Senva EM-RS485-RPM : Compact BACnet & Modbus Energy Meters, Reduced Point Map, 2-wire, BACnet MS/TP, Modbus RTU Outputs, Buy American Act Compliant, 7 Year Limited Warranty
The EM Series is the safest and fastest meter to install on the market. The unique design makes the meter entirely low-voltage. Ideal for retrofits as the high- voltage components are embedded in the Current/Voltage Transducer (CVT). Experience high-accuracy data-rich power metering in a compact, easy-to-use package. Meter recognizes CVTs automatically, eliminating time-consuming scaling. Each CVT uses digital communication with the meter for superior noise immunity The CVT are individually calibrated and can be mixed or matched as independent meter channels--1% total accuracy! Features both Modbus and self-configuring plug-and-play BACnet MS/TP for seamless integration.
Applications
- Energy Management & performance contracting
- Monitoring for commercial tenants
- Activity-based costing in commercial & industrial facilities
- Real-time power monitoring & load shedding
- Audits/temporary monitoring
- Distributed generation
Features
- Split-core Rogowski CVTTM senses both voltage and current, communicating with the meter through a low voltage data cable
- Easy to install Rogowski CVTTM is lightweight and compact
- True 3 channel meter--mix and match different voltages and currents per phase on HVAC equipment
- EM-RS485 self-configures baud rate, serial formal, protocol type and address - eliminating additional configuration steps
- No scaling required--easy set up
- Meter base is entirely low voltage--locate external to panel if desired
- 2 pulse inputs can connect to a variety of pulse output meters (water, gas, steam, etc.)
- Versatile DIN, screw, and magnetic mount
Specifications
Power Supply Input | 12-30VDC/24VAC(1), 100mA max. |
Output | |
RS-485 | 2-wire, BACnet MS/TP, Modbus RTU |
Baud Rates | 9600, 19200, 38400, 57600, 76800, 115200 |
RS-485 Loading | 1/4 unit |
Conductor gauge | 14-26 AWG |
Terminal torque rating | 0.5 min, 0.6 max |
Pulse Inputs | |
Dual Inputs | 3.5 +/- 0.5 VDC, short circuit current is 10mA max |
Pulse Rate | 50 Hz (default), configurable up to 500 Hz |
Pulse active | <100 ohms |
Pulse Undefined | 100-1000 ohms |
Pulse Idle | >1000 ohms |
Service Types | |
Configurations | 1Ph, 2Ph, 3Ph Wye (4-Wire), 3Ph Delta (3-Wire) |
Voltages | 90VL-N through 600VL-L |
Frequency | 45-65 Hz |
Datasheets
Senva EM-RS485 Multi-channel Energy Meters Data Sheet | |
Senva EM-RS485 Multi-channel Energy Meters Installation Sheet | |
Senva EM-RS485 BACnet Protocol Guide | |
Senva Made in American Certificate |
- Supported Protocols:
- Modbus RTU, BACnet MS/TP, Modbus TCP or BACnet IP
- Meter Type:
- Single Circuit
- Mounting:
- Din Mount
- Current Channels:
- 3