Prolon PL-C1050-BLR : Boiler Controller, 4 Digital Outputs, 1 Analog Output, 3 Analog Inputs, 1 Digital Input, Modbus RTU (RS485)

Prolon

Your Price:  $715.72
(No reviews yet) Write a Review
SKU:
PL-C1050-BLR
Condition:
New
Availability:
Ships in 1-2 Days
Adding to cart… The item has been added
ApplicationBoiler Controller
Digital Outputs4 triac
Analog Output1
Inputs3 analog, 1 digital
CommunicationModbus RTU (RS485)
Supply24 VAC, Class 2
The Prolon PL-C1050-BLR is a Modbus RTU boiler controller for hydronic heating systems, with outdoor reset of supply water temperature, pump and boiler lead-lag, and an optional three-way valve sequence.

Specifications on this page are taken from the Prolon Boiler Controller datasheet, REV 7.3.0 / PL-DATA-C1050BLR-C/F-EN.

The PL-C1050-BLR runs a hydronic boiler plant: it resets supply water temperature against outside air, stages the boilers, and manages the pumps. PI control loops hold the supply water setpoint rather than bouncing the boiler on and off around it.

It handles two boiler stages, which can be two boilers or one two-stage boiler, or a single modulating boiler with an optional backup stage. Lead-lag sequences are available for both the pumps and the boilers so runtime spreads evenly across the plant.

Pump activity can follow outside temperature, a call for heat, or both, and a configurable pump exercise sequence can run the pumps during extended periods of inactivity. An optional three-way valve sequence is included.

Best For

  • Boiler systems with up to 2 stages, or 1 modulating boiler with a backup stage
  • Loops needing supply water setpoint reset from outside temperature
  • Plants using pump and boiler lead-lag, or an optional three-way valve sequence

Key Features

Outdoor reset of supply water

Supply water setpoint resets based on outside temperature, and can be offset by a network-received demand or occupancy state.

Two boiler stages or one modulating boiler

Controls up to 2 boiler stages, being multiple boilers or a single multistage boiler, or 1 modulating boiler with an optional backup stage.

Pump and boiler lead-lag

Various lead-lag sequences are available for both the pumps and the boilers.

Pump exercise sequence

Configurable pump exercise sequence for extended periods of inactivity.

Optional three-way valve control

An optional control sequence for a three-way valve is included; the analog output serves the valve.

Protected outputs

All 4 digital outputs and the analog output are protected by resettable fuses.

Technical Specifications

SpecificationPL-C1050-BLR Value
Supply24 VAC ±10%, 50/60 Hz, Class 2
Power2 VA (consumption), 32 VA (input)
Inputs
  • Outside air - thermistor 10K
  • Return water - thermistor 10K
  • Supply water - thermistor 10K
  • Proof of pump - dry contact
Digital Outputs4 triac outputs, 10-30 VAC source or sink, 300 mA max (resettable fuse)
Analog Output1 output 0-10 VDC / 2-10 VDC / 0-5 VDC, 40 mA max (resettable fuse), for the valve
Indication Lights (LED)State of each output / Communication / Supply / State of microprocessor
MicroprocessorPIC18F6722, 8 bits, 40 MHz, 128 KB FLASH memory
CasingMolded ABS, UL94-HB
CommunicationModbus RTU (RS485), up to 127 nodes
Baud Rates9600, 19200, 38400, 57600, 76800, 115200
ConnectionRemovable screw-type terminal blocks (16 AWG max)
Dimensions6.2 in x 5.2 in x 2.5 in (157 mm x 132 mm x 64 mm)
Weight0.85 lbs (0.39 kg)
Environment-4 to 122 °F (-20 to 50 °C), non-condensing
CertificationUL916 Energy Management Equipment, CAN/CSA-C22.2, RoHS, FCC part 15: 2012 class B

Documentation

Frequently Asked Questions

How many boilers can the PL-C1050-BLR control?
Up to 2 boiler stages, which can be multiple boilers or a single multistage boiler. It can alternatively control 1 modulating boiler with an optional backup stage.
Does it do outdoor reset?
Yes. The supply water setpoint resets based on outside temperature, and can additionally be offset by a network-received demand or occupancy state.
What controls the pumps?
Pump activity can be based on outside temperature, a call for heat, or both. A configurable pump exercise sequence runs the pumps during extended periods of inactivity.
Can it drive a three-way valve?
Yes. An optional three-way valve sequence is available, and the analog output is specified for the valve.
Is it a BACnet controller?
No. The C1050-BLR communicates using Modbus RTU over RS485, up to 127 nodes.
Controller Type:
Boiler
Digital Outputs:
4
Analog Outputs:
1
Analog Inputs:
3
Digital Inputs:
1
Communication:
Modbus RTU (RS485)