ACI A/SCTA2-5 : Split-Core 4 to 20 mA Output Analog Current Sensor, 0 to 5 A Range, 4 to 20 mA (2-wire, loop powered), Average Measurement, 5-Year Warranty

ACI

Your Price:  $0.00
(No reviews yet) Write a Review
SKU:
A/SCTA2-5
Condition:
New
Availability:
Discontinued - Contact Us
This product is discontinued
ACI has discontinued the A/SCTA2-5. It is no longer available to order. No direct replacement identified. Contact ZOT Supply to confirm the correct current-sensing configuration for your application.
ACI documents the A/SCTA2-5 for a specific external 5 A current transformer application, used when the monitored current exceeds 250 A or the conductor exceeds 0.750 in (1.90 cm), so another A/SCTA2 model should not be substituted without reviewing the installation.
Not sure which part fits? Call 855-825-2811 or email sales@zotsupply.com and we will match it.
Core StyleSplit-Core
Amperage Range0 to 5 A
Output Signal4 to 20 mA (2-wire, loop powered)
MeasurementAverage · Pure Sinusoidal
Accuracy+/- 1% of selected range
Warranty5-Year Limited

ACI A/SCTA2-5 4 to 20 mA Output Analog Current Sensor

The ACI A/SCTA2-5 is a split-core AC analog current sensor that converts 0 to 5 A into a 4 to 20 mA (2-wire, loop powered) signal using average measurement. Accuracy is +/- 1% of selected range.

The A/SCTA2-5 uses averaging measurement, which assumes a pure sinusoidal waveform with little or no distortion on the monitored conductor. It is the correct and lower-cost choice for resistive and single-speed linear loads such as incandescent lighting, heating elements and across-the-line motors. Where the load is fed by a VFD or a switching supply, ACI directs users to the True RMS A/CTA2-RMS or A/SCTA2-RMS series instead.

ACI's Standard Ordering grid lists a single 0 to 5 A range for the A/SCTA2-5. There is no range jumper to set on this model.

The output is a 2-wire, loop-powered 4 to 20 mA signal, which needs an external +8.5 to 30 VDC supply. ACI specifies a maximum run of 30 m (98.4 ft) of 2-conductor shielded cable between the sensor and the building management system. Where the controller input expects a voltage signal, ACI publishes 249 Ohm and 499 Ohm precision resistors that convert the loop to 1 to 5 VDC or 2 to 10 VDC at the panel.

ACI documents a specific pairing for this model: where the normal operating current exceeds 250 A, or the monitored conductor is larger than 0.750 in (1.90 cm) in diameter, an external Ratio:5 A output current transformer is used to step the load current down to a proportional 0 to 5 A signal, and the A/SCTA2-5 scales that 0 to 5 A secondary to 4 to 20 mA. ACI does not state that an external transformer is required in every application.

The split-core housing opens around an existing conductor, so the A/SCTA2-5 can be fitted to wiring that is already terminated. All power sources must be disconnected and locked out before installation. That makes it the practical choice for retrofit and service work.

Specifications on this page are taken from the ACI 4-20 mA Output Current Sensor Series Installation & Operation Instructions I0000789 Rev. 9.0, which is the last published revision to carry this model in its Standard Ordering grid, with product weight taken from the ACI 4-20 mA Output product specifications published at workaci.com.

Best For

  • Load trending and basic power monitoring on single-speed linear loads
  • LEED documentation and energy project ROI justification
  • Continuous amperage feedback to a BMS, PLC or DDC analog input
  • Preventative maintenance programs that need measured current, not just on/off status

Warranty

Five (5) Year Limited Warranty. Covered by ACI's Five (5) Year Limited Warranty. The warranty is published in the front of ACI's Sensors & Transmitters catalog and on the ACI website.

Key Features

Average Measurement

Averaging measurement for pure sinusoidal waveforms. Correct and cost-effective on resistive and single-speed linear loads.

0 to 5 A Range

ACI's Standard Ordering grid lists a single 0 to 5 A range for this model, with no range jumper to set at commissioning.

4 to 20 mA (2-wire, loop powered) Output

Loop-powered 2-wire signal on 2-conductor shielded cable, up to the 30 m (98.4 ft) run ACI specifies. Optional 249 Ohm and 499 Ohm resistors convert to 1 to 5 VDC or 2 to 10 VDC at the panel.

Split-Core Aperture

Opens around an existing conductor for retrofit installation without disconnecting any wiring.

Works With an External 5 A CT

Where ACI specifies an external Ratio:5 A output current transformer — above 250 A, or on conductors larger than 0.750 in (1.90 cm) — this sensor scales the transformer's 0 to 5 A secondary to 4 to 20 mA.

Published Accuracy

+/- 1% of selected range. All current output sensors are calibrated at an ambient room temperature of 71 °F (21.5 °C).

Technical Specifications

ACI Item Number142376
Core StyleSplit-Core
Sensor Amperage Range0 to 5 A
Measurement MethodAverage
AC WaveformPure Sinusoidal
Output Signal4 to 20 mA (2-wire, loop powered)
Accuracy+/- 1% of selected range
Operating Frequency Range40 Hz to 1000 Hz
Response Time< 600 mS (rise and fall time)
Monitored Current TypeAC Current
Maximum AC Voltage600 VAC
Isolation Voltage2200 VAC
Supply Voltage+8.5 to 30 VDC (reverse polarity protected); 250 Ohm load (1 to 5 VDC): +13.5 to 30 VDC; 500 Ohm load (2 to 10 VDC): +18.5 to 30 VDC
Supply Current25 mA minimum
Maximum Load Resistance @ 24 VDC775 Ohms (formula: (24 VDC - 8.5 VDC) / 0.020 A)
Output Signal | Maximum Output4 to 20 mA (2-wire, loop powered) | limited to 25 mA
Aperture Size0.75 in (19.05 mm)
DIN Rail Size35 mm (U.S. Patent No. 7,416,421)
Operating Temperature Range5 to 104 °F (-15 to 40 °C)
Operating Humidity Range0 to 95% RH, non-condensing
Storage Temperature | RH Range41 to 95 °F (5 to 35 °C) | 40 to 85% RH, non-condensing
Enclosure Material | Flammability RatingPC/ABS (polycarbonate / ABS blend) | UL94-V0
Wiring Connections2-position screw terminal block (polarity sensitive)
Wire Recommendations2-conductor shielded cable
Wire Size18 to 24 AWG (0.823 mm2 to 0.205 mm2), copper wires only
Terminal Block Torque Rating4.43 to 5.31 in-lbs (0.5 to 0.6 Nm)
Minimum Mounting Distance1 in (2.6 cm) from relays, contactors and transformers
Calibration ReferenceAll current output sensors are calibrated at an ambient room temperature of 71 °F (21.5 °C)
Agency ApprovalsUL/CUL US Listed (UL 508) Industrial Control Equipment, File # E309723, RoHS2, WEEE, UKCA; -RMS versions CE to IEC 61326-1:2012 Class A
Product Dimensions (L x W x H)2.780 in (70.51 mm) x 3.238 in (82.25 mm) x 1.120 in (28.45 mm)
Product Weight0.274 lbs (0.124 kg)
WarrantyFive (5) Year Limited Warranty

Not intended for use in life / safety applications or in hazardous / classified locations.

Disconnect and lock out all power sources before installation. Required by the ACI Installation & Operation Instructions. Installation must be performed by qualified personnel in compliance with all national and local electrical codes.

Output Conversion Resistors (ordered separately)

ACI Item #Description
100307249 Ohm, 1/4 W, +/- 1% tolerance, 50 ppm resistor (converts output to 1 to 5 VDC)
100306249 Ohm, 1/4 W, +/- 0.1% tolerance, 50 ppm resistor, recommended for best accuracy (converts output to 1 to 5 VDC)
100469499 Ohm, 1 W, +/- 1% tolerance, 50 ppm resistor (converts output to 2 to 10 VDC)

Documentation

Frequently Asked Questions

What output signal does the ACI A/SCTA2-5 produce?

The A/SCTA2-5 produces a 4 to 20 mA (2-wire, loop powered) signal. It is loop powered and needs an external +8.5 to 30 VDC supply.

What amperage range does the ACI A/SCTA2-5 cover?

ACI's Standard Ordering grid lists a single 0 to 5 A range for the A/SCTA2-5. There is no range selection jumper to set on this model.

Can the ACI A/SCTA2-5 be used downstream of a variable frequency drive?

No. This sensor uses averaging measurement, which assumes a pure sinusoidal waveform. For VFDs, switching power supplies and other distorted waveforms, ACI directs users to the True RMS A/CTA2-RMS or A/SCTA2-RMS series.

When does the ACI A/SCTA2-5 need an external current transformer?

For applications above 250 A, or where the monitored conductor exceeds 0.750 in (1.90 cm), ACI instructs using an external Ratio:5 A output current transformer and the A/SCTA2-5 to scale the transformer's 0 to 5 A secondary to a 4 to 20 mA signal. The transformer is ordered separately. ACI does not state that an external transformer is required in every application.

What is the published accuracy of the ACI A/SCTA2-5?

+/- 1% of selected range. All ACI current output sensors are calibrated at an ambient room temperature of 71 °F (21.5 °C).

ACI Five (5) Year Limited Warranty. This product is covered by Automation Components, Inc.’s Five (5) Year Limited Warranty, published in the front of the ACI Sensors & Transmitters catalog and on the ACI website. Warranty terms are set by the manufacturer and are subject to change without notice.

Mounting Type:
Split-Core
Amp Range:
0-5A
Output Signal:
4-20 mA
Measurement:
Average
AC Waveform:
Pure Sinusoidal
Sensor Power:
Loop Powered
Warranty:
5-Year Limited