Senva TGW-ANX-AW : Wall Mount Toxic Gas NO2 Sensor/Controller, 0-10V, 0-5V, 1-5V and 4-20mA Selectable Output, LCD Display, All White Solid Enclosure, 7-Year Warranty
Senva UL Listed TG Series sensors can be ordered as individual CO or NO2 sensors or as a combination CO/NO2 sensor in a shared enclosure. The analog output model features 2 outputs that support daisy chain wiring - multiple sensors may be used in a parallel sequence (0-10V) for cost effective coverage of large areas. The unit can also act as a stand alone controller, utilizing the relay for exhaust fan operation or the output for direct control of a VFD. The BACnet/Modbus model supports BACnet MS/TP & Modbus network communication in one unit. Standard features include network auto-configuration, a programmable fan relay, LED indicators, integrated display and audible alarm.
APPLICATIONS
- Ensure adequate air flow in occupied spaces
- Ideal fo parking lot garages
- Monitor multiple toxic gases with one mounted unit
- Alert occupants of elevated gas levels
- Directly control exhaust fans
Power Supply | 15-30VDC/24VAC(1), 4W max, 160mA max. | |
Analog Outputs | 2 programmable outputs | 0-10V (default), 0-5V, 1-5V and 4-20mA (menu selectable) |
CO output scaling | 0-200ppm (default), 0-1000ppm (menu selectable) | |
NO2 output scaling | 0-10ppm (default), 0-30ppm (menu selectable) | |
Temperature output scaling | -20 to 85oC | |
BACnet /Modbus | Protocol RS-485 | BACnet MS/TP, Modbus RTU, Modbus ASCII |
Baud Rates | 9600, 19200, 38400, 57600, 76800, 115200 | |
Fan Relay | Fan relay characteristics | N.C. 1A@24/30VDC (50/60Hz) (no mains connection) |
CO fan relay setpoint | 25ppm (default), 0-1000 ppm (menu selectable) | |
NO2 fan relay setpoint | 1ppm (default), 0-30ppm (menu selectable) | |
Alarm Relay | Alarm relay characteristics | N.C. 1A@24/30VDC (50/60Hz) (no mains conenction) |
CO alarm relay setpoint | 100ppm (default), 0-1000 ppm (menu selectable) | |
NO2 alarm relay setpoint | 3ppm (default), 0-30ppm (menu selectable) | |
Display | 3-1/2 digit LCD | Indicates CO ppm, NO2 ppm (menu selectable) |
LEDs | Green, Yellow, Red | Green = Normal, Yellow = Relay, Red = Alarm |
Audible Alarm Exposure | 85dB Piezo transducer | 30 minutes above alarm setpoint per UL2034 (menu selectable) |
CO Sensor Performance | Type | Electrochemical |
Accuracy | ±5% of default range(2) ±5%of reading above 200ppm | |
Resolution | 1ppm | |
Certifications | UL2034 Listed Component | |
Life expectancy | >7 years | |
Coverage Area | 5000-7500 square feet | |
NO2 Sensor Performance | Type | Electrochemical |
Accuracy | ±5% of default range(3) ±5%of reading above 20ppm | |
Resolution | 0.1ppm | |
Life expectancy | >7 years | |
Coverage Area | 5000-7500 square feet | |
Carbon Dioxide (CO2) | Type | Non-Dispersive Infrared (NDIR) |
Accuracy(4) | ±(30ppm +3% of reading) (400-2000ppm), @-10-50°C ±(50ppm +5% of reading) Standard (2000-5000ppm), ±(50ppm+3% of reading) Dual Channel (2000-5000ppm), ±(100ppm+10% of reading) (5000-10000ppm) | |
Resolution | 1 ppm | |
Life expectancy | 15 years | |
Coverage Area | 5000-7500 square feet | |
Operating Environment | Temperature, continuous | -20 to 50oC |
Humidity | 15-95% continuous, 0-95% intermittent | |
Max Elevation | 2000m | |
Enclosure (Wall & Duct) | Material | ABS/Polycarbonate |
Dimensions | 4.0”h x 4.4”w x 2.1”d (+6.8” probe for duct version) | |
Conduit Opening | Tapped 1/2” NPT | |
Rating | IP20 | |
Enclosure (Metal) | Material & Enclosure Rating | Powder coated steel/acrylic, NEMA 3R |
Dimensions | 5.0”h x 4.3”w x 2.25”d | |
Opening | Dual air vents on bottom of enclosure | |
Mounting | Pre-drilled for 2x4” electrical box | |
Rating | IP20 | |
Agency | Compliance | UL61010-1 Listed UL, cUL, CE |
Datasheets
- Enclosure Style:
- Wall
- Gas Element:
- Nitrogen Dioxide
- Analog Output:
- 2
- Relay Output:
- 2 SPDT
- Communication:
- None
- Display:
- LCD Display