Prolon PL-C1050-VAV-PI : VAV Zone Controller, 4 Digital Outputs, 1 Analog Outputs, 3 Analog Inputs, 1 Digital Input, Pressure Independent Iair Flow Sensor Installed), Modbus RTU (RS485)

The Prolon C1050 VAV series zone controllers are designed for variable air volume zoning systems. The built-in microprocessor offers precise digital control to maximize performance. The outputs and control sequences are all fully configurable, either locally or remotely, using free software or from the digital room sensor. A remote actuator (floating or modulating) connects to the C1050 VAV for damper control. When in a network, the C1050 can share information such as the occupancy state, the demand, the supply temperature and more.

Features

  • Proportional integral (PI) control loops maximize performance
  • Designed to use single or multiple outboard damper actuators (floating / modulating)
  • Up to 4 digital outputs and 1 analog output, all protected with resettable fuses
  • Supports Modbus and BACnet protocols
  • Remote monitoring and configuration with FREE Prolon Focus software
  • Stand-alone or networked (up to 127 nodes)
  • Configurable sequences for radiant floor and duct heater
  • Works with or without a flow sensor
  • Monitoring and configuration from a digital sensor
  • Quick and easy installation using detachable numbered terminal blocks
  • Possibility of multiple actuator control
  • FlexiZone system facilitates multiple zone management by evaluating the average weighted demand of the zones using customized groups

Specifications

Supply 24 VAC ±10%, 50/60 Hz, Class 2
Power 2 VA (consumption), 32 VA (input)
Inputs
  • Room – thermistor 10K / Duct – thermistor 10K
  • Setpoint – potentiometer 0-10K
  • Optional flow sensor / External clock – dry contact
  • Override – dry contact / Digital room sensor
Flow sensor 0-3000 ft/min
Digital Outputs 4 triac outputs, 10-30 VAC source or sink, 300 mA max (resettable fuse), ON/OFF or pulsed, heating/ cooling
Analog Outputs 0-10 VDC, 40 mA max (resettable fuse), modu- lating, ON/OFF or pulsed, heating or cooling
Indication lights (LED) State of each output / Communication / Power / State of microprocessor
Microprocessor PIC18F6722, 8 bits, 40 MHz, 128KB FLASH memory
Casing Molded ABS, UL94-HB
Communication 1x Modbus RTU (RS485) or BACnet MS/ TP (RS485) up to 127 nodes, 1 RS485 port for digital sensor or computer interface
Baud Rates 9600, 19200, 38400, 57600, 76800, 115200
Connection Removable screw-type terminal blocks (max 16 AWG) and RJ45 modular jacks
Dimensions 6.2” x 5.2” x 2.5” (157mm x 132mm x 64mm)
Weight 0.85 lbs (0.39 kg)
Environment -4 to 122 oF (-20 to 50 oC) Non-Condensing
Certification UL916 Energy Management Equipment, CAN / CSA-C22.2, FCC part 15: 2012 class B, RoHS

 

Datasheets

Controller Type:
VAV Zone
Digital Outputs:
4
Analog Outputs:
1
Inputs:
4
Communication:
Modbus RTU (RS485)