The Senva CT1D-F3D is a duct-mount CO2 (carbon dioxide) and temperature sensor with a single-channel NDIR element and a 3-wire 4-20 mA, 0-5 V or 0-10 V output for demand-controlled ventilation. It also carries a passive 10K Type III Thermistor. The LCD and push-button menu set range, calibration and relay setpoints.
ZOT Supply is an authorized distributor of Senva products.
Where this model fits
Choose the CT1D to measure CO2 in return or supply air. It mounts through a 3/4 in hole in the duct with the supplied gasket and screws, and the 6.8 in probe does not need to face the airflow.
Compare mounting alternatives: CT1O-F3D (outdoor, dual-channel as standard, a different CO2 channel type from this model). A matching temperature and display code does not make two models interchangeable: check the CO2 channel type and the mounting before substituting.
Single-channel models rely on automatic baseline correction (ABC), which tracks the lowest CO2 level the space reaches. That suits offices, classrooms and other spaces that empty out regularly. Senva does not recommend disabling ABC except in continuously occupied spaces or greenhouses.
The 10K Type III Thermistor is a passive element. The controller reads its resistance directly, so the input must be set for the matching 10K Type III curve. If the controller needs a 4-20 mA or voltage temperature signal, pick the B (transmitter) option instead.
Warranty and origin
Senva's warranty is a 7-year limited warranty on the electronics and 3 years on the NDIR CO2 module. ZOT Supply is an authorized Senva distributor. See Senva's published warranty terms for conditions and exclusions.
Senva's commerce declaration (updated 04/21/2026) lists the CT1D series as manufactured in Beaverton, Oregon, with domestic components above 65% of component cost, and declares conformance with BABAA, TAA and the ARRA Buy American provisions. It is the manufacturer's statement, not a project-specific ruling, so check it against your project's requirements.
Key facts
- Single-channel NDIR with automatic baseline correction (ABC). Accuracy ±(30 ppm + 3% of reading) from 400 to 2000 ppm.
- CO2 range: 0-2000 ppm default; 0-5000 ppm or 0-10,000 ppm selectable in the LCD menu (SCL).
- Temperature: passive 10K Type III Thermistor, 10 kΩ at 25°C (10K Type III curve).
- CO2 setpoint relay: solid-state, normally open, 1 A at 30 VAC/DC, adjustable from the LCD menu.
- Power: 24 VAC (100 mA max) or 12-30 VDC (50 mA max). The 0-10 V output needs 15-30 VDC or 24 VAC.
Specifications
| Manufacturer part number | CT1D-F3D |
|---|---|
| CO2 sensing element | Non-dispersive infrared (NDIR), single-channel; field-replaceable |
| CO2 output scaling | 0-2000 ppm default; 0-5000 ppm or 0-10,000 ppm selectable in the LCD menu (SCL). |
| CO2 accuracy | ±(30 ppm + 3% of reading), 400-2000 ppm, -10 to 50°C, 0-85% RH ±(50 ppm + 5% of reading), 2000-5000 ppm, -10 to 50°C, 0-85% RH ±(100 ppm + 10% of reading), 5000-10,000 ppm, 0 to 50°C, 0-85% RH |
| Drift with ABC disabled | 35 ppm/month; may vary with environment |
| Automatic calibration (ABC) | On by default per Senva's datasheet; can be switched on or off in the LCD menu (CAL). |
| Pressure dependency | +1% of reading per kPa deviation from 101 kPa |
| CO2 response time | 60 s to 90% of reading; output updates every 1 s |
| Analog outputs | 3-wire 4-20 mA and 0-5 V / 0-10 V. DIP switch 1 selects 0-5 V or 0-10 V. |
| Temperature | Passive 10K Type III Thermistor, 10 kΩ at 25°C (10K Type III curve). It is wired on its own terminals as a resistance signal; it is not an analog transmitter output and is not shown on the LCD. |
| CO2 setpoint relay | Solid-state, normally open, 1 A at 30 VAC/DC, set from the LCD menu. On point (SPH) default 800 ppm; off point (SPL) default 700 ppm. |
| Display | LCD with push-button menu: scaling (SCL), relay setpoints (SPH, SPL), offset adjustment (ADJ, ±250 ppm) and automatic calibration (CAL). |
| Power supply | 24 VAC, 100 mA max, or 12-30 VDC, 50 mA max. The 0-10 V output requires 15-30 VDC or 24 VAC. Senva recommends a dedicated transformer for AC supply. |
| Operating environment | -10 to 50°C (14 to 122°F), 0-95% RH non-condensing |
| Enclosure | ABS / polycarbonate, IP20 / NEMA 1 |
| Dimensions | 4.0 in H x 4.4 in W x 2.1 in D, plus 6.8 in probe |
| Warranty | Senva 7-year limited warranty on electronics; NDIR CO2 module 3 years |
Documents
Senva CT1D CO2 and Temperature Duct Sensor Datasheet (PDF)
CT1D / CT1O Installation Manual, 152-0381-0C, rev. 5/28/2024 (PDF)
Senva Thermistor and RTD Resistance-Temperature Tables (PDF)
Senva Commerce Declaration: BABAA, TAA, ARRA, updated 04/21/2026 (PDF)
Frequently asked questions
What CO2 range does the CT1D-F3D output?
It ships scaled 0-2000 ppm. The LCD menu can change the scale to 0-5000 ppm or 0-10,000 ppm.
How does the CT1D-F3D report temperature?
Through a passive 10K Type III Thermistor on its own terminals. The controller reads the resistance directly and must be set for the 10K Type III curve; Senva's resistance-temperature tables are linked under Documents.
Does the CT1D-F3D have a CO2 setpoint relay?
Yes. It has a solid-state, normally open relay rated 1 A at 30 VAC/DC. The on and off points are set in the LCD menu and default to 800 ppm and 700 ppm.
Does the CT1D-F3D need field calibration?
Senva calibrates it at the factory and does not recommend routine field calibration. Automatic baseline correction (ABC) tracks low ambient CO2 to correct long-term drift; the LCD menu also has a ±250 ppm offset adjustment.
Related CT1 models
- CT1D-F3X: same sensor without a display
- CT1D-A3D: CO2 only, no temperature element
- CT1D-B3D: Temperature Transmitter
- CT1D-C3D: 100 Ohm Platinum RTD
- CT1D-D3D: 1K Platinum RTD
- CT1D-E3D: 10K Type II Thermistor
Specifications are taken from Senva's CT1D / CT1O installation manual 152-0381-0C (rev. 5/28/2024) and the Senva CT1D datasheet. Where the two differ, the installation manual is used. The instructions shipped with the product take precedence, and specifications may change without notice.
Warranty
Senva 7-year limited warranty on electronics; 3-year warranty on the NDIR CO2 sensing module. Warranty covers defects in materials and workmanship under normal use and service. Refer to Senva’s published warranty terms for coverage, conditions and exclusions.
- Sensor Type:
- Duct Mount
- CO2 Element:
- Yes
- Temperature Element:
- 10K Type III
- Humidity Element:
- None
- VOC:
- No
- Display:
- LCD Display
- CO2 Range:
- 2000/5000/10000ppm Selectable
- Supported Protocols:
- None
- Country of Origin:
- USA
- Mounting:
- Duct
- CO2 Channel:
- Single Channel
- CO2 Setpoint Relay:
- Solid-State Relay