Skip to main content

Prolon PL-PANEL-M2000-CHL : Pre-Wired Prolon M2000 Chiller Control Panel, Isolation Relays, NEMA 1 Enclosure, UL508 Certified

Prolon

$2,216.32
(No reviews yet) Write a Review
SKU:
PL-PANEL-M2000-CHL
Condition:
New
Availability:
Ships in 2-4 Days
Adding to cart… The item has been added

Prolon PL-PANEL-M2000-CHL : Pre-Wired Prolon M2000 Chiller Control Panel, Isolation Relays, NEMA 1 Enclosure, UL508 Certified

Features

  • Pre-wired industrial control panel equipped with clearly marked terminal blocks and fuses
  • Maintains all functionality and flexibility of the M2000 controller including the ability to reflash into a different controller program (wiring diagrams available free at proloncontrols.com)
  • Remote monitoring and configuration with FREE Prolon Focus software
  • Stand-alone or networked (up to 127 nodes)
  • Proportional integral (PI) control loops maximize performance
  • 5 digital outputs and 3 analog outputs equipped with resettable fuses and Hand/Off/Auto switches
  • Built-in real time clock can run standalone schedule up to 4 periods per day, 7 days per week, plus holi- day calendar. Clock stays accurate for up to 10 days without power
  • Highly customizable M2000 control sequences with protective limits, delays, and interlocks.
  • All digital outputs are isolated with relays that are built into the panel
  • Onboard LEDs allows for quick diagnostics of po- wer, communication, and operation

Technical Specifications

  • Supply: 24 VAC ±10%, 50/60 Hz, Class 2
  • Power: 5 VA (consumption), 40 VA (input)
  • Overcurrent Protection: Disconnect-Style Slo-Blo fuse (3A @ 250 VAC), with ad- ditional replacement fuse included
  • Inputs: 9 analog inputs configurable (thermistor / dry contact / 4-20mA / 0-5 VDC / 1-5 VDC) individually configurable for each input
  • Digital Outputs: 5 triac outputs, 24 VAC source, 300 mA max (resettable fuse). All digital outputs are isolated by relays in panel
  • Analog Output: 3 outputs 0-10 VDC / 2-10 VDC / 0-5 VDC / 1-5 VDC, 40 mA max (resettable fuse)
  • Indication lights (LED): State of each output / Communication / Power / State of microprocessor
  • Casing: Molded ABS, UL94-HB
  • Communication: Modbus RTU (RS485) up to 127 nodes
  • Baud Rates: 9600, 19200, 38400, 57600, 76800, 115200
  • Connection: Removable screw-type terminal blocks (max 16 AWG) and RJ45 modular jacks
  • Dimensions: 12.25” x 16.25” x 6.25” (311mm x 403mm x 159mm)
  • Weight: 18.8 lbs (8.53 kg)
  • Environment: -4 to 122 oF (-20 to 50 oC) non-Condensing
  • Certification: UL916 Energy Management Equipment, CAN/CSA-C22.2, RoHS, FCC part 15: 2012 class B

Datasheets

pdf logo Pre-Wired Prolon M2000 Controller Panel (PL-PANEL-M2000-XXX
Panel Type:
Single Controler Panel
Display:
No Display