The Senva CT1D-K3X is a duct-mount CO2 (carbon dioxide) and temperature sensor with a single-channel NDIR element and a 3-wire 4-20 mA, 0-5 V or 0-10 V output for demand-controlled ventilation. It also carries a passive 20K Thermistor. This is the no-display version: the CO2 range, calibration settings and relay setpoints cannot be changed without the LCD menu. The 0-5 V or 0-10 V output is still selected with DIP switch 1. The LCD version is the CT1D-K3D.
ZOT Supply is an authorized distributor of Senva products.
Where this model fits
Choose the CT1D to measure CO2 in return or supply air. It mounts through a 3/4 in hole in the duct with the supplied gasket and screws, and the 6.8 in probe does not need to face the airflow.
Compare mounting alternatives: CT1R-K3X (recessed wall, single-channel); CT1O-K3X (outdoor, dual-channel as standard, a different CO2 channel type from this model). A matching temperature and display code does not make two models interchangeable: check the CO2 channel type and the mounting before substituting.
Single-channel models rely on automatic baseline correction (ABC), which tracks the lowest CO2 level the space reaches. That suits offices, classrooms and other spaces that empty out regularly. Senva does not recommend disabling ABC except in continuously occupied spaces or greenhouses.
The 20K Thermistor is a passive element. The controller reads its resistance directly, so the input must be set for the matching 20K Thermistor curve. If the controller needs a 4-20 mA or voltage temperature signal, pick the B (transmitter) option instead.
Warranty and origin
Senva's warranty is a 7-year limited warranty on the electronics and 3 years on the NDIR CO2 module. ZOT Supply is an authorized Senva distributor. See Senva's published warranty terms for conditions and exclusions.
Senva's commerce declaration (updated 04/21/2026) lists the CT1D series as manufactured in Beaverton, Oregon, with domestic components above 65% of component cost, and declares conformance with BABAA, TAA and the ARRA Buy American provisions. It is the manufacturer's statement, not a project-specific ruling, so check it against your project's requirements.
Key facts
- Single-channel NDIR with automatic baseline correction (ABC). Accuracy ±(30 ppm + 3% of reading) from 400 to 2000 ppm.
- CO2 range: 0-2000 ppm factory range. Changing the range requires the LCD version.
- Temperature: passive 20K Thermistor, 20 kΩ at 25°C (20K curve).
- Power: 24 VAC (100 mA max) or 12-30 VDC (50 mA max). The 0-10 V output needs 15-30 VDC or 24 VAC.
Specifications
| Manufacturer part number | CT1D-K3X |
|---|---|
| CO2 sensing element | Non-dispersive infrared (NDIR), single-channel; field-replaceable |
| CO2 output scaling | 0-2000 ppm factory range. Changing the range requires the LCD version. |
| CO2 accuracy at the 0-2000 ppm output | ±(30 ppm + 3% of reading), 400-2000 ppm, -10 to 50°C, 0-85% RH |
| Drift with ABC disabled | 35 ppm/month; may vary with environment |
| Automatic calibration (ABC) | On by default per Senva's datasheet; it cannot be changed without the LCD version. |
| Pressure dependency | +1% of reading per kPa deviation from 101 kPa |
| CO2 response time | 60 s to 90% of reading; output updates every 1 s |
| Analog outputs | 3-wire 4-20 mA and 0-5 V / 0-10 V. DIP switch 1 selects 0-5 V or 0-10 V. |
| Temperature | Passive 20K Thermistor, 20 kΩ at 25°C (20K curve). It is wired on its own terminals as a resistance signal; it is not an analog transmitter output. |
| CO2 setpoint relay | None on this no-display model. |
| Display | None. The CO2 range, offset adjustment and automatic calibration setting are LCD menu settings and cannot be changed on this model. DIP switch 1 still selects the 0-5 V or 0-10 V output. |
| Power supply | 24 VAC, 100 mA max, or 12-30 VDC, 50 mA max. The 0-10 V output requires 15-30 VDC or 24 VAC. Senva recommends a dedicated transformer for AC supply. |
| Operating environment | -10 to 50°C (14 to 122°F), 0-95% RH non-condensing |
| Enclosure | ABS / polycarbonate, IP20 / NEMA 1 |
| Dimensions | 4.0 in H x 4.4 in W x 2.1 in D, plus 6.8 in probe |
| Warranty | Senva 7-year limited warranty on electronics; NDIR CO2 module 3 years |
Documents
Senva CT1D CO2 and Temperature Duct Sensor Datasheet (PDF)
CT1D / CT1O Installation Manual, 152-0381-0C, rev. 5/28/2024 (PDF)
Senva Thermistor and RTD Resistance-Temperature Tables (PDF)
Senva Commerce Declaration: BABAA, TAA, ARRA, updated 04/21/2026 (PDF)
Frequently asked questions
What CO2 range does the CT1D-K3X output?
It ships scaled 0-2000 ppm, and that range cannot be changed in the field. The 0-5000 and 0-10,000 ppm ranges need the LCD version (CT1D-K3D).
How does the CT1D-K3X report temperature?
Through a passive 20K Thermistor on its own terminals. The controller reads the resistance directly and must be set for the 20K Thermistor curve; Senva's resistance-temperature tables are linked under Documents.
Can the CT1D-K3X switch a relay at a CO2 setpoint?
No. This no-display model has no CO2 setpoint relay. If relay control is required, choose the LCD version (CT1D-K3D).
Does the CT1D-K3X need field calibration?
Senva calibrates it at the factory and does not recommend routine field calibration. Automatic baseline correction (ABC) tracks low ambient CO2 to correct long-term drift.
Related CT1 models
- CT1D-K3D: same sensor with LCD
- CT1D-A3X: CO2 only, no temperature element
- CT1D-B3X: Temperature Transmitter
- CT1D-C3X: 100 Ohm Platinum RTD
- CT1D-D3X: 1K Platinum RTD
- CT1D-E3X: 10K Type II Thermistor
Specifications are taken from Senva's CT1D / CT1O installation manual 152-0381-0C (rev. 5/28/2024) and the Senva CT1D datasheet. Where the two differ, the installation manual is used. The instructions shipped with the product take precedence, and specifications may change without notice.
Warranty
Senva 7-year limited warranty on electronics; 3-year warranty on the NDIR CO2 sensing module. Warranty covers defects in materials and workmanship under normal use and service. Refer to Senva’s published warranty terms for coverage, conditions and exclusions.
- Sensor Type:
- Duct Mount
- CO2 Element:
- Yes
- Temperature Element:
- 20K
- Humidity Element:
- None
- VOC:
- No
- Display:
- No Display
- CO2 Range:
- 2000ppm Fixed
- Supported Protocols:
- None
- Country of Origin:
- USA
- Mounting:
- Duct
- CO2 Channel:
- Single Channel
- CO2 Setpoint Relay:
- None