Adding to cart… The item has been added
AccuracyRevenue Grade · ANSI C12.20 Class 0.2
ProtocolsBACnet MS/TP · Modbus RTU/ASCII
Load Range0.25–6000A · 90–600V
PowerSelf-Powered · 1–3 Phase
SetupSenvaSync NFC App
ListingUL/cUL E489498 · Made in USA

The Senva EMX-L is a simplified, revenue-grade True RMS electrical energy meter (ANSI C12.20 Class 0.2, 0.2% meter accuracy) with BACnet MS/TP, Modbus RTU, and Modbus ASCII over 2-wire RS-485, 2 pulse inputs, and 2 pulse outputs. It shares the EMX terminal layout but omits the display, data logging, and RTC for a lower-cost installation. It is self-powered from 1 to 3 phase service (90–600V), monitors loads from 0.25 to 6000A using any 0.333V CT or metering Rogowski coil, mounts on PR30 DIN rail, and is made in the USA by Senva, Inc. (Buy American Act, BABAA, ARRA, and TAA conformant).

Senva EMX-L Lite True RMS Energy Meter

The Senva EMX-L delivers the EMX revenue-grade metering engine in a streamlined package for projects where the BAS does the trending and a local display is unnecessary. It keeps the same terminals, the same BACnet MS/TP, Modbus RTU, and Modbus ASCII protocols over 2-wire RS-485, and the same dual pulse outputs as the flagship EMX — removing only the display, data logging, and real-time clock.

Configuration is handled entirely through the SenvaSync app over NFC, even while the meter is powered off. The EMX-L is line-powered from the monitored service (1 to 3 phase, 90–600V), accepts any 0.333V CT or standard metering Rogowski coil without external integrators, and maintains 0.2% ANSI C12.20 Class 0.2 True RMS accuracy on distorted, harmonic-rich loads.

Best For

  • Energy management and performance contracting
  • Tenant submetering and activity-based costing in commercial and industrial facilities
  • Real-time power monitoring and load shedding
  • Energy audits and temporary monitoring
  • Distributed generation and data center energy sensing
Warranty: Backed by Senva’s 7-year limited warranty.

Key Features

Revenue-Grade Accuracy

0.2% meter accuracy to ANSI C12.20 Class 0.2 standards with 1% system accuracy for V, A, kW, kVAR, and kVA — suitable for tenant billing and cost allocation.

Simplified, Cost-Effective

Same metering engine and terminals as the EMX, minus the display, logging, and RTC — the right fit when the BAS handles trending and history.

SenvaSync NFC Setup

No display needed: configure everything from the SenvaSync app on iOS or Android over NFC — even while the meter is powered off.

BACnet & Modbus on RS-485

BACnet MS/TP, Modbus RTU, and Modbus ASCII over 2-wire RS-485 at baud rates from 9600 to 115200 — drops onto virtually any BAS trunk.

Universal CT Input

Accepts any 0.333V split-core CT or standard metering Rogowski coil with no bulky external integrators — ideal for retrofits with existing CTs.

Self-Powered + Pulse I/O

Line-powered from 1 to 3 phase service, 90VLN–600VLL, with 2 pulse inputs and 2 pulse outputs (import & export energy).

Technical Specifications

Specifications verified against the Senva EMX datasheet, revision V2 (October 15, 2024), and the 2026 Senva Commerce Declaration.

Power Supply Input
Line / High Voltage90VLN–600VLL (+20%), 50/60 Hz, 1–3 phase, self-powered
Power Consumption4W typical
Communications – RS-485
ProtocolsModbus RTU, Modbus ASCII, BACnet MS/TP
Baud Rates9600, 19200, 38400, 57600, 76800, 115200
RS-485 Loading1/4 unit load
Pulse Outputs (2)
Dual OutputsImport & export energy outputs
TypeSolid state dry contact, N.O. and N.C., 300mA max, 40Vac/dc
Pulse Scaling0.01, 0.1, 1, 10, 100, 1k Wh/pulse
Pulse Duration10, 25, 50, 100, 250, 500 ms
Pulse Inputs (2)
Input Rating3.5 ± 0.5 VDC, short circuit current 10mA max
Pulse LengthAccepts pulses >10ms, rejects pulses <5ms
Service Types
Configurations1Ph, 2Ph, 3Ph Wye (4-wire), 3Ph Delta (3-wire)
Voltages90VL-N through 600VL-L
Frequency45–65 Hz
Measurement CategoryCAT III
Performance
Meter Accuracy0.2% (ANSI C12.20 Class 0.2 standards)
System Accuracy1% for V, A, kW, kVAR, kVA
CT CompatibilityAny 0.333V CT or standard metering Rogowski coil (no integrator required)
Operating Environment
Operating Temperature-22 to 158°F (-30 to 70°C)
Storage Temperature-40 to 158°F (-40 to 70°C)
Humidity0–95% non-condensing
Environmental RatingIP20
Enclosure
MaterialPolycarbonate/ABS
Dimensions3.55”H x 4.18”W x 2.26”D
DIN Rail CompatibilityPR30 (TS 35/F6)
Optional Industrial EnclosureNEMA 4X / IP65, polycarbonate, 7.78”H x 7.78”W x 4.8”D (EMX-ENC)
Compliance
AgencyUL Listed, cUL Listed, File E489498
StandardsRoHS, CE (requires metal enclosure)
Trade ComplianceMade in USA – Buy American Act, BABAA, ARRA §1605, and TAA conformant (see declaration)

Documentation

Related Senva Metering Products

Senva EMX

The flagship model — RS-485 (BACnet MS/TP, Modbus RTU/ASCII), color OLED display, logging, RTC, and dual pulse outputs.

Senva EMX-IP

The Ethernet version — BACnet IP and Modbus TCP/IP over 10/100 Base-T, same revenue-grade engine, display, and logging.

Metering Series Rogowski CTs

Flexible 6000A-rated Rogowski coils for the EMX series in 9” (CT-F09), 15” (CT-F15), 24” (CT-F24), and 36” (CT-F36) circumferences.

Senva EM-RS485

Compact CVT-based alternative — fully low-voltage meter base with plug-and-play BACnet MS/TP and Modbus RTU.

Frequently Asked Questions

Is the Senva EMX-L a revenue-grade meter?

Yes. The EMX-L meets ANSI C12.20 Class 0.2 standards (0.2% meter accuracy), commonly referred to as ANSI revenue grade, making it suitable for tenant submetering and billing applications.

How do I configure the EMX-L without a display?

Through the SenvaSync app on iOS or Android over NFC. All settings — service type, CT assignment, protocol, addressing — are handled in the app, and configuration works even while the meter is powered off.

Does the EMX-L log data?

No. The EMX-L omits onboard logging and the real-time clock. Energy and power values are read live over BACnet MS/TP or Modbus, so trending and history are handled by the connected BAS or data acquisition system. If onboard logging is needed, choose the standard EMX.

What is the difference between the EMX-L and the EMX?

The EMX-L shares the EMX terminals, RS-485 protocols (BACnet MS/TP, Modbus RTU/ASCII), pulse inputs, and pulse outputs, but removes the OLED display, data logging, and RTC for a simplified, lower-cost installation.

Does the EMX-L work with my existing CTs?

Yes. The EMX-L accepts any standard 0.333V output CT as well as standard metering Rogowski coils, with no external integrators required.

Is the Senva EMX-L Buy American Act compliant?

Yes. The EMX series is manufactured in the USA by Senva in Beaverton, Oregon, and conforms to the Buy American Act, Build America Buy America Act (BABAA), ARRA Section 1605, and the Trade Agreements Act (TAA). The signed 2026 conformance declaration is available in the documentation section above.

Product Line:
EMX Series
Product Type:
Energy Meter
Protocol:
BACnet MS/TP
Protocol:
Modbus RTU
Protocol:
Modbus ASCII
Mounting:
DIN Rail
Revenue Grade:
Yes
Pulse Outputs:
Yes
Country of Origin:
USA