null Skip to main content

Prolon PL-PN1-4G : Pre-Wired One Controller Panel with C1050 Zoning Heat Pump Controller, Isolation Relays, NEMA 1 Enclosure, UL508A Certified

Prolon

Your Price:  $1,760.68
(No reviews yet) Write a Review
SKU:
PL-PN1-4G
Condition:
New
Availability:
Ships in 2-4 Days
Adding to cart… The item has been added

Controller

C1050

Program

Zoning Heatpump

Supply

24 VAC, Class 2

Outputs

4 DO / 1 AO

Protocol

Modbus RTU / BACnet MS/TP

Panel

NEMA 1, UL508A

Overview

The Prolon PL-PN1-4G is a pre-wired, UL508A certified NEMA 1 control panel built with one Prolon C1050 controller running the Zoning Heatpump Controller program, which operates residential or commercial heatpump equipment using PI control loops, and acts as a master when networked with Prolon zone controllers. Isolation relays on all digital outputs, overcurrent fuse protection and clearly marked terminal blocks come factory wired.

Program strategies include unoccupied mode settings, morning warm-up and supply air pre-heating. The panel contains 1 Modbus RTU (RS485) node and runs stand-alone or on a Prolon network of up to 127 nodes.

Specifications per Prolon Pre-Wired One Controller Panel datasheet PL-DATA-PANEL1CON-EN-V1; Prolon PL-C1050-HP Controller datasheet REV 7.3.0 / PL-DATA-C1050HP-C/F-EN; Prolon C1050 Heatpump Controller Hardware Guide (HP and HPS) REV 7.3.2; Prolon One Controller Panel product page (proloncontrols.com) retrieved 2026-09-22. Reviewed September 2026.

Best For

  • Zoned heat pump systems with Prolon zone controllers
  • Commercial or residential heat pump units
  • Heat pumps needing morning warm-up and supply air pre-heating

Warranty

For warranty coverage on this Prolon panel, contact ZOT Supply at sales@zotsupply.com or 855-825-2811.

Key Features

Zoning master

Acts as the master when used on a network with Prolon zone controllers, analyzing zone demand to drive the heat pump.

17A isolation relays

Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel (C1050 = 4), and the controller outputs are protected by resettable fuses.

Fused, pre-wired NEMA 1 panel

Clearly marked terminal blocks, wire management channels and a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included. The panel wiring diagram is in the door, and all inputs and outputs are tested in the factory.

Reflash to another program

The C1050 keeps its full functionality, including the ability to reflash into a different controller program. Wiring diagrams are available free at proloncontrols.com.

Outputs wired in SOURCE mode

All 4 triac outputs are set to SOURCE mode because they share a single source supply, the equipment transformer.

Free Prolon Focus software

Remote monitoring and configuration with free Prolon Focus software, stand-alone or networked up to 127 nodes.

Authorized Distributor

ZOT Supply is an authorized distributor of Prolon products.

Technical Specifications

Panel
ControllerProlon C1050, Zoning Heatpump Controller program
Supply24 VAC ±10%, 50/60 Hz, Class 2
Overcurrent ProtectionDisconnect-style Slo-Blo fuse (3A @ 250 VAC), with additional replacement fuse included
EnclosureNEMA 1
Panel Dimensions12.25 in. W x 16.25 in. H x 6.25 in. D
Weight23 lbs (10.5 kg)
Isolation Relays17A @ 277 VAC on all digital outputs (C1050 = 4, M2000 = 5)
Environment-4 to 122 °F (-20 to 50 °C), non-condensing
Panel CertificationComplete panel is UL508A certified
CertificationUL916 Energy Management Equipment, CAN/CSA-C22.2, RoHS, FCC part 15: 2012 class B
C1050 Controller Hardware
Power2 VA (consumption), 32 VA (input)
Inputs4 configurable inputs with selectable functions (outside temp / return temp / supply temp / water intake temp / night setback / proof of fan / alarm)
Digital Outputs4 triac outputs, 10-30 VAC source, 300 mA max (resettable fuse)
Analog Outputs1 output 0-10 VDC / 2-10 VDC / 0-5 VDC, 40 mA max (resettable fuse)
Indication Lights (LED)State of each output / Communication / Power / State of microprocessor
CasingMolded ABS, UL94-HB
CommunicationModbus RTU (RS485) or BACnet MS/TP (RS485) up to 127 nodes
Baud Rates9600, 19200, 38400, 57600, 76800, 115200
ConnectionRemovable screw-type terminal blocks (16 AWG max)
Zoning Heatpump Controller Program
ProgramZoning Heatpump Controller
ApplicationOperates residential or commercial heatpump equipment using PI control loops, and acts as a master when networked with Prolon zone controllers
Program Outputs4 triac outputs, all set to SOURCE mode because they share a single source supply (the equipment transformer), 300 mA max (resettable fuse); analog output: 1 output 0-10 VDC / 2-10 VDC / 0-5 VDC

Documentation

Frequently Asked Questions

What is the Prolon PL-PN1-4G?

A pre-wired one controller panel built with a Prolon C1050 controller running the Zoning Heatpump Controller program, in a UL508A certified NEMA 1 enclosure with isolation relays on all digital outputs.

What does the zoning heatpump program control?

It operates residential or commercial heatpump equipment using PI control loops, and acts as a master when networked with Prolon zone controllers. Strategies include unoccupied mode settings, morning warm-up and supply air pre-heating.

Which inputs does the PL-PN1-4G use?

4 configurable inputs with selectable functions (outside temp / return temp / supply temp / water intake temp / night setback / proof of fan / alarm).

What power does the panel require?

24 VAC ±10%, 50/60 Hz, Class 2. The C1050 draws 2 VA (consumption), 32 VA (input).

Are the outputs isolated and protected?

Yes. Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel, the triac outputs are rated 300 mA max with resettable fuses, and the panel has a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included.

What size is the PL-PN1-4G panel?

12.25 in. W x 16.25 in. H x 6.25 in. D, and it weighs 23 lbs (10.5 kg).

How are the digital outputs wired on the heat pump program?

All triac outputs are set to SOURCE mode because they share a single source supply, the equipment transformer.

Does the PL-PN1-4G support BACnet?

Yes. The C1050 heat pump program communicates over Modbus RTU (RS485) or BACnet MS/TP (RS485), up to 127 nodes, and is configured with free Prolon Focus software.

Panel Type:
Single Controler Panel
Display:
No Display
Controller Type:
Heat Pump
Communication:
Modbus RTU (RS485)
Communication:
BACnet MS/TP (RS485)