Senva TGD-ANX-A : Duct Mount Toxic Gas NO2 Sensor/Controller, 0-10V, 0-5V, 1-5V and 4-20mA Selectable Output, LCD Display, Clear/Tinted Enclosure, 7-Year Warranty
The Senva TGD-ANX-A is a duct mount toxic gas NO2 sensor/controller featuring selectable outputs in the range of 0-10V, 0-5V, 1-5V, and 4-20mA. Equipped with an 3-1/2 digit LCD display indicating NO2 ppm, and LEDs for normal, warning/fan relay, and alarm/alarm relay status. The TGD-ANX-A comes with a 7-year warranty. The power supply specifications include a range of 15-30VDC/24VAC. The analog outputs are programmable, and the NO2 output scaling can be set to 0-10ppm (default) or 0-30ppm. An audible alarm with a 85dB piezo transducer is available, and the NO2 sensor, based on electrochemical technology, offers an accuracy of ±5% of the default range and a resolution of 0.1ppm. The sensor has a life expectancy of over 7 years and covers an area of 5000-7500 square feet. It complies with UL61010-1 standards and is listed UL, cUL, and CE.
Applications
- Ensure adequate air flow in occupied spaces
- Ideal fo parking lot garages
- Alert occupants of elevated gas levels
- Directly control exhaust fans
Specifications
| Power Supply | 15-30VDC/24VAC(1), 4W max, 160mA max. |
| Analog Outputs | |
| Programmable Outputs | 0-10V (default), 0-5V, 1-5V and 4-20mA (menu selectable) |
| NO2 output scaling | 0-10ppm (default), 0-30ppm (menu selectable) |
| Fan Relay | |
| Fan relay characteristics | N.C. 1A@24/30VDC (50/60Hz) (no mains connection) |
| NO2 fan relay setpoint | 1ppm (default), 0-30ppm (menu selectable) |
| Alarm Relay | |
| Alarm relay characteristics | N.C. 1A@24/30VDC (50/60Hz) (no mains connection) |
| NO2 alarm relay setpoint | 3ppm (default), 0-30ppm (menu selectable) |
| Display | |
| 3-1/2 digit LCD | Indicates NO2 ppm (menu selectable) |
| LEDs | |
| Green, Yellow, Red | Green = Normal, Yellow = Warning/Fan Relay, Red = Alarm/Alarm Relay |
| Audible Alarm Exposure | |
| 85dB Piezo transducer | 30 minutes above alarm setpoint per UL2034 (menu selectable) |
| NO2 Sensor Performance | |
| Type | Electrochemical |
| Accuracy | ±5% of default range(3) ±5%of reading above 20ppm |
| Resolution | 0.1ppm |
| Life expectancy | >7 years |
| Coverage Area | 5000-7500 square feet (placed within 50' apart from a Senva TG sensor.) |
| Enclosure (Wall & Duct) | |
| Material | ABS/Polycarbonate |
| Dimensions | 4.0”h x 4.4”w x 2.1”d (+6.8” probe for duct version) |
| Conduit Opening | Tapped 1/2” NPT |
| Rating | IP20 |
| Compliance | UL61010-1 Listed UL, cUL, CE |
Datasheets
- Enclosure Style:
- Duct
- Gas Element:
- Nitrogen Dioxide
- Analog Output:
- 2
- Relay Output:
- 2 SPDT
- Communication:
- None
- Display:
- LCD Display