null Skip to main content

Prolon PL-PN1-7C : Pre-Wired One Controller Panel with M2000 Boiler Controller, Isolation Relays, NEMA 1 Enclosure, UL508A Certified

Prolon

Your Price:  $2,443.49
(No reviews yet) Write a Review
SKU:
PL-PN1-7C
Condition:
New
Availability:
Ships in 2-4 Days
Adding to cart… The item has been added

Controller

M2000

Program

Boiler

Supply

24 VAC, Class 2

Outputs

5 DO / 3 AO

Protocol

Modbus RTU (RS485)

Panel

NEMA 1, UL508A

Overview

The Prolon PL-PN1-7C is a pre-wired, UL508A certified NEMA 1 control panel built with one Prolon M2000 controller running the Boiler Controller program, which runs staged or modulating boiler sequences with their pumps. Isolation relays on all digital outputs, overcurrent fuse protection and clearly marked terminal blocks come factory wired.

Program strategies include staged boiler configuration and modulating boiler configuration. The panel contains 1 Modbus RTU (RS485) node and runs stand-alone or on a Prolon network of up to 127 nodes.

Specifications per Prolon Pre-Wired One Controller Panel datasheet PL-DATA-PANEL1CON-EN-V1; Prolon PL-M2000-BLR Controller datasheet REV 7.3.0 / PL-DATA-M2000BLR-C/F-EN; Prolon M2000 Series Quick Start Guide REV 7.0 / PL-QCK-M2000-EN; Prolon One Controller Panel product page (proloncontrols.com) retrieved 2026-09-22. Reviewed September 2026.

Best For

  • Staged boiler plants up to 4 stages
  • Modulating boilers driven by 0-10 / 2-10 / 0-5 VDC signals
  • Boiler rooms that need an onboard schedule without a network

Warranty

For warranty coverage on this Prolon panel, contact ZOT Supply at sales@zotsupply.com or 855-825-2811.

Key Features

Staged or modulating boilers

Wiring configurations cover staged boilers (4 boiler stage outputs plus pumps) and modulating boilers driven from the analog outputs.

17A isolation relays

Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel (M2000 = 5), and the controller outputs are protected by resettable fuses.

Fused, pre-wired NEMA 1 panel

Clearly marked terminal blocks, wire management channels and a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included. The panel wiring diagram is in the door, and all inputs and outputs are tested in the factory.

Reflash to another program

The M2000 keeps its full functionality, including the ability to reflash into a different controller program. Wiring diagrams are available free at proloncontrols.com.

Manual/off/auto switches

A manual/off/auto switch for each of the eight outputs of the M2000 controller.

Free Prolon Focus software

Remote monitoring and configuration with free Prolon Focus software, stand-alone or networked up to 127 nodes.

Authorized Distributor

ZOT Supply is an authorized distributor of Prolon products.

Technical Specifications

Panel
ControllerProlon M2000, Boiler Controller program
Supply24 VAC ±10%, 50/60 Hz, Class 2
Overcurrent ProtectionDisconnect-style Slo-Blo fuse (3A @ 250 VAC), with additional replacement fuse included
EnclosureNEMA 1
Panel Dimensions12.25 in. W x 16.25 in. H x 6.25 in. D
Weight23 lbs (10.5 kg)
Isolation Relays17A @ 277 VAC on all digital outputs (C1050 = 4, M2000 = 5)
Environment-4 to 122 °F (-20 to 50 °C), non-condensing
Panel CertificationComplete panel is UL508A certified
CertificationUL916 Energy Management Equipment, CAN/CSA-C22.2, RoHS, FCC part 15: 2012 class B
M2000 Controller Hardware
Power5 VA (consumption), 40 VA (input)
Inputs7 configurable analog inputs (outside temp / supply temp / return temp / dry contacts for proof of pumps, max heat request and boiler disable). Input signals (thermistor / dry contact / 4-20mA / 0-5 VDC) individually configurable for each input
Digital Outputs5 triac outputs, 10-30 VAC source, 300 mA max (resettable fuse)
Analog Outputs3 x 0-10 VDC outputs, 40 mA max (resettable fuse)
Indication Lights (LED)State of each output / Communication / Power / State of microprocessor
CasingMolded ABS, UL94-HB
CommunicationModbus RTU (RS485), up to 127 nodes
Baud Rates9600, 19200, 38400, 57600, 76800, 115200
ConnectionRemovable screw-type terminal blocks (16 AWG max) and RJ45 modular jacks
Boiler Controller Program
ProgramBoiler Controller
ApplicationRuns staged or modulating boiler sequences with their pumps
Program InputsOutside air, supply water and return water: 10K thermistor; proof of pump 1, proof of pump 2, use max heat setpoint and disable boiler call: dry contact
Program OutputsStaged: DO1-DO4 boiler stages, DO5 pump 1, AO1 pump 2, AO3 valve (0-10 / 2-10 / 0-5 VDC). Modulating: AO2 and AO3 modulating boiler stages (0-10 / 2-10 / 0-5 VDC)

Documentation

Frequently Asked Questions

What is the Prolon PL-PN1-7C?

A pre-wired one controller panel built with a Prolon M2000 controller running the Boiler Controller program, in a UL508A certified NEMA 1 enclosure with isolation relays on all digital outputs.

What does the boiler program control?

It runs staged or modulating boiler sequences with their pumps. Strategies include staged boiler configuration and modulating boiler configuration.

Which inputs does the PL-PN1-7C use?

Outside air, supply water and return water: 10K thermistor; proof of pump 1, proof of pump 2, use max heat setpoint and disable boiler call: dry contact.

What power does the panel require?

24 VAC ±10%, 50/60 Hz, Class 2. The M2000 draws 5 VA (consumption), 40 VA (input).

Are the outputs isolated and protected?

Yes. Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel, the triac outputs are rated 300 mA max with resettable fuses, and the panel has a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included.

How does the PL-PN1-7C communicate?

Modbus RTU (RS485), up to 127 nodes, at 9600 to 115200 baud. The panel contains 1 node and is configured with free Prolon Focus software.

What size is the PL-PN1-7C panel?

12.25 in. W x 16.25 in. H x 6.25 in. D, and it weighs 23 lbs (10.5 kg).

Can the M2000 boiler program run a schedule on its own?

Yes. The Prolon boiler controller on the M2000 includes a real time clock, and its schedule is used when no occupancy is received from the network.

Panel Type:
Single Controler Panel
Display:
No Display
Controller Type:
Boiler
Communication: