Prolon PL-T200F-WGL Communicating Digital Wall Sensor

Sensor10KΩ Type 3 NTC, 1%
SetpointKnob, 59-86 °F Scale
OverrideMomentary Pushbutton
Link to ControllerModbus RTU, RS485
Power24 VAC, 2 VA max
FinishWhite / Grey Label

Overview

The Prolon PL-T200F-WGL is a communicating digital wall sensor with a white enclosure, grey label and a setpoint knob with a printed 59-86 °F scale. It sends ambient zone temperature, heating and cooling setpoints and schedule override requests to its Prolon controller over Modbus RTU (RS485).

A built-in 10KΩ Type 3 NTC thermistor with 1% precision measures the zone, and an embossed momentary pushbutton overrides unoccupied status. The low profile enclosure wires through a numbered screw terminal block or an RJ45 modular jack, and mounting hardware is included for drywall or a standard 2 x 4 in. electrical box.

Best For

  • Classrooms, hotels, executive areas, office spaces and other commercial areas
  • Zones served by Prolon C1050-VAV, C1050-FCU, M2000-FCU or VC2000 controllers
  • Spaces where occupants adjust setpoint with a 59-86 °F knob and override the schedule

Warranty

For warranty terms on this Prolon product, contact ZOT Supply at sales@zotsupply.com or 855-825-2811.

Key Features

Built-in Temperature Sensor

10KΩ Type 3 NTC thermistor with 1% precision reports ambient zone temperature to the connected Prolon controller.

Setpoint Knob

Rotary knob with a printed 59-86 °F scale on a standard 10KΩ setpoint potentiometer, +/- 20% tolerance across the range, sends heating and cooling setpoint adjustments to the controller.

Override Pushbutton

Embossed momentary pushbutton sends a schedule override request to override unoccupied status. Hold for 3 seconds.

Communicating, No Network Address

Talks to its associated controller over Modbus RTU (RS485) at 57600 bps instead of sending a resistive signal, without occupying a network address.

Two Wiring Options

Numbered screw terminal block (INT+, INT-, 24VAC, COM) or RJ45 modular jack.

Low Profile Enclosure

Mounting hardware included for drywall or a standard single-gang (2 x 4 in.) electrical box.

Authorized Distributor

ZOT Supply is an authorized distributor of Prolon products.

Technical Specifications

Supply24 VAC ±10%, 50/60 Hz
Power Consumption2 VA max
Temperature Sensor10KΩ Type 3 NTC thermistor, 1% precision
Setpoint AdjustmentRotary knob with printed 59-86 °F scale; standard 10KΩ setpoint potentiometer, +/- 20% tolerance across the range
Schedule OverrideEmbossed momentary pushbutton; hold 3 seconds
InterfaceRotary knob and schedule override push-button
MicroprocessorSyncMOS 8-bit, 11 MHz, 64KB Flash memory
Communication to ControllerModbus RTU (RS485), 57600 bps
Network AddressDoes not occupy a network address or count toward network device total
ConnectionScrew-type terminal blocks (16 AWG max) and RJ45 modular jack
Face Dimensions3.23 x 4.96 in. (82 x 126 mm)
Weight0.35 lb (0.16 kg)
Environment32-122 °F (0-50 °C)
MountingStandard 2 x 4 in. electrical box; mounting hardware for drywall or single-gang box included
Enclosure / LabelWhite enclosure, grey label
ComplianceFCC CFR47 Part 15, Subpart B, Class B; ICES-003 Issue 5, CAN ICES-3 (B)/NMB-3(B); RoHS Directive (2002/95/EC)

Specifications verified against Prolon Digital Sensor PL-T200 Datasheet, REV 7.1.2 (PL-DATA-T200-C/F-EN), and the current Prolon PL-T200 product page, reviewed September 25, 2026.

Documentation

Frequently Asked Questions

Which controllers does the Prolon PL-T200F-WGL work with?

It works with Prolon controllers that accept a digital wall sensor, including the C1050-VAV, C1050-FCU, M2000-FCU and VC2000, sending them room temperature, room setpoint and schedule override requests.

How is the PL-T200F-WGL wired and powered?

Land the RS485 communication on INT+ and INT- and 24 VAC power on 24VAC and COM, or use the RJ45 modular jack. Power draw is 2 VA max; C1050-VAV and VC2000 controllers provide an extra 24 VAC and COM pair to simplify powering the sensor.

Does it use a network address?

No. It communicates only with its associated controller, so it does not occupy a network address or count toward the total network device count.

How do occupants override the schedule?

Hold the embossed pushbutton for 3 seconds to send a schedule override request that overrides unoccupied status.

What setpoint range does the knob show?

The PL-T200F knob is printed 59-86 °F. Set the connected controller's scale limits to match the sensor's printed scale.

What do the letters in PL-T200F-WGL mean?

The letter after T200 sets the setpoint knob: C = Celsius (15-30 °C), F = Fahrenheit (59-86 °F), A = +/- scale, B = no setpoint knob. The PL-T200F-WGL has a white enclosure with a grey label.

Sensor Type:
Wall Mount
Temperature Element:
10K Type III
Supported Protocols:
Modbus RTU
Humidity Element:
None
CO2 Element:
None
Setpoint:
Setpoint
Override:
Override
Display:
No Display