Senva TGW-BCX-AS : Wall Mount Toxic Gas CO Sensor/Controller, BACnet MS/TP, Modbus RTU, Modbus ASCII Output, LCD Display, Solid/Opaque Enclosure, 7-Year Warranty
Applications
- Ensure adequate air flow in occupied spaces
- Ideal fo parking lot garages
- Alert occupants of elevated gas levels
- Directly control exhaust fans
Specifications
| Power Supply | 15-30VDC/24VAC(1), 4W max, 160mA max. |
| BACnet /Modbus | |
| Protocol RS-485 | BACnet MS/TP, Modbus RTU, Modbus ASCII |
| Baud Rates | 9600, 19200, 38400, 57600, 76800, 115200 |
| Fan Relay | |
| Fan relay characteristics | N.C. 1A@24/30VDC (50/60Hz) (no mains connection) |
| CO fan relay setpoint | 25ppm (default), 0-1000 ppm (menu selectable) |
| Alarm Relay | |
| Alarm relay characteristics | N.C. 1A@24/30VDC (50/60Hz) (no mains connection) |
| CO alarm relay setpoint | 100ppm (default), 0-1000 ppm (menu selectable) |
| Display | |
| 3-1/2 digit LCD | Indicates CO ppm (menu selectable) |
| LEDs | |
| Green, Yellow, Red | Green = Normal, Yellow = Warning/Fan Relay, Red = Alarm/Alarm Relay |
| Audible Alarm Exposure | |
| 85dB Piezo transducer | 30 minutes above alarm setpoint per UL2034 (menu selectable) |
| CO Sensor Performance | |
| Type | Electrochemical |
| Accuracy | ±5% of default range(2) ±5%of reading above 200ppm |
| Resolution | 1ppm |
| Certifications | UL2034 Listed Component |
| Life expectancy | >7 years |
| Coverage Area | 5000-7500 square feet (placed within 50' apart from a Senva TG sensor) |
| Enclosure (Wall & Duct) | |
| Material | ABS/Polycarbonate |
| Dimensions | 4.0”h x 4.4”w x 2.1”d (+6.8” probe for duct version) |
| Conduit Opening | Tapped 1/2” NPT |
| Rating | IP20 |
| Compliance | UL61010-1 Listed UL, cUL, CE |
Datasheets
- Enclosure Style:
- Wall
- Gas Element:
- Carbon Monoxide
- Analog Output:
- None
- Relay Output:
- 2 SPDT
- Communication:
- BACnet/Modbus
- Display:
- LCD Display