Prolon PL-PN1-4H : Pre-Wired One Controller Panel with C1050 Single-Zone Heat Pump Controller, Isolation Relays, NEMA 1 Enclosure, UL508A Certified

Prolon

Your Price:  $1,760.68
(No reviews yet) Write a Review
SKU:
PL-PN1-4H
Condition:
New
Availability:
Ships in 2-4 Days
Adding to cart… The item has been added

Controller

C1050

Program

Single-Zone Heatpump

Supply

24 VAC, Class 2

Outputs

4 DO / 1 AO

Protocol

Modbus RTU (RS485)

Panel

NEMA 1, UL508A

Overview

The Prolon PL-PN1-4H is a pre-wired, UL508A certified NEMA 1 control panel built with one Prolon C1050 controller running the Single-Zone Heatpump Controller program, which operates residential or commercial heatpump equipment using PI control loops as a standalone controller that relies on the demand from a local sensor rather than acting as a master to zone controllers. Isolation relays on all digital outputs, overcurrent fuse protection and clearly marked terminal blocks come factory wired.

Program strategies include unoccupied mode settings, morning warm-up and supply air pre-heating. The panel contains 1 Modbus RTU (RS485) node and runs stand-alone or on a Prolon network of up to 127 nodes.

Specifications per Prolon Pre-Wired One Controller Panel datasheet PL-DATA-PANEL1CON-EN-V1; Prolon PL-C1050-HPS Controller datasheet REV 7.3.0 / PL-DATA-C1050HPS-C/F-EN; Prolon C1050 Heatpump Controller Hardware Guide (HP and HPS) REV 7.3.2; Prolon One Controller Panel product page (proloncontrols.com) retrieved 2026-09-22. Reviewed September 2026.

Best For

  • Single-zone heat pumps controlled from one room sensor
  • Standalone heat pump units without zone dampers
  • Heat pumps controlled from a Prolon digital room sensor

Warranty

For warranty coverage on this Prolon panel, contact ZOT Supply at sales@zotsupply.com or 855-825-2811.

Key Features

Local digital sensor

The INT port connects a Prolon digital temperature sensor, and the controller supplies 24 VAC to power it.

17A isolation relays

Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel (C1050 = 4), and the controller outputs are protected by resettable fuses.

Fused, pre-wired NEMA 1 panel

Clearly marked terminal blocks, wire management channels and a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included. The panel wiring diagram is in the door, and all inputs and outputs are tested in the factory.

Reflash to another program

The C1050 keeps its full functionality, including the ability to reflash into a different controller program. Wiring diagrams are available free at proloncontrols.com.

Outputs wired in SOURCE mode

All 4 triac outputs are set to SOURCE mode because they share a single source supply, the equipment transformer.

Free Prolon Focus software

Remote monitoring and configuration with free Prolon Focus software, stand-alone or networked up to 127 nodes.

Authorized Distributor

ZOT Supply is an authorized distributor of Prolon products.

Technical Specifications

Panel
ControllerProlon C1050, Single-Zone Heatpump Controller program
Supply24 VAC ±10%, 50/60 Hz, Class 2
Overcurrent ProtectionDisconnect-style Slo-Blo fuse (3A @ 250 VAC), with additional replacement fuse included
EnclosureNEMA 1
Panel Dimensions12.25 in. W x 16.25 in. H x 6.25 in. D
Weight23 lbs (10.5 kg)
Isolation Relays17A @ 277 VAC on all digital outputs (C1050 = 4, M2000 = 5)
Environment-4 to 122 °F (-20 to 50 °C), non-condensing
Panel CertificationComplete panel is UL508A certified
CertificationUL916 Energy Management Equipment, CAN/CSA-C22.2, RoHS, FCC part 15: 2012 class B
C1050 Controller Hardware
Power2 VA (consumption), 32 VA (input)
Inputs4 configurable inputs with selectable functions (outside temp / return temp / supply temp / water intake temp / night setback / proof of fan / alarm)
Digital Outputs4 triac outputs, 10-30 VAC source, 300 mA max (resettable fuse)
Analog Outputs1 output 0-10 VDC / 2-10 VDC / 0-5 VDC, 40 mA max (resettable fuse)
Indication Lights (LED)State of each output / Communication / Power / State of microprocessor
CasingMolded ABS, UL94-HB
CommunicationModbus RTU (RS485) up to 127 nodes
Baud Rates9600, 19200, 38400, 57600, 76800, 115200
ConnectionRemovable screw-type terminal blocks (16 AWG max)
Single-Zone Heatpump Controller Program
ProgramSingle-Zone Heatpump Controller
ApplicationOperates residential or commercial heatpump equipment using PI control loops as a standalone controller that relies on the demand from a local sensor rather than acting as a master to zone controllers
Program Inputs4 configurable inputs with selectable functions (outside temp / return temp / supply temp / water intake temp / night setback / proof of fan / alarm); INT port connects a Prolon digital temperature sensor, powered at 24 VAC
Program Outputs4 triac outputs, all set to SOURCE mode because they share a single source supply (the equipment transformer), 300 mA max (resettable fuse); analog output: 1 output 0-10 VDC / 2-10 VDC / 0-5 VDC

Documentation

Frequently Asked Questions

What is the Prolon PL-PN1-4H?

A pre-wired one controller panel built with a Prolon C1050 controller running the Single-Zone Heatpump Controller program, in a UL508A certified NEMA 1 enclosure with isolation relays on all digital outputs.

What does the single-zone heatpump program control?

It operates residential or commercial heatpump equipment using PI control loops as a standalone controller that relies on the demand from a local sensor rather than acting as a master to zone controllers. Strategies include unoccupied mode settings, morning warm-up and supply air pre-heating.

Which inputs does the PL-PN1-4H use?

4 configurable inputs with selectable functions (outside temp / return temp / supply temp / water intake temp / night setback / proof of fan / alarm); INT port connects a Prolon digital temperature sensor, powered at 24 VAC.

What power does the panel require?

24 VAC ±10%, 50/60 Hz, Class 2. The C1050 draws 2 VA (consumption), 32 VA (input).

Are the outputs isolated and protected?

Yes. Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel, the triac outputs are rated 300 mA max with resettable fuses, and the panel has a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included.

How does the PL-PN1-4H communicate?

Modbus RTU (RS485), up to 127 nodes, at 9600 to 115200 baud. The panel contains 1 node and is configured with free Prolon Focus software.

What size is the PL-PN1-4H panel?

12.25 in. W x 16.25 in. H x 6.25 in. D, and it weighs 23 lbs (10.5 kg).

How are the digital outputs wired on the heat pump program?

All triac outputs are set to SOURCE mode because they share a single source supply, the equipment transformer.

Panel Type:
Single Controler Panel
Display:
No Display
Controller Type:
Heat Pump
Communication: