null Skip to main content

Prolon PL-PN1-7G : Pre-Wired One Controller Panel with M2000 Zoning Heat Pump Controller, Isolation Relays, NEMA 1 Enclosure, UL508A Certified

Prolon

Your Price:  $2,443.49
(No reviews yet) Write a Review
SKU:
PL-PN1-7G
Condition:
New
Availability:
Ships in 2-4 Days
Adding to cart… The item has been added

Controller

M2000

Program

Zoning Heatpump

Supply

24 VAC, Class 2

Outputs

5 DO / 3 AO

Protocol

Modbus RTU (RS485)

Panel

NEMA 1, UL508A

Overview

The Prolon PL-PN1-7G is a pre-wired, UL508A certified NEMA 1 control panel built with one Prolon M2000 controller running the Zoning Heatpump Controller program, which operates residential or commercial heatpump equipment using PI control loops, and acts as a master when networked with Prolon zone controllers. Isolation relays on all digital outputs, overcurrent fuse protection and clearly marked terminal blocks come factory wired.

Program strategies include bypass or VFD and outside air damper control, CO2 levels and schedule, unoccupied mode, morning warm-up and supply air pre-heating. The panel contains 1 Modbus RTU (RS485) node and runs stand-alone or on a Prolon network of up to 127 nodes.

Specifications per Prolon Pre-Wired One Controller Panel datasheet PL-DATA-PANEL1CON-EN-V1; Prolon PL-M2000-HP Controller datasheet REV 7.3.1 / PL-DATA-M2000HP-C/F-EN; Prolon M2000 Heatpump Controller Hardware Guide (HP and HPS) REV 7.3.1; Prolon One Controller Panel product page (proloncontrols.com) retrieved 2026-09-22. Reviewed September 2026.

Best For

  • Zoned heat pump systems with bypass or VFD control
  • Heat pumps with outside air dampers and CO2 control
  • Networks that need a scheduling master

Warranty

For warranty coverage on this Prolon panel, contact ZOT Supply at sales@zotsupply.com or 855-825-2811.

Key Features

Zoning master with schedule

Acts as the master for Prolon zone controllers and operates on a configurable schedule using an internal real-time clock.

17A isolation relays

Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel (M2000 = 5), and the controller outputs are protected by resettable fuses.

Fused, pre-wired NEMA 1 panel

Clearly marked terminal blocks, wire management channels and a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included. The panel wiring diagram is in the door, and all inputs and outputs are tested in the factory.

Reflash to another program

The M2000 keeps its full functionality, including the ability to reflash into a different controller program. Wiring diagrams are available free at proloncontrols.com.

Manual/off/auto switches

A manual/off/auto switch for each of the eight outputs of the M2000 controller.

Free Prolon Focus software

Remote monitoring and configuration with free Prolon Focus software, stand-alone or networked up to 127 nodes.

Authorized Distributor

ZOT Supply is an authorized distributor of Prolon products.

Technical Specifications

Panel
ControllerProlon M2000, Zoning Heatpump Controller program
Supply24 VAC ±10%, 50/60 Hz, Class 2
Overcurrent ProtectionDisconnect-style Slo-Blo fuse (3A @ 250 VAC), with additional replacement fuse included
EnclosureNEMA 1
Panel Dimensions12.25 in. W x 16.25 in. H x 6.25 in. D
Weight23 lbs (10.5 kg)
Isolation Relays17A @ 277 VAC on all digital outputs (C1050 = 4, M2000 = 5)
Environment-4 to 122 °F (-20 to 50 °C), non-condensing
Panel CertificationComplete panel is UL508A certified
CertificationUL916 Energy Management Equipment, CAN/CSA-C22.2, RoHS, FCC part 15: 2012 class B
M2000 Controller Hardware
Power5 VA (consumption), 40 VA (input)
Inputs9 configurable analog inputs (outside temperature / return / supply / zone / water supply / dry contact for clogged filter / schedule override / proof of fan / alarm, room setpoint, static pressure). Input signals (thermistor / dry contact / 4-20mA / 0-5 VDC) individually configurable for each input
Digital Outputs5 triac outputs, 10-30 VAC source, 300 mA max (resettable fuse)
Analog Outputs3 x 0-10 VDC outputs, 40 mA max
Indication Lights (LED)State of each output / Communication / Power / State of microprocessor
CasingMolded ABS, UL94-HB
CommunicationModbus RTU (RS485) up to 127 nodes
Baud Rates9600, 19200, 38400, 57600, 76800, 115200
ConnectionRemovable screw-type terminal blocks (max 16 AWG) and RJ45 modular jacks
Zoning Heatpump Controller Program
ProgramZoning Heatpump Controller
ApplicationOperates residential or commercial heatpump equipment using PI control loops, and acts as a master when networked with Prolon zone controllers
Program Inputs9 configurable analog inputs: outside temperature, return, supply, zone, water supply, dry contact for clogged filter, schedule override, proof of fan, alarm, room setpoint, static pressure (thermistor / dry contact / 4-20mA / 0-5 VDC)
Program Outputs3 x 0-10 VDC analog outputs, 40 mA max

Documentation

Frequently Asked Questions

What is the Prolon PL-PN1-7G?

A pre-wired one controller panel built with a Prolon M2000 controller running the Zoning Heatpump Controller program, in a UL508A certified NEMA 1 enclosure with isolation relays on all digital outputs.

What does the zoning heatpump program control?

It operates residential or commercial heatpump equipment using PI control loops, and acts as a master when networked with Prolon zone controllers. Strategies include bypass or VFD and outside air damper control, CO2 levels and schedule, unoccupied mode, morning warm-up and supply air pre-heating.

Which inputs does the PL-PN1-7G use?

9 configurable analog inputs: outside temperature, return, supply, zone, water supply, dry contact for clogged filter, schedule override, proof of fan, alarm, room setpoint, static pressure (thermistor / dry contact / 4-20mA / 0-5 VDC).

What power does the panel require?

24 VAC ±10%, 50/60 Hz, Class 2. The M2000 draws 5 VA (consumption), 40 VA (input).

Are the outputs isolated and protected?

Yes. Every digital output is isolated by a relay rated 17A @ 277 VAC built into the panel, the triac outputs are rated 300 mA max with resettable fuses, and the panel has a disconnect-style Slo-Blo fuse (3A @ 250 VAC) with a replacement fuse included.

How does the PL-PN1-7G communicate?

Modbus RTU (RS485), up to 127 nodes, at 9600 to 115200 baud. The panel contains 1 node and is configured with free Prolon Focus software.

What size is the PL-PN1-7G panel?

12.25 in. W x 16.25 in. H x 6.25 in. D, and it weighs 23 lbs (10.5 kg).

Panel Type:
Single Controler Panel
Display:
No Display
Controller Type:
Heat Pump
Communication:
Modbus RTU (RS485)