null Skip to main content

Prolon PL-T500-BWL : Communicating Digital Wall Sensor, 10K Type 3 Thermistor, Backlit LCD, Rotary Setpoint Knob, Override Pushbutton, Black Enclosure, White Label

Prolon

Your Price:  $326.16
(No reviews yet) Write a Review
SKU:
PL-T500-BWL
Condition:
New
Availability:
Ships in 1-2 Days
Adding to cart… The item has been added

Prolon PL-T500-BWL Communicating Digital Wall Sensor

Sensor10KΩ Type 3 NTC, 1%
DisplayBacklit LCD, 80x130
SetpointRotary Encoder Knob
OverridePushbutton, Hold 3 s
Power24 VAC, 5 VA max
FinishBlack / White Label

Overview

The Prolon PL-T500-BWL is a communicating digital wall sensor with a black enclosure, white label, backlit graphical LCD and a setpoint knob mounted on a precision rotary encoder. It sends ambient zone temperature, heating and cooling setpoints and schedule override requests to its Prolon controller.

The infinitely turning knob has incremental detents that give mechanical feedback for precise setpoint adjustment. Holding the pushbutton for 3 seconds requests a schedule override, and double-clicking it changes the displayed unit between °F and °C. The sensor wires through a numbered screw terminal block (INT+, INT-, 24VAC, COM) or an RJ45 modular jack, and mounting hardware is included for drywall or a 2 x 4 in. electrical junction box.

Best For

  • Prolon-controlled HVAC zones requiring local temperature display, setpoint adjustment and schedule override
  • Zones served by Prolon C1050-VAV, C1050-FCU, M2000-FCU or VC2000 controllers

Warranty

For warranty terms on this Prolon product, contact ZOT Supply at sales@zotsupply.com or 855-825-2811.

Key Features

Built-in Temperature Sensor

10KΩ Type 3 NTC thermistor with 1% precision reports ambient zone temperature to the connected Prolon controller.

Backlit Graphical LCD

80x130 pixel oval-shaped screen with backlighting shows temperatures and setpoints.

Rotary Encoder Knob

Infinitely turning knob on a precision rotary encoder with incremental detents gives mechanical feedback for precise setpoint adjustment.

Override Pushbutton

Hold 3 seconds to send a schedule override request. Double-click to switch the displayed unit between °F and °C.

Communicating Sensor

Talks Modbus RTU over RS485 to the controller's interface (INT) port instead of sending conventional resistive signals, and does not occupy a network address.

Two Wiring Options

Numbered screw terminal block (16 AWG max) or RJ45 modular jack; mounting hardware included for drywall or a 2 x 4 in. box.

Authorized Distributor

ZOT Supply is an authorized distributor of Prolon products.

Technical Specifications

Supply24 VAC ±10%, 50/60 Hz
Power Consumption5 VA max
Temperature Sensor10KΩ Type 3 NTC thermistor, 1% precision
InputsNone
OutputsNone
ScreenLCD 80x130 pixels with backlighting
InterfaceKnob mounted on rotary encoder with detents and schedule override push-button
Schedule OverrideHold pushbutton 3 seconds
Display Unit°F or °C; double-click pushbutton to change
MicroprocessorSyncMOS 8-bit, 11 MHz, 64KB Flash memory
Communication to ControllerModbus RTU over RS485, to the controller's interface (INT) port
Network AddressDoes not occupy a network address or count toward network device total
ConnectionScrew-type terminal blocks (16 AWG max) and RJ45 modular jack
Face Dimensions3.23 x 4.96 in. (82 x 126 mm)
Weight0.5 lb (0.23 kg)
Environment32-122 °F (0-50 °C)
MountingStandard 2 x 4 in. electrical box; mounting hardware for drywall included
Enclosure / LabelBlack enclosure, white label
ComplianceFCC CFR47 Part 15, Subpart B, Class B; ICES-003 Issue 5, CAN ICES-3 (B)/NMB-3(B); RoHS Directive (2002/95/EC)

Specifications per Prolon Datasheet, Digital Sensor PL-T500, REV 7.1.1 (PL-DATA-T500-C/F-EN), and Prolon Quick Start Guide, VAV Controllers & Wall Sensors, REV 4.0, reviewed September 25, 2026.

Documentation

Frequently Asked Questions

Which controllers does the Prolon PL-T500-BWL work with?

It works with Prolon controllers that accept a digital wall sensor on their interface (INT) port, including the C1050-VAV, C1050-FCU, M2000-FCU and VC2000, sending them room temperature, setpoint and schedule override requests.

How is the PL-T500-BWL wired and powered?

Land the RS485 communication on INT+ and INT- and 24 VAC power on 24VAC and COM, or use the RJ45 modular jack. Power draw is 5 VA max; C1050-VAV and VC2000 controllers provide an extra 24 VAC and COM pair to simplify powering the sensor.

Does it use a network address?

No. It communicates only with its associated controller, so it does not occupy a network address or count toward the total network device count.

How do occupants override the schedule?

Hold the pushbutton for 3 seconds to send a schedule override request.

Can the display show Fahrenheit or Celsius?

Yes. Double-click the pushbutton to change the displayed unit between °F and °C.

How does the setpoint knob work?

The knob is mounted on a precision rotary encoder that turns infinitely, with incremental detents that give mechanical feedback as the setpoint is adjusted on the display.

What do the letters in PL-T500-BWL mean?

The suffix identifies the casing and label colors for this SKU. The PL-T500-BWL has a black enclosure with a white label.

Sensor Type:
Wall Mount
Temperature Element:
10K Type III
Supported Protocols:
Modbus RTU
Humidity Element:
None
CO2 Element:
None
Setpoint:
Setpoint
Override:
Override
Display:
LCD Display

Videos Hide Videos Show Videos