Senva TGD-ACN-A : Duct Mount Dual Toxic Gas CO/NO2 Sensor/Controller, 0-10V, 0-5V, 1-5V and 4-20mA Selectable Output, LCD Display, Clear/Tinted Enclosure, 7-Year Warranty
The Senva TGD-ACN-A is a duct mount dual toxic gas CO/NO2 sensor/controller designed for precise monitoring and control. with selectable outputs including 0-10V, 0-5V, 1-5V, and 4-20mA. TGD-ACN-A includes an LCD display that provides clear visibility of readings. Operating on a power supply of 15-30VDC/24VAC, the sensor/controller features programmable analog outputs and adjustable scaling for CO and NO2 outputs. It includes a fan relay with customizable setpoints and an alarm relay for enhanced safety. The 3-1/2 digit LCD displays CO and NO2 levels, while LEDs indicate normal, warning/fan relay, and alarm/alarm relay statuses. Equipped with a reliable electrochemical CO sensor and an electrochemical NO2 sensor, both with a lifespan exceeding 7 years, this device ensures accurate monitoring. The enclosure, made of ABS/Polycarbonate, is suitable for wall and duct installations, conforming to UL61010-1, UL, cUL, and CE compliance standards. With a coverage area of 5000-7500 square feet, this sensor/controller guarantees efficient and long-lasting toxic gas monitoring within proximity to a Senva TG sensor.
Applications
- Ensure adequate air flow in occupied spaces
- Ideal fo parking lot garages
- Monitor multiple toxic gases with one mounted unit
- Alert occupants of elevated gas levels
- Directly control exhaust fans
Specifications
Power Supply | 15-30VDC/24VAC(1), 4W max, 160mA max. |
Analog Outputs | |
2 programmable outputs | 0-10V (default), 0-5V, 1-5V and 4-20mA (menu selectable) |
CO output scaling | 0-200ppm (default), 0-1000ppm (menu selectable) |
NO2 output scaling | 0-10ppm (default), 0-30ppm (menu selectable) |
Fan Relay | |
Fan relay characteristics | N.C. 1A@24/30VDC (50/60Hz) (no mains connection) |
CO fan relay setpoint | 25ppm (default), 0-1000 ppm (menu selectable) |
NO2 fan relay setpoint | 1ppm (default), 0-30ppm (menu selectable) |
Alarm Relay | |
Alarm relay characteristics | N.C. 1A@24/30VDC (50/60Hz) (no mains connection) |
CO alarm relay setpoint | 100ppm (default), 0-1000 ppm (menu selectable) |
NO2 alarm relay setpoint | 3ppm (default), 0-30ppm (menu selectable) |
Display | |
3-1/2 digit LCD | Indicates CO ppm, NO2 ppm (menu selectable) |
LEDs | |
Green, Yellow, Red | Green = Normal, Yellow = Warning/Fan Relay, Red = Alarm/Alarm Relay |
Audible Alarm Exposure | |
85dB Piezo transducer | 30 minutes above alarm setpoint per UL2034 (menu selectable) |
CO Sensor Performance | |
Type | Electrochemical |
Accuracy | ±5% of default range(2) ±5%of reading above 200ppm |
Resolution | 1ppm |
Certifications | UL2034 Listed Component |
Life expectancy | >7 years |
Coverage Area | 5000-7500 square feet (placed within 50' apart from a Senva TG sensor) |
NO2 Sensor Performance | |
Type | Electrochemical |
Accuracy | ±5% of default range(3) ±5%of reading above 20ppm |
Resolution | 0.1ppm |
Life expectancy | >7 years |
Coverage Area | 5000-7500 square feet (placed within 50' apart from a Senva TG sensor.) |
Enclosure (Wall & Duct) | |
Material | ABS/Polycarbonate |
Dimensions | 4.0”h x 4.4”w x 2.1”d (+6.8” probe for duct version) |
Conduit Opening | Tapped 1/2” NPT |
Rating | IP20 |
Compliance | UL61010-1 Listed UL, cUL, CE |
Datasheets
- Enclosure Style:
- Duct
- Gas Element:
- Carbon Monoxide / Nitrogen Dioxide
- Analog Output:
- 2
- Relay Output:
- 2 SPDT
- Communication:
- None
- Display:
- LCD Display