow 5 VA per controller.
What wire does the kit need?
Use #18/2 AWG stranded for the 24 VAC supply, with shielded wire recommended, and #22/2 AWG stranded, shielded, low capacitance cable for the wall sensor data run, with a twisted pair recommended. The duct temperature sensor lands on the controller analog input terminals 13 and 14.
Can the kit be networked or reached remotely?
The controller daisy chains to other Prolon devices over the RS485 NET A and NET B terminals. Internet connectivity requires a PL-NC2000 Network Controller, sold separately. Smartphone app and Focus software configuration use the PL-485-BT Prolon Connection Tool, also sold separately.
Does the kit support a wireless wall sensor?
Wireless wall sensor operation is supported using PL-TREE-COM adapters, sold separately. Both devices still require 24 VAC power.
What are the default airflow setpoints?
The included guide ships the pressure independent defaults at a minimum ventilation setpoint of 90 CFM and a maximum ventilation setpoint of 225 CFM.
- Controller Type:
- VAV Zone
- Digital Outputs:
- 1
- Analog Outputs:
- 1
- Inputs:
- 1
- Communication:
- Modbus RTU or BACnet MS/TP (RS485)