null Skip to main content

Senva CT1R-C3D-D Recessed Dual-Channel CO2/Temperature Sensor, 100 Ohm Platinum RTD, LCD & Setpoint Relay, 4-20 mA/0-5/0-10 V

Senva

MSRP: $575.50
Your Price:  $268.83
(You save $306.67 )
(No reviews yet) Write a Review
SKU:
CT1R-C3D-D
Condition:
New
Availability:
Ships in 1-2 Days
Adding to cart… The item has been added
CO2 SensingNDIR, Dual Channel
CO2 Range2000 / 5000 / 10,000 ppm
Temperature100 Ω Pt RTD
DisplayLCD + Setpoint Relay
Outputs4-20 mA / 0-5 V / 0-10 V
MountingRecessed Wall

The Senva CT1R-C3D-D is a recessed room CO2 (carbon dioxide) and temperature sensor with a dual-channel NDIR element and a 3-wire 4-20 mA, 0-5 V or 0-10 V output for demand-controlled ventilation. It also carries a passive 100 Ohm Platinum RTD. The LCD and push-button menu set range, calibration and the built-in setpoint relay.

Authorized Distributor

ZOT Supply is an authorized distributor of Senva products.

Where this model fits

Choose the CT1R when the sensor should sit nearly flush with the wall. It mounts in a standard junction box or straight into drywall using its built-in clamps. Mount it vertically at light-switch height on an interior wall, away from supply air, doors, windows and heat sources.

Compare mounting alternatives: CT1D-C3D (duct, single-channel, a different CO2 channel type from this model); CT1O-C3D (outdoor, dual-channel as standard). A matching temperature and display code does not make two models interchangeable: check the CO2 channel type and the mounting before substituting.

Dual-channel sensing uses a reference channel instead of depending on an unoccupied period. Senva recommends it for continuously occupied spaces such as hospitals, transit stations, 24-hour stores and greenhouses. For spaces that empty out daily, the single-channel CT1R-C3D is the standard choice.

The 100 Ohm Platinum RTD is a passive element. The controller reads its resistance directly, so the input must be set for the matching 100 Ω Pt RTD curve. If the controller needs a 4-20 mA or voltage temperature signal, pick the B (transmitter) option instead.

Warranty and origin

Senva covers the CT1 series with a 7-year limited warranty. ZOT Supply is an authorized Senva distributor. See Senva's published warranty terms for conditions and exclusions.

Senva's commerce declaration (updated 04/21/2026) lists the CT1R series as manufactured in Beaverton, Oregon, with domestic components above 65% of component cost, and declares conformance with BABAA, TAA and the ARRA Buy American provisions. It is the manufacturer's statement, not a project-specific ruling, so check it against your project's requirements.

Key facts

  • Dual-channel NDIR: a reference channel corrects drift without depending on an unoccupied period. Accuracy ±(30 ppm + 3% of reading) from 400 to 2000 ppm.
  • CO2 range: 0-2000 ppm default; 0-5000 ppm or 0-10,000 ppm selectable in the LCD menu (SCL).
  • Temperature: passive 100 Ohm Platinum RTD, 100 Ω at 0°C (platinum, alpha 385).
  • CO2 setpoint relay: solid-state, normally open, 1 A at 30 VAC/DC, adjustable from the LCD menu.
  • Power: 24 VAC (100 mA max) or 12-30 VDC (50 mA max). The 0-10 V output needs 15-30 VDC or 24 VAC.

Specifications

Manufacturer part numberCT1R-C3D-D
CO2 sensing elementNon-dispersive infrared (NDIR), dual-channel
CO2 output scaling0-2000 ppm default; 0-5000 ppm or 0-10,000 ppm selectable in the LCD menu (SCL).
CO2 accuracy±(30 ppm + 3% of reading), 400-2000 ppm, 0 to 50°C
±(50 ppm + 3% of reading), 2000-5000 ppm, -10 to 50°C
±(100 ppm + 10% of reading), 5000-10,000 ppm, 0 to 50°C
Drift with ABC disabled5 ppm/month (dual channel); may vary with environment
Automatic calibration (ABC)Senva's CT1R manual states that dual-channel (-D) units ship with automatic calibration off; it can be switched in the LCD menu (CAL).
CO2 response time60 s to 90% of reading; output updates every 1 s
Analog outputs3-wire 4-20 mA and 0-5 V / 0-10 V. DIP switch 1 selects 0-5 V or 0-10 V.
TemperaturePassive 100 Ohm Platinum RTD, 100 Ω at 0°C (platinum, alpha 385). It is wired on its own terminals as a resistance signal; it is not an analog transmitter output.
CO2 setpoint relaySolid-state, normally open, 1 A at 30 VAC/DC. On point (SPH) 500 ppm to full scale, 800 ppm default; off point (SPL) 400 ppm to full scale, 700 ppm default.
DisplayLCD with push-button menu: scaling (SCL), relay setpoints (SPH, SPL), offset adjustment (ADJ, ±250 ppm) and automatic calibration (CAL).
Power supply24 VAC, 100 mA max, or 12-30 VDC, 50 mA max. The 0-10 V output requires 15-30 VDC or 24 VAC. Senva recommends a dedicated transformer for AC supply.
Operating environment-10 to 50°C (14 to 122°F), 0-95% RH non-condensing
EnclosureABS plastic, IP20 / NEMA 1
Dimensions5.66 in H x 3.00 in W x 0.36 in D from the wall (1.69 in D including the recessed portion)
WarrantySenva 7-year limited warranty

Documents

Frequently asked questions

What CO2 range does the CT1R-C3D-D output?

It ships scaled 0-2000 ppm. The LCD menu can change the scale to 0-5000 ppm or 0-10,000 ppm.

How does the CT1R-C3D-D report temperature?

Through a passive 100 Ohm Platinum RTD on its own terminals. The controller reads the resistance directly and must be set for the 100 Ω Pt RTD curve; Senva's resistance-temperature tables are linked under Documents.

Does the CT1R-C3D-D have a CO2 setpoint relay?

Yes. It has a solid-state, normally open relay rated 1 A at 30 VAC/DC. The on and off points are set in the LCD menu and default to 800 ppm and 700 ppm.

When should I choose a dual-channel CO2 sensor?

When the space is occupied around the clock or CO2 stays elevated, so a single-channel sensor never sees a clean baseline. Senva names hospitals, transit stations, 24-hour stores and greenhouses. Drift with ABC disabled is rated 5 ppm/month, compared with 35 ppm/month for the single-channel element.

Related CT1 models

Specifications are taken from Senva's CT1R installation manual 152-0132-0G (rev. 05/24/2024) and the Senva CT1R / CT1W datasheet. Where the two differ, the installation manual is used. The instructions shipped with the product take precedence, and specifications may change without notice.

Warranty

Senva 7-year limited warranty. Refer to Senva’s published warranty terms for coverage, conditions and exclusions.

Sensor Type:
Wall Mount
Temperature Element:
100 Ohm Platinum RTD
Supported Protocols:
None
Humidity Element:
None
CO2 Element:
Yes
Setpoint:
Setpoint
Display:
LCD Display
Material:
Plastic
Mounting:
Recessed
CO2 Channel:
Dual Channel
CO2 Range:
2000/5000/10000ppm Selectable
CO2 Setpoint Relay:
Solid-State Relay
Country of Origin:
USA